TeSys K contactor - 4P(4 NO) - AC-1 -

CONTACTOR 600VAC 12AMP IEC +OP

SQDLC1K12004T7 LC1K12004T7 785901790143
129.56 / EA
http://schema.org/OutOfStock
  • Certifications: CSA, UL
  • Control Circuit Voltage: 480 V
  • Depth: 2.24 in, 57 mm
  • Height: 2.28 in, 58 mm
  • IP Rating: IP2x
  • Package Quantity: 1
  • Package Weight: 0.40 lb
  • Rated Insulation Voltage: 600 V, 690 V
  • Weight: 0.18 kg, 0.4 lb
  • Width: 1.77 in, 45 mm
QTY
  • Specifications
  • Main
    • Commercial Status : Commercialised
    • Range of product : TeSys K
    • Product or component type : Contactor
    • Device short name : LC1K
    • Contactor application : Resistive load
    • Utilisation category : AC-1
    • Poles description : 4P
    • Pole contact composition : 4 NO
    • [Ue] rated operational voltage : 690 V AC 50/60 Hz for power circuit
    • [Ie] rated operational current : 16 A ( 20 A (
    • Control circuit type : AC 50/60 Hz
    • Control circuit voltage : 480 V AC 50/60 Hz
    • [Uimp] rated impulse withstand voltage : 8 kV
    • Overvoltage category : III
    • [Ith] conventional free air thermal current : 20 A at
    • Irms rated making capacity : 144 A AC for power circuit conforming to IEC 60947
    • Irms rated making capacity : 144 A AC for power circuit conforming to NF C 63-110
    • Rated breaking capacity : 70 A at 660...690 V conforming to IEC 60947
    • Rated breaking capacity : 80 A at 500 V conforming to IEC 60947
    • Rated breaking capacity : 110 A at 440 V conforming to IEC 60947
    • [Icw] rated short-time withstand current : 25 A = 15 s power circuit
    • [Icw] rated short-time withstand current : 50 A 55 A 75 A 100 A 105 A 115 A
    • Associated fuse rating : 25 A aM for power circuit
    • Associated fuse rating : 25 A gG at
    • Average impedance : 3 mOhm at 50 Hz - Ith 20 A for power circuit
    • [Ui] rated insulation voltage : 600 V for power circuit conforming to CSA C22.2 No 14
    • [Ui] rated insulation voltage : 690 V for power circuit conforming to IEC 60947-4-1
    • [Ui] rated insulation voltage : 600 V for power circuit conforming to UL 508
    • Electrical durability : 0.3 Mcycles 20 A AC-1 at Ue
    • Mounting support : Plate
    • Mounting support : Rail
    • Standards : BS 5424
    • Standards : IEC 60947
    • Standards : NF C 63-110
    • Standards : VDE 0660
    • Product certifications : CSA
    • Product certifications : UL
    • Connections - terminals : Screw clamp terminals 2 cable(s) 0...0 in² (0.34...1.5 mm²) - cable stiffness: flexible - with cable end
    • Connections - terminals : Screw clamp terminals 2 cable(s) 0...0.01 in² (0.75...4 mm²) - cable stiffness: flexible - without cable end
    • Connections - terminals : Screw clamp terminals 2 cable(s) 0...0.01 in² (1.5...4 mm²) - cable stiffness: solid
    • Connections - terminals : Screw clamp terminals 1 cable(s) 0...0 in² (0.34...2.5 mm²) - cable stiffness: flexible - with cable end
    • Connections - terminals : Screw clamp terminals 1 cable(s) 0...0.01 in² (0.75...4 mm²) - cable stiffness: flexible - without cable end
    • Connections - terminals : Screw clamp terminals 1 cable(s) 0...0.01 in² (1.5...4 mm²) - cable stiffness: solid
    • Tightening torque : 11.5 lbf.in (1.3 N.m) - on screw clamp terminals - with screwdriver flat Ø 6 mm
    • Tightening torque : 11.5 lbf.in (1.3 N.m) - on screw clamp terminals - with screwdriver Philips No 2
    • Operating time : 10...20 ms coil energisation and NO closing
    • Operating time : 10...20 ms coil de-energisation and NO opening
    • Safety reliability level : B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
    • Safety reliability level : B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
    • Mechanical durability : 10 Mcycles
    • Operating rate : 3600 cyc/h
  • Complementary
    • Control circuit voltage limits : 0.2...0.75 Uc at 0.8...1.15 Uc at
    • Inrush power in VA : 30 VA at 68 °F (20 °C)
    • Hold-in power consumption in VA : 4.5 VA at 68 °F (20 °C)
    • Heat dissipation : 1.3 W
  • Environment
    • IP degree of protection : IP2x conforming to VDE 0106
    • Protective treatment : TC conforming to DIN 50016
    • Protective treatment : TC conforming to IEC 60068
    • Ambient air temperature for operation : -13...122 °F (-25...50 °C)
    • Ambient air temperature for storage : -58...176 °F (-50...80 °C)
    • Operating altitude : 6561.68 ft (2000 m) without derating in temperature
    • Flame retardance : Requirement 2 conforming to NF F 16-102
    • Flame retardance : Requirement 2 conforming to NF F 16-101
    • Flame retardance : V1 conforming to UL 94
    • Mechanical robustness : Vibrations contactor opened 2 Gn, 5...300 Hz IEC 60068-2-6
    • Mechanical robustness : Vibrations contactor closed 4 Gn, 5...300 Hz IEC 60068-2-6
    • Mechanical robustness : Shocks contactor opened, on Z axis 10 Gn for 11 ms IEC 60068-2-27
    • Mechanical robustness : Shocks contactor opened, on Y axis 10 Gn for 11 ms IEC 60068-2-27
    • Mechanical robustness : Shocks contactor opened, on X axis 6 Gn for 11 ms IEC 60068-2-27
    • Mechanical robustness : Shocks contactor closed, on Z axis 15 Gn for 11 ms IEC 60068-2-27
    • Mechanical robustness : Shocks contactor closed, on Y axis 15 Gn for 11 ms IEC 60068-2-27
    • Mechanical robustness : Shocks contactor closed, on X axis 10 Gn for 11 ms IEC 60068-2-27
    • Height : 2.28 in (58 mm)
    • Width : 1.77 in (45 mm)
    • Depth : 2.24 in (57 mm)
    • Product weight : 0.4 lb(US) (0.18 kg)
  • Ordering and Shipping Details
    • Category : 22326 - CTR,K-LINE,AC,OPEN,NONREV
    • Discount Schedule : I12
    • GTIN : 00785901790143
    • Nbr. of units in pkg. : 1
    • Package weight(Lbs) : 0.40
    • Product availability : Non-Stock - Not normally stocked in distribution facility
    • Returnability : N
    • Country of origin : FR
  • Offer Sustainability
    • Sustainable offer status : Green Premium product
    • RoHS : Compliant - since 0640 -
    • RoHS : Schneider Electric declaration of conformity
    • REACh : Reference not containing SVHC above the threshold
    • Product environmental profile : Available
    • Product environmental profile : Download Product environmental
    • Product end of life instructions : Need no specific recycling operations
  • Contractual Warranty
    • Period : 18 months