IEC contactor, TeSys D, nonreversing, 60A resistive, 4 pole, 4 NO, 230VAC 50/60Hz coil, open style

IEC contactor, TeSys D, nonreversing, 60A resistive, 4 pole, 4 NO, 230VAC 50/60Hz coil, open style

SQDLC1DT60AP7 LC1DT60AP7 338911940930
0.00 / EA
  • Certifications: BV, CCC, CSA, DNV, GL, GOST, LROS (Lloyds Register Of Shipping), RINA, UKCA, UL
  • Contact Configuration: 1 NO + 1 NC
  • Contact Configuration: 4 NO
  • Depth: 120 mm
  • Height: 122 mm
  • Impedance: 1.6 MOhm - Ith 60 A 50 Hz Power Circuit
  • Net Weight: 1.09 kg
  • Standard: CSA C22.2 No 14, EN 60947-4-1, EN 60947-5-1, IEC 60947-4-1, IEC 60947-5-1, UL 508
  • Storage Temperature: -60-80 °C
  • Warranty Length: 18 mth
  • Width: 70 mm
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 4 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactor has four normally open power contacts. Power contacts have a 60A resistive load rating. Contactor is supplied with a 230 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 4.80 inches tall, 2.76 inches wide and 4.72 inches deep. It weighs 2.40 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
  • Product Description
  • Specifications
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 4 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactor has four normally open power contacts. Power contacts have a 60A resistive load rating. Contactor is supplied with a 230 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 4.80 inches tall, 2.76 inches wide and 4.72 inches deep. It weighs 2.40 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
  • Environment
    • Operating Altitude : 0...9842.52 ft (0...3000 m)
    • Ambient Air Temperature For Operation : -40-60 °C || 60-70 °C with derating
    • Flame Retardance : V1 conforming to UL 94
    • Height : 122 mm
    • Net Weight : 1.09 kg
    • Width : 70 mm
    • Fire Resistance : 850 °C IEC 60695-2-1
    • Ambient Air Temperature For Storage : -60-80 °C
    • Ip Degree Of Protection : IP20 front face IEC 60529
    • Pollution Degree : 3
    • Mechanical Robustness : vibrations contactor open2 Gn, 5...300 Hz || vibrations contactor closed4 Gn, 5...300 Hz || shocks contactor closed15 Gn for 11 ms || shocks contactor open10 Gn for 11 ms
    • Protective Treatment : TH IEC 60068-2-30
    • Depth : 120 mm
  • Auxiliary Contact Composition : 1 NO + 1 NC
  • Product Certifications : GL || GOST || UL || LROS (Lloyds register of shipping) || CCC || CSA || BV || DNV || RINA || UKCA
  • Associated Fuse Rating : 10 A gG signalling circuit IEC 60947-5-1 || 80 A gG <= 690 V type 1 power circuit || 80 A gG <= 690 V type 2 power circuit
  • Mounting Support : rail || plate
  • Contactor Application : resistive load
  • Rated Breaking Capacity : 800 A 440 V power circuit IEC 60947
  • Overvoltage Category : III
  • Product Or Component Type : contactor
  • Connections - Terminals : control circuit screw clamp terminals 2 1-2.5 mm²flexible with cable end || control circuit screw clamp terminals 1 1-4 mm²flexible without cable end || control circuit screw clamp terminals 2 1-4 mm²flexible without cable end || control circuit screw clamp terminals 1 1-4 mm²flexible with cable end || control circuit screw clamp terminals 1 1-4 mm²solid without cable end || control circuit screw clamp terminals 2 1-4 mm²solid without cable end || power circuit EverLink BTR screw connectors 1 1-35 mm²flexible without cable end || power circuit EverLink BTR screw connectors 2 1-25 mm²flexible without cable end || power circuit EverLink BTR screw connectors 1 1-35 mm²flexible with cable end || power circuit EverLink BTR screw connectors 2 1-25 mm²flexible with cable end || power circuit EverLink BTR screw connectors 1 1-35 mm²solid without cable end || power circuit EverLink BTR screw connectors 2 1-25 mm²solid without cable end
  • [Ie] Rated Operational Current : 60 A 60 °C) <= 440 V AC AC-1 power circuit
  • [Uimp] Rated Impulse Withstand Voltage : 6 kV IEC 60947
  • Poles Description : 4P
  • Device Short Name : LC1D
  • Irms Rated Making Capacity : 140 A AC signalling circuit IEC 60947-5-1 || 250 A DC signalling circuit IEC 60947-5-1 || 800 A 440 V power circuit IEC 60947
  • [Ith] Conventional Free Air Thermal Current : 10 A 60 °C signalling circuit || 60 A 60 °C power circuit
  • Electrical Durability : 1.4 Mcycles 60 A AC-1 <= 440 V
  • [Ue] Rated Operational Voltage : power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
  • Average Impedance : 1.6 mOhm - Ith 60 A 50 Hz power circuit
  • Pole Contact Composition : 4 NO
  • Mechanical Durability : 6 Mcycles
  • Safety Reliability Level : B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
  • Utilisation Category : AC-1
  • Standards : CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508
  • Range : TeSys
  • [Uc] Control Circuit Voltage : 230 V AC 50/60 Hz
  • Control Circuit Type : AC 50/60 Hz
  • Maximum Operating Rate : 3600 cyc/h 60 °C
  • Operating Time : 4...19 ms opening || 12...26 ms closing
  • [Ui] Rated Insulation Voltage : power circuit 600 V CSA || power circuit 600 V UL || signalling circuit 690 V IEC 60947-1 || signalling circuit 600 V CSA || signalling circuit 600 V UL || power circuit 690 V IEC 60947-4-1
  • Tightening Torque : control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || power circuit 8 N.m screw clamp terminals 25-35 mm² hexagonal 4 mm || power circuit 5 N.m screw clamp terminals 1-25 mm² hexagonal 4 mm
  • Protective Cover : with
  • Power Dissipation Per Pole : 5.8 W AC-1
  • [Icw] Rated Short-Time Withstand Current : 320 A 40 °C - 10 s power circuit || 720 A 40 °C - 1 s power circuit || 72 A 40 °C - 10 min power circuit || 165 A 40 °C - 1 min power circuit || 100 A - 1 s signalling circuit || 120 A - 500 ms signalling circuit || 140 A - 100 ms signalling circuit
  • Product Name : TeSys D
  • Complementary
    • Minimum Switching Current : 5 mA signalling circuit
    • Coil Technology : without built-in suppressor module
    • Non-Overlap Time : 1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
    • Minimum Switching Voltage : 17 V signalling circuit
    • Control Circuit Voltage Limits : 0.3...0.6 Uc -40-70 °C drop-out AC 50/60 Hz || 0.8...1.1 Uc -40-60 °C operational AC 50 Hz || 0.85...1.1 Uc -40-60 °C operational AC 60 Hz || 1...1.1 Uc 60-70 °C operational AC 50/60 Hz
    • Hold-In Power Consumption In Va : 13-13 VA 60 Hz 0.3 20 °C) || 15-15 VA 50 Hz 0.3 20 °C)
    • Signalling Circuit Frequency : 25...400 Hz
    • Heat Dissipation : 4-5 W 50/60 Hz
    • Inrush Power In Va : 140-140 VA 60 Hz 0.75 20 °C) || 160-160 VA 50 Hz 0.75 20 °C)
    • Insulation Resistance : > 10 MOhm signalling circuit
    • Auxiliary Contacts Type : mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
  • Contractual warranty
    • Warranty : 18 months
  • Offer Sustainability
    • Reach Free Of Svhc : Yes
    • Rohs Exemption Information : Yes
    • Sustainable Offer Status : Green Premium product
    • Pvc Free : Yes
    • Eu Rohs Directive : Compliant
    • California Proposition 65 : WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
    • Reach Regulation : Free of Substances of Very High Concern above the threshold
    • Environmental Disclosure : ENVPEP110205EN
    • China Rohs Regulation : Pro-active China RoHS declaration (out of China RoHS legal scope)
    • Toxic Heavy Metal Free : Yes
    • Weee : The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
    • Mercury Free : Yes