Schneider Electric at Mayer

IEC contactor, TeSys D, nonreversing, 25A resistive, 4 pole, 4 NO, 230VAC 50/60Hz coil, open style

CONTACTOR 600VAC 25AMP IEC + O

SQDLC1DT25P7 LC1DT25P7 785901532965
145.48 / EACH
  • Certifications: BV, CCC, CSA, DNV, GL, GOST, LROS (Lloyds Register Of Shipping), RINA, UL
  • Contact Configuration: 1 NO + 1 NC, 4 NO
  • Depth: 92 mm
  • Height: 85 mm
  • Impedance: 2.5 MOhm - Ith 25 A 50 Hz Power Circuit
  • Net Weight: 0.365 kg
  • Standard: CSA C22.2 No 14, EN 60947-4-1, EN 60947-5-1, IEC 60335-1, IEC 60947-4-1, IEC 60947-5-1, UL 508
  • Storage Temperature: -60-80 °C
  • Warranty Length: 18 mth
  • Width: 45 mm
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 4 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactor has four normally open power contacts. Power contacts have a 25A resistive load rating. Contactor is supplied with a 230 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.35 inches tall, 1.77 inches wide and 3.62 inches deep. It weighs 0.80 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
  • Product Description
  • Specifications
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 4 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactor has four normally open power contacts. Power contacts have a 25A resistive load rating. Contactor is supplied with a 230 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.35 inches tall, 1.77 inches wide and 3.62 inches deep. It weighs 0.80 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
  • Contractual warranty
    • Warranty : 18 months
  • Offer Sustainability
    • Toxic Heavy Metal Free : Yes
    • Sustainable Offer Status : Green Premium product
    • Weee : The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
    • Rohs Exemption Information : Yes
    • Reach Regulation : Free of Substances of Very High Concern above the threshold
    • Mercury Free : Yes
    • Environmental Disclosure : ENVPEP1501004EN
    • Eu Rohs Directive : Compliant
    • California Proposition 65 : WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
    • China Rohs Regulation : Pro-active China RoHS declaration (out of China RoHS legal scope)
    • Reach Free Of Svhc : Yes
    • Circularity Profile : ENVEOLI1501004EN
    • Pvc Free : Yes
  • Environment
    • Depth : 92 mm
    • Pollution Degree : 3
    • Protective Treatment : TH IEC 60068-2-30
    • Ambient Air Temperature For Operation : -40-60 °C || 60-70 °C with derating
    • Width : 45 mm
    • Height : 85 mm
    • Ip Degree Of Protection : IP20 front face IEC 60529
    • Fire Resistance : 850 °C IEC 60695-2-1
    • Operating Altitude : 0...9842.52 ft (0...3000 m)
    • Mechanical Robustness : vibrations contactor open2 Gn, 5...300 Hz || vibrations contactor closed4 Gn, 5...300 Hz || shocks contactor closed15 Gn for 11 ms || shocks contactor open10 Gn for 11 ms
    • Ambient Air Temperature For Storage : -60-80 °C
    • Flame Retardance : V1 conforming to UL 94
    • Net Weight : 0.365 kg
  • Complementary
    • Auxiliary Contacts Type : mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
    • Hold-In Power Consumption In Va : 7.5-7.5 VA 60 Hz 0.3 20 °C) || 7-7 VA 50 Hz 0.3 20 °C)
    • Minimum Switching Voltage : 17 V signalling circuit
    • Non-Overlap Time : 1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
    • Signalling Circuit Frequency : 25...400 Hz
    • Control Circuit Voltage Limits : 0.3...0.6 Uc -40-70 °C drop-out AC 50/60 Hz || 0.8...1.1 Uc -40-60 °C operational AC 50 Hz || 0.85...1.1 Uc -40-60 °C operational AC 60 Hz || 1...1.1 Uc 60-70 °C operational AC 50/60 Hz
    • Coil Technology : without built-in suppressor module
    • Heat Dissipation : 2-3 W 50/60 Hz
    • Insulation Resistance : > 10 MOhm signalling circuit
    • Minimum Switching Current : 5 mA signalling circuit
    • Inrush Power In Va : 70-70 VA 60 Hz 0.75 20 °C) || 70-70 VA 50 Hz 0.75 20 °C)
  • Power Dissipation Per Pole : 1.56 W AC-1
  • Maximum Operating Rate : 3600 cyc/h 60 °C
  • Contactor Application : resistive load
  • [Uimp] Rated Impulse Withstand Voltage : 6 kV IEC 60947
  • Rated Breaking Capacity : 250 A 440 V power circuit IEC 60947
  • Device Short Name : LC1D
  • Poles Description : 4P
  • [Ue] Rated Operational Voltage : power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
  • [Icw] Rated Short-Time Withstand Current : 30 A 40 °C - 10 min power circuit || 61 A 40 °C - 1 min power circuit || 105 A 40 °C - 10 s power circuit || 210 A 40 °C - 1 s power circuit || 100 A - 1 s signalling circuit || 120 A - 500 ms signalling circuit || 140 A - 100 ms signalling circuit
  • Protective Cover : with
  • Irms Rated Making Capacity : 140 A AC signalling circuit IEC 60947-5-1 || 250 A DC signalling circuit IEC 60947-5-1 || 250 A 440 V power circuit IEC 60947
  • Product Or Component Type : contactor
  • Range : TeSys || TeSys Deca
  • Safety Reliability Level : B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
  • Electrical Durability : 0.8 Mcycles 25 A AC-1 <= 440 V
  • [Uc] Control Circuit Voltage : 230 V AC 50/60 Hz
  • Auxiliary Contact Composition : 1 NO + 1 NC
  • [Ith] Conventional Free Air Thermal Current : 10 A 60 °C signalling circuit || 25 A 60 °C power circuit
  • Pole Contact Composition : 4 NO
  • Product Name : TeSys D || TeSys Deca
  • Control Circuit Type : AC 50/60 Hz
  • Product Certifications : UL || BV || CCC || LROS (Lloyds register of shipping) || DNV || CSA || RINA || GOST || GL
  • [Ui] Rated Insulation Voltage : power circuit 600 V CSA || power circuit 600 V UL || signalling circuit 690 V IEC 60947-1 || signalling circuit 600 V CSA || signalling circuit 600 V UL || power circuit 690 V IEC 60947-4-1
  • [Ie] Rated Operational Current : 25 A 60 °C) <= 440 V AC AC-1 power circuit
  • Standards : CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508 || IEC 60335-1
  • Average Impedance : 2.5 mOhm - Ith 25 A 50 Hz power circuit
  • Tightening Torque : control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || power circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || power circuit 1.7 N.m screw clamp terminals Philips No 2 || control circuit 1.7 N.m screw clamp terminals pozidriv No 2 || power circuit 2.5 N.m screw clamp terminals pozidriv No 2
  • Operating Time : 4...19 ms opening || 12...22 ms closing
  • Overvoltage Category : III
  • Mounting Support : plate || rail
  • Connections - Terminals : control circuit screw clamp terminals 2 1-2.5 mm²flexible with cable end || control circuit screw clamp terminals 1 1-4 mm²flexible without cable end || control circuit screw clamp terminals 2 1-4 mm²flexible without cable end || control circuit screw clamp terminals 1 1-4 mm²flexible with cable end || control circuit screw clamp terminals 1 1-4 mm²solid without cable end || control circuit screw clamp terminals 2 1-4 mm²solid without cable end || power circuit screw clamp terminals 1 1-4 mm²flexible without cable end || power circuit screw clamp terminals 2 1-4 mm²flexible without cable end || power circuit screw clamp terminals 1 1-4 mm²flexible with cable end || power circuit screw clamp terminals 2 1-2.5 mm²flexible with cable end || power circuit screw clamp terminals 1 1-4 mm²solid without cable end || power circuit screw clamp terminals 2 1-4 mm²solid without cable end
  • Associated Fuse Rating : 10 A gG signalling circuit IEC 60947-5-1 || 40 A gG <= 690 V type 1 power circuit || 25 A gG <= 690 V type 2 power circuit
  • Utilisation Category : AC-1
  • Mechanical Durability : 15 Mcycles