Schneider Electric at Mayer

TeSys GB2 thermal magnetic circuit protector, 2 P, 2 A, Id = 26 A

CIRCUIT PROTECTOR 277VAC 2A GB

SQDGB2DB07 GB2DB07 3389110865424
92.49 / EA
http://schema.org/OutOfStock
  • Country of Origin: France
  • Depth: 70 mm
  • Height: 74 mm
  • Net Weight: 0.115 kg
  • Warranty Length: 18 mth
  • Weight: 0.115 kg
  • Width: 30 mm
TeSys GB circuit breaker, 2 poles (2P), 2A/415V, for the protection of industrial equipment control circuits. It provides thermal magnetic protection with a magnetic tripping level at 26A (13 In) and breaking capacity Icu 15kA@415V. It can also be used for protection of DC loads up to 2A/48V DC-13 with a breaking capacity Icu 1.5kA@24V. Compact device (30mm wide), mounting on 35mm DIN-rail, control by toggle lever (start-stop guaranteed for 8000 cycles). Sold in lots of 3 units. It conforms to IEC 60947-1 and IEC 60947-2.
QTY
  • Product Description
  • Features
  • Specifications
TeSys GB circuit breaker, 2 poles (2P), 2A/415V, for the protection of industrial equipment control circuits. It provides thermal magnetic protection with a magnetic tripping level at 26A (13 In) and breaking capacity Icu 15kA@415V. It can also be used for protection of DC loads up to 2A/48V DC-13 with a breaking capacity Icu 1.5kA@24V. Compact device (30mm wide), mounting on 35mm DIN-rail, control by toggle lever (start-stop guaranteed for 8000 cycles). Sold in lots of 3 units. It conforms to IEC 60947-1 and IEC 60947-2.
  • Prop 65
    • WARNING: Cancer - www.P65Warnings.ca.gov
  • Environment
    • Ambient Air Temperature For Operation : -20-60 °C
    • Standards : EN/IEC 60947-1 || EN/IEC 60947-2
    • Ambient Air Temperature For Storage : -40-80 °C
    • Protective Treatment : TC
    • Ip Degree Of Protection : IP20 IEC 60529
    • Operating Altitude : 9842.52 ft (3000 m)
    • Fire Resistance : 960 °C IEC 60695-2-1
  • Contractual warranty
    • Warranty : 18 months
  • Environmental data
    • Rohs Exemption Information : Yes
    • Packaging Made With Recycled Cardboard : Yes
    • Mercury Free : Yes
    • Environmental Disclosure : ENVPEP2306022EN
    • Halogen Content Performance : Halogen free plastic parts product
    • Packaging Without Single Use Plastic : Yes
    • Weee Label : The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
    • Toxic Heavy Metal Free : Yes
    • Reach Regulation : Free of Substances of Very High Concern above the threshold
    • California Proposition 65 : WARNING: Cancer - www.P65Warnings.ca.gov
    • Reach Free Of Svhc : Yes
    • Circularity Profile : N/A
    • Take-Back : No
    • Carbon Footprint Of The Use Phase [B2, B3, B4, B6] : 4.727441133499354
    • Carbon Footprint Of The Manufacturing Phase [A1 To A3] : 0.7578613630612782
    • Carbon Footprint Of The Distribution Phase [A4] : 0 kg CO2 eq.
    • Carbon Footprint Of The Installation Phase [A5] : 0 kg CO2 eq.
    • Sustainable Packaging : Yes
    • Total Lifecycle Carbon Footprint : 6 kg CO2 eq.
    • Eu Rohs Directive : Compliant
    • Carbon Footprint Of The End-Of-Life Phase [C1 To C4] : 0.2867915999350902
    • Carbon Footprint (Kg Co2 Eq, Total Life Cycle) : 5.803104794905507
  • Complementary
    • Mechanical Robustness : shocks 22 Gn for 20 ms IEC 60068-2-27 || vibrations 5 Gn, 5...110 Hz IEC 60068-2-6
    • Line Rated Current : 2 A
    • [Ue] Rated Operational Voltage : 415 V AC 50/60 Hz IEC 60947-2 || 48 V DC
    • Height : 74 mm
    • Mounting Support : rail || plate
    • 9 Mm Pitches : 4
    • Net Weight : 0.115 kg
    • Connections - Terminals : connector 1 0.75-6 mm²solid without cable end || connector 2 0.75-4 mm²solid without cable end || connector 1 0.75-4 mm²flexible with cable end || connector 2 0.75-2.5 mm²flexible with cable end
    • [Uimp] Rated Impulse Withstand Voltage : 4 kV IEC 60947-2
    • Control Type : toggle
    • Power Dissipation Per Pole : 2 W
    • Electrical Durability : 8000 cycles
    • Mounting Mode : by clips
    • Tightening Torque : 1.2 N.m connector
    • Mechanical Durability : 8000 cycles
    • Quantity Per Set : set of 3
    • Mounting Position : vertical || horizontal
    • Width : 30 mm
    • Depth : 70 mm
  • Specifications
    • Country of Origin : France
    • Width : 30 mm
    • Height : 74 mm
    • Weight : 0.115 kg
    • Network Type : AC/DC
    • Magnetic Tripping Current : 26-26 A
    • Product Or Component Type : circuit breaker
    • Product Name : TeSys GB2
    • Utilisation Category : category A IEC 60947-2 || DC-12 IEC 60947-5-1 || DC-13 IEC 60947-5-1
    • Range : TeSys
    • [Ics] Rated Service Short-Circuit Breaking Capacity : 25 % 230/240 V AC 50/60 Hz IEC 60947-2 || 25 % 400/415 V AC 50/60 Hz IEC 60947-2
    • Breaking Capacity : 10 kA Icu 230/240 V AC 50/60 Hz IEC 60947-2 || 10 kA Icu 400/415 V AC 50/60 Hz IEC 60947-2
    • Poles Description : 2P
    • Network Frequency : 50/60 Hz IEC 60947-2
    • Device Application : control
    • Device Short Name : GB2
    • Trip Unit Technology : thermal-magnetic