IEC contactor, TeSys D, nonreversing, 40A resistive, 4 pole, 4 NO, 230VAC 50/60Hz coil, open style

CONTACTOR 600VAC 40AMP IEC + O

SQDLC1DT40P7 LC1DT40P7 785901834441
214.72 / EACH
  • Certifications: BV, CCC, CSA, DNV, GL, GOST, LROS (Lloyds Register Of Shipping), RINA, UL
  • Contact Configuration: 1 NO + 1 NC, 4 NO
  • Depth: 99 mm
  • Height: 91 mm
  • Impedance: 2 MOhm - Ith 40 A 50 Hz Power Circuit
  • Net Weight: 0.425 kg
  • Standard: CSA C22.2 No 14, EN 60947-4-1, EN 60947-5-1, IEC 60335-1, IEC 60947-4-1, IEC 60947-5-1, UL 508
  • Storage Temperature: -60-80 °C
  • Warranty Length: 18 mth
  • Width: 45 mm
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 4 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactor has four normally open power contacts. Power contacts have a 40A resistive load rating. Contactor is supplied with a 230 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.58 inches tall, 1.77 inches wide and 3.90 inches deep. It weighs 0.94 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
  • Product Description
  • Specifications
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 4 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactor has four normally open power contacts. Power contacts have a 40A resistive load rating. Contactor is supplied with a 230 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.58 inches tall, 1.77 inches wide and 3.90 inches deep. It weighs 0.94 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
  • Complementary
    • Inrush Power In Va : 70-70 VA 60 Hz 0.75 20 °C) || 70-70 VA 50 Hz 0.75 20 °C)
    • Coil Technology : without built-in suppressor module
    • Auxiliary Contacts Type : mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
    • Heat Dissipation : 2-3 W 50/60 Hz
    • Minimum Switching Current : 5 mA signalling circuit
    • Insulation Resistance : > 10 MOhm signalling circuit
    • Minimum Switching Voltage : 17 V signalling circuit
    • Hold-In Power Consumption In Va : 7.5-7.5 VA 60 Hz 0.3 20 °C) || 7-7 VA 50 Hz 0.3 20 °C)
    • Non-Overlap Time : 1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
    • Signalling Circuit Frequency : 25...400 Hz
    • Control Circuit Voltage Limits : 0.3...0.6 Uc -40-70 °C drop-out AC 50/60 Hz || 0.8...1.1 Uc -40-60 °C operational AC 50 Hz || 0.85...1.1 Uc -40-60 °C operational AC 60 Hz || 1...1.1 Uc 60-70 °C operational AC 50/60 Hz
  • Contractual warranty
    • Warranty : 18 months
  • Offer Sustainability
    • Weee : The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
    • Pvc Free : Yes
    • Environmental Disclosure : ENVPEP110229EN
    • Toxic Heavy Metal Free : Yes
    • Eu Rohs Directive : Compliant
    • Reach Free Of Svhc : Yes
    • Circularity Profile : ENVEOLI1102029EN
    • Sustainable Offer Status : Green Premium product
    • Rohs Exemption Information : Yes
    • California Proposition 65 : WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
    • Mercury Free : Yes
    • Reach Regulation : Free of Substances of Very High Concern above the threshold
    • China Rohs Regulation : Pro-active China RoHS declaration (out of China RoHS legal scope)
  • [Ie] Rated Operational Current : 40 A 60 °C) <= 440 V AC AC-1 power circuit
  • Overvoltage Category : III
  • Connections - Terminals : control circuit screw clamp terminals 2 1-2.5 mm²flexible with cable end || control circuit screw clamp terminals 1 1-4 mm²flexible without cable end || control circuit screw clamp terminals 2 1-4 mm²flexible without cable end || control circuit screw clamp terminals 1 1-4 mm²flexible with cable end || control circuit screw clamp terminals 1 1-4 mm²solid without cable end || control circuit screw clamp terminals 2 1-4 mm²solid without cable end || power circuit connector 1 2.5-10 mm²flexible without cable end || power circuit connector 2 2.5-10 mm²flexible without cable end || power circuit connector 1 2.5-10 mm²flexible with cable end || power circuit connector 2 2.5-10 mm²flexible with cable end || power circuit connector 1 2.5-16 mm²solid without cable end || power circuit connector 2 2.5-16 mm²solid without cable end
  • Maximum Operating Rate : 3600 cyc/h 60 °C
  • Product Name : TeSys D || TeSys Deca
  • Mechanical Durability : 15 Mcycles
  • Operating Time : 4...19 ms opening || 12...22 ms closing
  • Power Dissipation Per Pole : 3.2 W AC-1
  • Associated Fuse Rating : 10 A gG signalling circuit IEC 60947-5-1 || 63 A gG <= 690 V type 1 power circuit || 40 A gG <= 690 V type 2 power circuit
  • [Uimp] Rated Impulse Withstand Voltage : 6 kV IEC 60947
  • [Ue] Rated Operational Voltage : power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
  • Rated Breaking Capacity : 450 A 440 V power circuit IEC 60947
  • Auxiliary Contact Composition : 1 NO + 1 NC
  • [Icw] Rated Short-Time Withstand Current : 50 A 40 °C - 10 min power circuit || 120 A 40 °C - 1 min power circuit || 240 A 40 °C - 10 s power circuit || 380 A 40 °C - 1 s power circuit || 100 A - 1 s signalling circuit || 120 A - 500 ms signalling circuit || 140 A - 100 ms signalling circuit
  • Mounting Support : rail || plate
  • [Uc] Control Circuit Voltage : 230 V AC 50/60 Hz
  • Product Or Component Type : contactor
  • Control Circuit Type : AC 50/60 Hz
  • Standards : CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508 || IEC 60335-1
  • Irms Rated Making Capacity : 140 A AC signalling circuit IEC 60947-5-1 || 250 A DC signalling circuit IEC 60947-5-1 || 450 A 440 V power circuit IEC 60947
  • Electrical Durability : 1.4 Mcycles 40 A AC-1 <= 440 V
  • Range : TeSys || TeSys Deca
  • Pole Contact Composition : 4 NO
  • Poles Description : 4P
  • Protective Cover : with
  • [Ith] Conventional Free Air Thermal Current : 10 A 60 °C signalling circuit || 40 A 60 °C power circuit
  • Contactor Application : resistive load
  • Product Certifications : CCC || LROS (Lloyds register of shipping) || RINA || UL || DNV || BV || CSA || GL || GOST
  • Device Short Name : LC1D
  • Average Impedance : 2 mOhm - Ith 40 A 50 Hz power circuit
  • Utilisation Category : AC-1
  • Tightening Torque : control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || power circuit 1.7 N.m connector flat Ø 6 mm || power circuit 1.7 N.m connector Philips No 2 || control circuit 1.7 N.m screw clamp terminals pozidriv No 2 || power circuit 2.5 N.m screw clamp terminals pozidriv No 2
  • Safety Reliability Level : B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
  • [Ui] Rated Insulation Voltage : power circuit 600 V CSA || power circuit 600 V UL || signalling circuit 690 V IEC 60947-1 || signalling circuit 600 V CSA || signalling circuit 600 V UL || power circuit 690 V IEC 60947-4-1
  • Environment
    • Ambient Air Temperature For Storage : -60-80 °C
    • Fire Resistance : 850 °C IEC 60695-2-1
    • Depth : 99 mm
    • Mechanical Robustness : vibrations contactor open2 Gn, 5...300 Hz || vibrations contactor closed4 Gn, 5...300 Hz || shocks contactor closed15 Gn for 11 ms || shocks contactor open8 Gn for 11 ms
    • Ambient Air Temperature For Operation : -40-60 °C || 60-70 °C with derating
    • Flame Retardance : V1 conforming to UL 94
    • Height : 91 mm
    • Ip Degree Of Protection : IP20 front face IEC 60529
    • Net Weight : 0.425 kg
    • Operating Altitude : 0...9842.52 ft (0...3000 m)
    • Width : 45 mm
    • Protective Treatment : TH IEC 60068-2-30
    • Pollution Degree : 3