IEC contactor, TeSys Deca reversing, 12A, 7.5HP at 480VAC, 3 phase, 3 pole, 3 NO, 120VAC 50/60Hz coil, open style

REVERSING CONTACTOR 575VAC 12A

SQDLC2D12G7V LC2D12G7V 3389110410884
421.08 / EA
http://schema.org/OutOfStock
  • Country of Origin: France
  • Depth: 3.39 in
  • Height: 3.03 in
  • Warranty Length: 18 mth
  • Width: 3.54 in
TeSys Deca contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys Deca contactors are available in 13 contactor ratings for inductive motor applicati
QTY
  • Product Description
  • Features
  • Specifications
TeSys Deca contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys Deca contactors are available in 13 contactor ratings for inductive motor applicati
  • Uc Control Circuit Voltage
    • 120 V AC 50/60 Hz
  • Insulation Resistance
    • > 10 MOhm for signalling circuit
  • Heat Dissipation
    • 2-3 W 50/60 Hz
  • Connections Terminals
    • power circuit screw clamp terminals 1 1-4 mm²flexible without cable end
    • power circuit screw clamp terminals 1
  • Mounting Support
    • plate
    • rail
  • Uimp Rated Impulse Withstand Voltage
    • 6 kV IEC 60947
  • Range Of Product
    • TeSys D
    • TeSys Deca
  • Climatic Withstand
    • IACS E10
    • IEC 60947-1 Annex Q category D
  • Power Dissipation Per Pole
    • 1.56 W AC-1
    • 0.36 W AC-3
  • Maximum Operating Rate
    • 3600 cyc/h 60 °C
  • Prop 65
    • WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
  • Carbon Footprint Of The Installation Phase A5
    • 0.0520461497777044
    • 0.1 kg CO2 eq.
  • Non Overlap Time
    • 1.5 ms on de-energisation between NC and NO contact
    • 1.5 ms on energisation between NC and NO contact
  • Carbon Footprint Of The End Of Life Phase C1 To C4
    • 2 kg CO2 eq.
    • 1.6880716149297996
  • Standards
    • CSA C22.2 No 14
    • EN 60947-4-1
    • EN 60947-5-1
    • IEC 60947-4-1
    • IEC 60947-5-1
    • UL 60335-2-40:Annex JJ
    • IEC 60335-1
  • Ue Rated Operational Voltage
    • power circuit <= 690 V AC 25...400 Hz
    • power circuit <= 300 V DC
  • Ui Rated Insulation Voltage
    • power circuit 690 V IEC 60947-4-1
    • power circuit 600 V CSA
    • power circuit 600 V UL
    • signalling
  • Operating Time
    • 12...22 ms closing
    • 4...19 ms opening
  • Control Circuit Type
    • AC 50/60 Hz
  • Ip Degree Of Protection
    • IP20 front face IEC 60529
  • Minimum Switching Voltage
    • 17 V for signalling circuit
  • Carbon Footprint Of The Manufacturing Phase A1 To A3
    • 4 kg CO2 eq.
    • 4.16336010476112
  • Protective Treatment
    • TH IEC 60068-2-30
  • Average Impedance
    • 2.5 mOhm - Ith 25 A 50 Hz for power circuit
  • Electrical Durability
    • 2 Mcycles 12 A AC-3 <= 440 V
    • 0.8 Mcycles 25 A AC-1 <= 440 V
  • Maximum Horse Power Rating
    • 1 hp at 115 V AC 60 Hz for 1 phase motors
    • 2 hp at 230/240 V AC 60 Hz for 1 phase motor
  • Market Segmentation
    • Commercial
    • Industrial
  • Persona Type Names
    • End User
    • Contractor
    • Original Equipment Manufacturer
    • OEM - Control Panelbuilder
    • Panel Builder
    • System Integrator
  • Fire Resistance
    • 850 °C IEC 60695-2-1
  • Contactor Application
    • resistive load
    • motor control
  • Flame Retardance
    • V1 conforming to UL 94
  • Carbon Footprint Of The Use Phase B2 B3 B4 B6
    • 32 kg CO2 eq.
    • 32.425000751223415
  • Persona Type Ids
    • EU
    • LC
    • OM
    • OM8
    • PB
    • SI
  • Safety Reliability Level
    • B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1
    • B10d = 1369863 cycles contactor with nominal load EN/ISO 13
  • Carbon Footprint Of The Distribution Phase A4
    • 0.32347694981101516
    • 0.3 kg CO2 eq.
  • Tightening Torque
    • power circuit 1.7 N.m screw clamp terminals flat Ø 6 mm
    • power circuit 1.7 N.m screw cl
  • Ith Conventional Free Air Thermal Current
    • 10 A (at 60 °C) for signalling circuit
    • 25 A (at 60 °C) for power circuit
  • Irms Rated Making Capacity
    • 250 A at 440 V for power circuit conforming to IEC 60947
    • 140 A AC for signalling ci
  • Mechanical Robustness
    • vibrations contactor open2 Gn, 5...300 Hz
    • vibrations contactor closed4 Gn, 5...300 Hz
    • vibrations contactor closed4 Gn, 5...300
  • Minimum Switching Current
    • 5 mA for signalling circuit
  • Motor Power Kw
    • 3 kW at 220...230 V AC 50 Hz
    • 5.5 kW at 380...400 V AC 50 Hz
    • 5.5 kW at 415.
  • Control Circuit Voltage Limits
    • 0.3...0.6 Uc (-40-70 °C):drop-out AC 50/60 Hz
    • 0.8...1.1 Uc (-40-60 °C)
  • Utilisation Category
    • AC-3
    • AC-1
  • Ie Rated Operational Current
    • 25 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
    • 25 A (at <60 °C) at <= 440 V AC AC
  • Icw Rated Short Time Withstand Current
    • 30 A 40 °C - 10 min for power circuit
    • 61 A 40 °C - 1 min for power circuit
    • 61 A 40 °C - 1 min for power
  • Hold In Power Consumption In Va
    • 7.5-7.5 VA 60 Hz cos phi 0.3 (at 20 °C)
    • 7-7 VA 50 Hz cos phi 0.3 (at 20 °C)
    • 7-7 VA 50 Hz cos phi 0
  • Market Segmentation Id
    • COMMERCIAL
    • INDUSTRIAL
  • Inrush Power In Va
    • 70-70 VA 60 Hz cos phi 0.75 (at 20 °C)
    • 70-70 VA 50 Hz cos phi 0.75 (at 20 °C)
    • 70-70 VA 50 Hz cos p
  • Associated Fuse Rating
    • 10 A gG for signalling circuit conforming to IEC 60947-5-1
    • 40 A gG at <= 690
  • Ambient Air Temperature For Operation
    • -40-60 °C
    • 60-70 °C with derating
  • Rated Breaking Capacity
    • 250 A at 440 V for power circuit conforming to IEC 60947
  • Range
    • TeSys
    • TeSys Deca
  • Product Certifications
    • DNV
    • CSA
    • CCC
    • UL
    • GL
    • LROS (Lloyds register of shipping)
    • BV
    • RINA
    • GOST
    • UKCA
  • Important Information Attributes
    • Country Id : US
    • Local Data Status : Publishable
    • Local Publishable Date : 2025-05-31
    • ETIM 10 : EC000010
    • Html Descr : REVERSING CONTACTOR 575VAC 12A, AC-3/AC-1, 3P, 120 V AC 50/60 Hz, 1 NO + 1 NC, IEC
    • Manufacturer : Schneider Electric
    • Device Type : LV equipment - LV contactor
    • Serviceability : No
    • Traceability : No
    • Field Service Division : PPIBS
    • Average Life Duration : 20 year(s)
    • Manufacturing Carbon Footprint : 4.16336010476112
    • Distribution Carbon Footprint : 0.323476949811015
    • Installation Carbon Footprint : 5.20461497777044e-02
    • Use Carbon Footprint : 32.4250007512234
    • End Of Life Carbon Footprint : 1.6880716149298
    • Legacy WEEE Scope : In
    • WEEE Product Category : 5
    • Scope Perimeter : At least in Europe
    • EOLI Availability Display : Yes
    • End Of Life Doc Ref : ENVEOLI1501004
    • Reach Full Compliance Status : Free of Substances of Very High Concern above the threshold
    • Reach Full Compliance Status Id : NOT_CONTAINING_SVHC
    • Reach Compliance Directive : Free of Substances of Very High Concern above the threshold
    • ROHS Eur In Scope : Yes
    • ROHS Eur Status : Compliant
    • ROHS Eur Conformity Date : 2538
    • ROHS Eur Full Compliance Status : Compliant
    • ROHS Eur Full Compliance Status Id : COMPLIANT
    • China ROHS In Scope : No
    • China ROHS Label : 1
    • Green Premium Status For Reporting : Green Premium product
    • With Recycled Cardboard : Yes
    • Without Single Use Plastic : Yes
    • Product Contributes To Saved And Avoided Emissions : No
    • Return Indicator : Y
    • WD Status : 1 - GSC certified
    • Tier Id : 1
    • Tier : 1
    • Function Option Id : STANDARD
    • Function Option : Standard
    • Coil Technology : without built-in suppressor module
    • Compatibility Code : LC2D
    • Contact Compatibility : M2
    • Device Short Name : LC2D
    • Interlocking Type : electrical and mechanical
    • Mechanical Durability : 15 Mcycles
    • Overvoltage Category : III
    • Package Weight Lbs : 816.466 g
    • Pole Contact Composition : 3 NO
    • Poles Description : 3P
    • Product Availability : Stock - Normally stocked in distribution facility
    • Product Or Component Type : reversing contactor
    • Returnability : Yes
    • Signalling Circuit Frequency : 25...400 Hz
    • Sustainable Packaging : Yes
    • Total Lifecycle Carbon Footprint : 39 kg CO2 eq.
    • Weee Label : The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
    • Carbon Footprint Kg Co2 Eq Total Life Cycle : 38.65195557050305
    • Relationshiptype : Spare part relationship
  • General Attributes
    • Product Or Component Type : reversing contactor
  • Environment Attributes
    • ROHS Exemption Information : Yes
    • China ROHS Url : https://checkaproduct.se.com/DistantRequestDispatcher.aspx?action=exportPdfRoHSChina&pid=625520&lang=en-us
    • Take Back : No
    • Reach Free Shvc : Yes
    • Recycled Metal Content At Cr Level : 0 %
    • China ROHS Regulation : Pro-active China RoHS declaration (out of China RoHS legal scope)
    • Toxic Heavy Metal Free : Yes
    • Mercury Free : Yes
    • Carbon Footprint : 38.651955570503
    • Ambient Air Temperature For Storage : -60-80 °C
    • Circularity Profile : ENVEOLI1501004
    • Environmental Disclosure : ENVPEP1501004
    • Eu Rohs Directive : Compliant
    • Operating Altitude : 0...9842.52 ft (0...3000 m)
    • Packaging Made With Recycled Cardboard : Yes
    • Packaging Without Single Use Plastic : Yes
    • Reach Free Of Svhc : Yes
    • Reach Regulation : Free of Substances of Very High Concern above the threshold
  • Contractual Warranty Attributes
    • Warranty Period : 18 months
    • Warranty : 18 months
  • Specifications
    • Country of Origin : France
    • Height : 3.03 in
    • Width : 3.54 in
    • Depth : 3.39 in
  • Overview Attributes
    • Device Presentation : preassembled with reversing power busbar