IEC contactor, TeSys D, nonreversing, 32A resistive, 4 pole, 4 NO, 120VAC 50/60Hz coil, open style

IEC contactor, TeSys D, nonreversing, 32A resistive, 4 pole, 4 NO, 120VAC 50/60Hz coil, open style

SQDLC1DT326G7 LC1DT326G7 338911033436
0.00 / EA
  • Certifications: BV, CCC, CSA, DNV, GL, GOST, LROS (Lloyds Register Of Shipping), RINA, UL
  • Contact Configuration: 1 NO + 1 NC
  • Contact Configuration: 4 NO
  • Depth: 99 mm
  • Height: 91 mm
  • Impedance: 2.5 MOhm - Ith 32 A 50 Hz Power Circuit
  • Net Weight: 0.425 kg
  • Standard: CSA C22.2 No 14, EN 60947-4-1, EN 60947-5-1, IEC 60947-4-1, IEC 60947-5-1, UL 508
  • Storage Temperature: -60-80 °C
  • Warranty Length: 18 mth
  • Width: 45 mm
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 4 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactor has four normally open power contacts. Power contacts have a 32A resistive load rating. Contactor is supplied with a 120 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Ring-lug screw terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.58 inches tall, 1.77 inches wide and 3.90 inches deep. It weighs 0.94 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
  • Product Description
  • Specifications
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 4 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactor has four normally open power contacts. Power contacts have a 32A resistive load rating. Contactor is supplied with a 120 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Ring-lug screw terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.58 inches tall, 1.77 inches wide and 3.90 inches deep. It weighs 0.94 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
  • Offer Sustainability
    • Rohs Exemption Information : Yes
    • California Proposition 65 : WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
    • Weee : The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
    • Circularity Profile : ENVEOLI1501004EN
    • Eu Rohs Directive : Compliant
    • Mercury Free : Yes
    • Reach Regulation : Free of Substances of Very High Concern above the threshold
    • Toxic Heavy Metal Free : Yes
    • Sustainable Offer Status : Green Premium product
    • China Rohs Regulation : Pro-active China RoHS declaration (out of China RoHS legal scope)
    • Reach Free Of Svhc : Yes
    • Environmental Disclosure : ENVPEP1501004EN
    • Pvc Free : Yes
  • Contactor Application : resistive load
  • Device Short Name : LC1D
  • [Ie] Rated Operational Current : 32 A 60 °C) <= 440 V AC AC-1 power circuit
  • Associated Fuse Rating : 10 A gG signalling circuit IEC 60947-5-1 || 50 A gG <= 690 V type 1 power circuit || 35 A gG <= 690 V type 2 power circuit
  • Standards : CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508
  • Product Name : TeSys D
  • Range : TeSys
  • Utilisation Category : AC-1
  • [Ue] Rated Operational Voltage : power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
  • Protective Cover : with
  • Average Impedance : 2.5 mOhm - Ith 32 A 50 Hz power circuit
  • [Uimp] Rated Impulse Withstand Voltage : 6 kV IEC 60947
  • [Ith] Conventional Free Air Thermal Current : 10 A 60 °C signalling circuit || 32 A 60 °C power circuit
  • Connections - Terminals : control circuit lugs-ring terminals 8 mm) || power circuit lugs-ring terminals 8 mm)
  • Power Dissipation Per Pole : 2.5 W AC-1
  • Electrical Durability : 1 Mcycles 32 A AC-1 <= 440 V
  • [Ui] Rated Insulation Voltage : power circuit 600 V CSA || power circuit 600 V UL || signalling circuit 690 V IEC 60947-1 || signalling circuit 600 V CSA || signalling circuit 600 V UL || power circuit 690 V IEC 60947-4-1
  • [Uc] Control Circuit Voltage : 120 V AC 50/60 Hz
  • Poles Description : 4P
  • Tightening Torque : control circuit 1.7 N.m lugs-ring terminals flat Ø 6 mm M3.5 || control circuit 1.7 N.m lugs-ring terminals Philips No 2 M3.5 || power circuit 1.8 N.m lugs-ring terminals flat Ø 6 mm M3.5 || power circuit 1.8 N.m lugs-ring terminals Philips No 2 M3.5
  • Control Circuit Type : AC 50/60 Hz
  • Pole Contact Composition : 4 NO
  • Maximum Operating Rate : 3600 cyc/h 60 °C
  • Operating Time : 4...19 ms opening || 12...22 ms closing
  • Mechanical Durability : 15 Mcycles
  • Safety Reliability Level : B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
  • Mounting Support : plate || rail
  • Rated Breaking Capacity : 300 A 440 V power circuit IEC 60947
  • Overvoltage Category : III
  • Product Or Component Type : contactor
  • [Icw] Rated Short-Time Withstand Current : 40 A 40 °C - 10 min power circuit || 84 A 40 °C - 1 min power circuit || 145 A 40 °C - 10 s power circuit || 240 A 40 °C - 1 s power circuit || 100 A - 1 s signalling circuit || 120 A - 500 ms signalling circuit || 140 A - 100 ms signalling circuit
  • Product Certifications : GL || LROS (Lloyds register of shipping) || BV || UL || GOST || RINA || CSA || DNV || CCC
  • Auxiliary Contact Composition : 1 NO + 1 NC
  • Irms Rated Making Capacity : 140 A AC signalling circuit IEC 60947-5-1 || 250 A DC signalling circuit IEC 60947-5-1 || 300 A 440 V power circuit IEC 60947
  • Complementary
    • Heat Dissipation : 2-3 W 50/60 Hz
    • Non-Overlap Time : 1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
    • Minimum Switching Current : 5 mA signalling circuit
    • Coil Technology : without built-in suppressor module
    • Insulation Resistance : > 10 MOhm signalling circuit
    • Signalling Circuit Frequency : 25...400 Hz
    • Auxiliary Contacts Type : mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
    • Inrush Power In Va : 70-70 VA 60 Hz 0.75 20 °C) || 70-70 VA 50 Hz 0.75 20 °C)
    • Control Circuit Voltage Limits : 0.3...0.6 Uc -40-70 °C drop-out AC 50/60 Hz || 0.8...1.1 Uc -40-60 °C operational AC 50 Hz || 0.85...1.1 Uc -40-60 °C operational AC 60 Hz || 1...1.1 Uc 60-70 °C operational AC 50/60 Hz
    • Minimum Switching Voltage : 17 V signalling circuit
    • Hold-In Power Consumption In Va : 7.5-7.5 VA 60 Hz 0.3 20 °C) || 7-7 VA 50 Hz 0.3 20 °C)
  • Contractual warranty
    • Warranty : 18 months
  • Environment
    • Maximum Width : 45 mm
    • Maximum Height : 91 mm
    • Net Weight : 0.425 kg
    • Protective Treatment : TH IEC 60068-2-30
    • Pollution Degree : 3
    • Operating Altitude : 0...9842.52 ft (0...3000 m)
    • Maximum Depth : 99 mm
    • Flame Retardance : V1 conforming to UL 94
    • Mechanical Robustness : vibrations contactor open2 Gn, 5...300 Hz || vibrations contactor closed4 Gn, 5...300 Hz || shocks contactor closed15 Gn for 11 ms || shocks contactor open8 Gn for 11 ms
    • Ambient Air Temperature For Storage : -60-80 °C
    • Fire Resistance : 850 °C IEC 60695-2-1
    • Ip Degree Of Protection : IP20 front face IEC 60529
    • Ambient Air Temperature For Operation : -40-60 °C || 60-70 °C with derating