IEC contactor, TeSys D, nonreversing, 40A resistive, 4 pole, 4 NO, 125VDC coil, open style

CONTACTOR 600VAC 40AMP IEC + O

SQDLC1DT40GD LC1DT40GD 338911033094
0.00 / EA
  • Certifications: BV, CCC, CSA, DNV, GL, GOST, LROS (Lloyds Register Of Shipping), RINA, UL
  • Contact Configuration: 1 NO + 1 NC, 4 NO
  • Depth: 107 mm
  • Height: 91 mm
  • Impedance: 2 MOhm - Ith 40 A 50 Hz Power Circuit
  • Net Weight: 0.425 kg
  • Standard: CSA C22.2 No 14, EN 60947-4-1, EN 60947-5-1, IEC 60335-1, IEC 60947-4-1, IEC 60947-5-1, UL 508
  • Storage Temperature: -60-80 °C
  • Warranty Length: 18 mth
  • Width: 45 mm
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 4 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactor has four normally open power contacts. Power contacts have a 40A resistive load rating. Contactor is supplied with a 125 VDC coil with transient suppressor module. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.58 inches tall, 1.77 inches wide and 4.21 inches deep. It weighs 0.94 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
  • Product Description
  • Specifications
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 4 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactor has four normally open power contacts. Power contacts have a 40A resistive load rating. Contactor is supplied with a 125 VDC coil with transient suppressor module. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.58 inches tall, 1.77 inches wide and 4.21 inches deep. It weighs 0.94 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
  • Offer Sustainability
    • California Proposition 65 : WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
    • Reach Free Of Svhc : Yes
    • Eu Rohs Directive : Compliant
    • Weee : The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
    • Sustainable Offer Status : Green Premium product
    • Circularity Profile : ENVEOLI1102029EN
    • Mercury Free : Yes
    • Environmental Disclosure : ENVPEP110229EN
    • Reach Regulation : Free of Substances of Very High Concern above the threshold
    • Pvc Free : Yes
    • China Rohs Regulation : Pro-active China RoHS declaration (out of China RoHS legal scope)
    • Toxic Heavy Metal Free : Yes
    • Rohs Exemption Information : Yes
  • Utilisation Category : AC-1
  • Protective Cover : with
  • Standards : CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508 || IEC 60335-1
  • [Ui] Rated Insulation Voltage : power circuit 600 V CSA || power circuit 600 V UL || signalling circuit 690 V IEC 60947-1 || signalling circuit 600 V CSA || signalling circuit 600 V UL || power circuit 690 V IEC 60947-4-1
  • Electrical Durability : 1.4 Mcycles 40 A AC-1 <= 440 V
  • Mounting Support : rail || plate
  • Auxiliary Contact Composition : 1 NO + 1 NC
  • Associated Fuse Rating : 10 A gG signalling circuit IEC 60947-5-1 || 63 A gG <= 690 V type 1 power circuit || 40 A gG <= 690 V type 2 power circuit
  • Safety Reliability Level : B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
  • Rated Breaking Capacity : 450 A 440 V power circuit IEC 60947
  • Device Short Name : LC1D
  • Mechanical Durability : 30 Mcycles
  • Pole Contact Composition : 4 NO
  • Product Certifications : DNV || CSA || UL || GOST || BV || LROS (Lloyds register of shipping) || CCC || GL || RINA
  • [Ith] Conventional Free Air Thermal Current : 10 A 60 °C signalling circuit || 40 A 60 °C power circuit
  • Average Impedance : 2 mOhm - Ith 40 A 50 Hz power circuit
  • Irms Rated Making Capacity : 140 A AC signalling circuit IEC 60947-5-1 || 250 A DC signalling circuit IEC 60947-5-1 || 450 A 440 V power circuit IEC 60947
  • Connections - Terminals : control circuit screw clamp terminals 2 1-2.5 mm²flexible with cable end || control circuit screw clamp terminals 1 1-4 mm²flexible without cable end || control circuit screw clamp terminals 2 1-4 mm²flexible without cable end || control circuit screw clamp terminals 1 1-4 mm²flexible with cable end || control circuit screw clamp terminals 1 1-4 mm²solid without cable end || control circuit screw clamp terminals 2 1-4 mm²solid without cable end || power circuit connector 1 2.5-10 mm²flexible without cable end || power circuit connector 2 2.5-10 mm²flexible without cable end || power circuit connector 1 2.5-10 mm²flexible with cable end || power circuit connector 2 2.5-10 mm²flexible with cable end || power circuit connector 1 2.5-16 mm²solid without cable end || power circuit connector 2 2.5-16 mm²solid without cable end
  • Maximum Operating Rate : 3600 cyc/h 60 °C
  • Contactor Application : resistive load
  • [Icw] Rated Short-Time Withstand Current : 50 A 40 °C - 10 min power circuit || 120 A 40 °C - 1 min power circuit || 240 A 40 °C - 10 s power circuit || 380 A 40 °C - 1 s power circuit || 100 A - 1 s signalling circuit || 120 A - 500 ms signalling circuit || 140 A - 100 ms signalling circuit
  • [Uimp] Rated Impulse Withstand Voltage : 6 kV IEC 60947
  • Overvoltage Category : III
  • Control Circuit Type : DC standard
  • Poles Description : 4P
  • Product Or Component Type : contactor
  • Operating Time : 16...24 ms opening || 53.55...72.45 ms closing
  • [Uc] Control Circuit Voltage : 125 V DC
  • [Ie] Rated Operational Current : 40 A 60 °C) <= 440 V AC AC-1 power circuit
  • Power Dissipation Per Pole : 3.2 W AC-1
  • Product Name : TeSys D || TeSys Deca
  • [Ue] Rated Operational Voltage : power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
  • Tightening Torque : control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || power circuit 1.7 N.m connector flat Ø 6 mm || power circuit 1.7 N.m connector Philips No 2 || control circuit 1.7 N.m screw clamp terminals pozidriv No 2 || power circuit 2.5 N.m screw clamp terminals pozidriv No 2
  • Range : TeSys || TeSys Deca
  • Contractual warranty
    • Warranty : 18 months
  • Environment
    • Net Weight : 0.425 kg
    • Mechanical Robustness : vibrations contactor open2 Gn, 5...300 Hz || vibrations contactor closed4 Gn, 5...300 Hz || shocks contactor closed15 Gn for 11 ms || shocks contactor open8 Gn for 11 ms
    • Ambient Air Temperature For Storage : -60-80 °C
    • Ambient Air Temperature For Operation : -40-60 °C || 60-70 °C with derating
    • Operating Altitude : 0...9842.52 ft (0...3000 m)
    • Width : 45 mm
    • Pollution Degree : 3
    • Height : 91 mm
    • Ip Degree Of Protection : IP20 front face IEC 60529
    • Flame Retardance : V1 conforming to UL 94
    • Fire Resistance : 850 °C IEC 60695-2-1
    • Protective Treatment : TH IEC 60068-2-30
    • Depth : 107 mm
  • Complementary
    • Coil Technology : built-in bidirectional peak limiting diode suppressor
    • Hold-In Power Consumption In W : 5.4-5.4 W 20 °C
    • Signalling Circuit Frequency : 25...400 Hz
    • Insulation Resistance : > 10 MOhm signalling circuit
    • Time Constant : 28 ms
    • Inrush Power In W : 5.4-5.4 W 20 °C)
    • Non-Overlap Time : 1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
    • Control Circuit Voltage Limits : 0.1...0.25 Uc -40-70 °C drop-out DC || 0.7...1.25 Uc -40-60 °C operational DC || 1...1.25 Uc 60-70 °C operational DC
    • Minimum Switching Current : 5 mA signalling circuit
    • Auxiliary Contacts Type : mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
    • Minimum Switching Voltage : 17 V signalling circuit