IEC contactor, TeSys D, nonreversing, 40A resistive, 4 pole, 4 NO, low consumption 24VDC coil, open style

IEC contactor, TeSys D, nonreversing, 40A resistive, 4 pole, 4 NO, low consumption 24VDC coil, open style

SQDLC1DT40BL LC1DT40BL 785901610670
268.75 / EACH
  • Certifications: BV, CCC, CSA, DNV, GL, GOST, LROS (Lloyds Register Of Shipping), RINA, UL
  • Contact Configuration: 1 NO + 1 NC
  • Contact Configuration: 4 NO
  • Depth: 107 mm
  • Height: 91 mm
  • Impedance: 2 MOhm - Ith 40 A 50 Hz Power Circuit
  • Net Weight: 0.425 kg
  • Standard: CSA C22.2 No 14, EN 60947-4-1, EN 60947-5-1, IEC 60947-4-1, IEC 60947-5-1, UL 508
  • Storage Temperature: -60-80 °C
  • Warranty Length: 18 mth
  • Width: 45 mm
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 4 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactor has four normally open power contacts. Power contacts have a 40A resistive load rating. Contactor is supplied with a low consumption 24 VDC coil with transient suppressor module. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.58 inches tall, 1.77 inches wide and 4.21 inches deep. It weighs 0.94 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
  • Product Description
  • Specifications
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 4 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactor has four normally open power contacts. Power contacts have a 40A resistive load rating. Contactor is supplied with a low consumption 24 VDC coil with transient suppressor module. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.58 inches tall, 1.77 inches wide and 4.21 inches deep. It weighs 0.94 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
  • [Uimp] Rated Impulse Withstand Voltage : 6 kV IEC 60947
  • Connections - Terminals : control circuit screw clamp terminals 2 1-2.5 mm²flexible with cable end || control circuit screw clamp terminals 1 1-4 mm²flexible without cable end || control circuit screw clamp terminals 2 1-4 mm²flexible without cable end || control circuit screw clamp terminals 1 1-4 mm²flexible with cable end || control circuit screw clamp terminals 1 1-4 mm²solid without cable end || control circuit screw clamp terminals 2 1-4 mm²solid without cable end || power circuit connector 1 2.5-10 mm²flexible without cable end || power circuit connector 2 2.5-10 mm²flexible without cable end || power circuit connector 1 2.5-10 mm²flexible with cable end || power circuit connector 2 2.5-10 mm²flexible with cable end || power circuit connector 1 2.5-16 mm²solid without cable end || power circuit connector 2 2.5-16 mm²solid without cable end
  • [Ue] Rated Operational Voltage : power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
  • Poles Description : 4P
  • [Ui] Rated Insulation Voltage : power circuit 600 V CSA || power circuit 600 V UL || signalling circuit 690 V IEC 60947-1 || signalling circuit 600 V CSA || signalling circuit 600 V UL || power circuit 690 V IEC 60947-4-1
  • Rated Breaking Capacity : 450 A 440 V power circuit IEC 60947
  • [Uc] Control Circuit Voltage : 24 V DC
  • Average Impedance : 2 mOhm - Ith 40 A 50 Hz power circuit
  • Product Or Component Type : contactor
  • Utilisation Category : AC-1
  • Product Certifications : BV || DNV || UL || GL || LROS (Lloyds register of shipping) || RINA || GOST || CSA || CCC
  • Mounting Support : rail || plate
  • Tightening Torque : control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || power circuit 1.7 N.m connector flat Ø 6 mm || power circuit 1.7 N.m connector Philips No 2
  • Auxiliary Contact Composition : 1 NO + 1 NC
  • Contactor Application : resistive load
  • Pole Contact Composition : 4 NO
  • [Ie] Rated Operational Current : 40 A 60 °C) <= 440 V AC AC-1 power circuit
  • Power Dissipation Per Pole : 3.2 W AC-1
  • Range : TeSys
  • [Icw] Rated Short-Time Withstand Current : 50 A 40 °C - 10 min power circuit || 120 A 40 °C - 1 min power circuit || 240 A 40 °C - 10 s power circuit || 380 A 40 °C - 1 s power circuit || 100 A - 1 s signalling circuit || 120 A - 500 ms signalling circuit || 140 A - 100 ms signalling circuit
  • Device Short Name : LC1D
  • Product Name : TeSys D
  • Protective Cover : with
  • Electrical Durability : 1.4 Mcycles 40 A AC-1 <= 440 V
  • Control Circuit Type : DC low consumption
  • Mechanical Durability : 30 Mcycles
  • Operating Time : 65.45...88.55 ms closing || 20...30 ms opening
  • Standards : CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508
  • Overvoltage Category : III
  • Safety Reliability Level : B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
  • [Ith] Conventional Free Air Thermal Current : 10 A 60 °C signalling circuit || 40 A 60 °C power circuit
  • Maximum Operating Rate : 3600 cyc/h 60 °C
  • Irms Rated Making Capacity : 140 A AC signalling circuit IEC 60947-5-1 || 250 A DC signalling circuit IEC 60947-5-1 || 450 A 440 V power circuit IEC 60947
  • Associated Fuse Rating : 10 A gG signalling circuit IEC 60947-5-1 || 63 A gG <= 690 V type 1 power circuit || 40 A gG <= 690 V type 2 power circuit
  • Offer Sustainability
    • Circularity Profile : ENVEOLI1102029EN
    • Reach Regulation : Free of Substances of Very High Concern above the threshold
    • Weee : The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
    • Sustainable Offer Status : Green Premium product
    • Pvc Free : Yes
    • Rohs Exemption Information : Yes
    • California Proposition 65 : WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
    • Mercury Free : Yes
    • Environmental Disclosure : ENVPEP110229EN
    • China Rohs Regulation : Pro-active China RoHS declaration (out of China RoHS legal scope)
    • Reach Free Of Svhc : Yes
    • Eu Rohs Directive : Compliant
    • Toxic Heavy Metal Free : Yes
  • Complementary
    • Minimum Switching Voltage : 17 V signalling circuit
    • Control Circuit Voltage Limits : 0.1...0.3 Uc -40-70 °C drop-out DC || 0.8...1.25 Uc -40-60 °C operational DC || 1...1.25 Uc 60-70 °C operational DC
    • Signalling Circuit Frequency : 25...400 Hz
    • Coil Technology : built-in bidirectional peak limiting diode suppressor
    • Inrush Power In W : 2.4-2.4 W 20 °C)
    • Minimum Switching Current : 5 mA signalling circuit
    • Hold-In Power Consumption In W : 2.4-2.4 W 20 °C
    • Insulation Resistance : > 10 MOhm signalling circuit
    • Time Constant : 40 ms
    • Non-Overlap Time : 1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
    • Auxiliary Contacts Type : mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
  • Contractual warranty
    • Warranty : 18 months
  • Environment
    • Fire Resistance : 850 °C IEC 60695-2-1
    • Mechanical Robustness : vibrations contactor open2 Gn, 5...300 Hz || vibrations contactor closed4 Gn, 5...300 Hz || shocks contactor closed15 Gn for 11 ms || shocks contactor open8 Gn for 11 ms
    • Maximum Height : 91 mm
    • Maximum Width : 45 mm
    • Net Weight : 0.425 kg
    • Ambient Air Temperature For Operation : -40-60 °C || 60-70 °C with derating
    • Ambient Air Temperature For Storage : -60-80 °C
    • Pollution Degree : 3
    • Ip Degree Of Protection : IP20 front face IEC 60529
    • Operating Altitude : 0...9842.52 ft (0...3000 m)
    • Flame Retardance : V1 conforming to UL 94
    • Protective Treatment : TH IEC 60068-2-30
    • Maximum Depth : 107 mm