IEC contactor, TeSys D, nonreversing, 200A resistive, 4 pole, 4 NO, 115VAC 50/60Hz coil, open style

IEC contactor, TeSys D, nonreversing, 200A resistive, 4 pole, 4 NO, 115VAC 50/60Hz coil, open style

SQDLC1D115004FE7 LC1D115004FE7 338911096369
0.00 / EA
  • Certifications: BV, CCC, CSA, DNV, GL, GOST, LROS (Lloyds Register Of Shipping), RINA, UKCA, UL
  • Contact Configuration: 4 NO
  • Depth: 132 mm
  • Height: 158 mm
  • Impedance: 0.6 MOhm - Ith 200 A 50 Hz Power Circuit
  • Net Weight: 2.86 kg
  • Standard: CSA C22.2 No 14, EN 60947-4-1, EN 60947-5-1, IEC 60947-4-1, IEC 60947-5-1, UL 508
  • Storage Temperature: -60-80 °C
  • Warranty Length: 18 mth
  • Width: 150 mm
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 4 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactor has four normally open power contacts. Power contacts have a 200A resistive load rating. Contactor is supplied with a 115 VAC 50/60 Hz coil. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 6.22 inches tall, 5.91 inches wide and 5.20 inches deep. It weighs 6.31 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
  • Product Description
  • Specifications
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 4 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactor has four normally open power contacts. Power contacts have a 200A resistive load rating. Contactor is supplied with a 115 VAC 50/60 Hz coil. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 6.22 inches tall, 5.91 inches wide and 5.20 inches deep. It weighs 6.31 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
  • Complementary
    • Heat Dissipation : 3-8 W 50/60 Hz
    • Inrush Power In Va : 280-350 VA 60 Hz 0.8 20 °C) || 280-350 VA 50 Hz 0.8 20 °C)
    • Control Circuit Voltage Limits : 0.3...0.5 Uc -40-70 °C drop-out AC 50/60 Hz || 0.8...1.15 Uc -40-55 °C operational AC 50/60 Hz || 1...1.15 Uc 55-70 °C operational AC 50/60 Hz
    • Hold-In Power Consumption In Va : 2-18 VA 60 Hz 0.3 20 °C) || 2-18 VA 50 Hz 0.3 20 °C)
    • Coil Technology : built-in bidirectional peak limiting diode suppressor
  • Contractual warranty
    • Warranty : 18 months
  • Offer Sustainability
    • Mercury Free : Yes
    • Eu Rohs Directive : Compliant
    • Reach Regulation : Free of Substances of Very High Concern above the threshold
    • Circularity Profile : ENVEOLI100405EN
    • Environmental Disclosure : ENVPEP060301EN
    • Pvc Free : Yes
    • Rohs Exemption Information : Yes
    • Weee : The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
    • China Rohs Regulation : Product out of China RoHS scope. Substance declaration for your information.
    • Sustainable Offer Status : Green Premium product
    • California Proposition 65 : WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
  • Environment
    • Height : 158 mm
    • Pollution Degree : 3
    • Ambient Air Temperature For Storage : -60-80 °C
    • Ambient Air Temperature For Operation : -40-60 °C || 60-70 °C with derating
    • Net Weight : 2.86 kg
    • Width : 150 mm
    • Protective Treatment : TH IEC 60068-2-30
    • Depth : 132 mm
    • Fire Resistance : 850 °C IEC 60695-2-1
    • Operating Altitude : 0...9842.52 ft (0...3000 m)
    • Flame Retardance : V1 conforming to UL 94
    • Ip Degree Of Protection : IP20 front face IEC 60529
    • Mechanical Robustness : vibrations contactor open2 Gn, 5...300 Hz || vibrations contactor closed4 Gn, 5...300 Hz || shocks contactor closed15 Gn for 11 ms || shocks contactor open6 Gn for 11 ms
  • Range : TeSys
  • [Ui] Rated Insulation Voltage : power circuit 600 V CSA || power circuit 600 V UL || power circuit 1000 V IEC 60947-4-1
  • [Ie] Rated Operational Current : 200 A 60 °C) <= 440 V AC AC-1 power circuit
  • [Ue] Rated Operational Voltage : power circuit <= 1000 V AC 25...400 Hz || power circuit <= 460 V DC
  • Product Or Component Type : contactor
  • Mechanical Durability : 8 Mcycles
  • Safety Reliability Level : B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
  • Maximum Operating Rate : 2400 cyc/h 60 °C
  • Utilisation Category : AC-1
  • [Icw] Rated Short-Time Withstand Current : 250 A 40 °C - 10 min power circuit || 550 A 40 °C - 1 min power circuit || 950 A 40 °C - 10 s power circuit || 1100 A 40 °C - 1 s power circuit
  • Average Impedance : 0.6 mOhm - Ith 200 A 50 Hz power circuit
  • Connections - Terminals : control circuit screw clamp terminals 2 1-2.5 mm²flexible with cable end || control circuit screw clamp terminals 1 1-2.5 mm²flexible with cable end || control circuit screw clamp terminals 1 1-2.5 mm²flexible without cable end || control circuit screw clamp terminals 2 1-2.5 mm²flexible without cable end || control circuit screw clamp terminals 1 1-2.5 mm²solid without cable end || control circuit screw clamp terminals 2 1-2.5 mm²solid without cable end || power circuit connector 1 10-120 mm²flexible without cable end || power circuit connector 2 10-50 mm²flexible without cable end || power circuit connector 1 10-120 mm²flexible with cable end || power circuit connector 2 10-50 mm²flexible with cable end || power circuit connector 1 10-120 mm²solid without cable end || power circuit connector 2 10-50 mm²solid without cable end
  • Rated Breaking Capacity : 1100 A 440 V power circuit IEC 60947
  • Device Short Name : LC1D
  • Standards : CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508
  • Power Dissipation Per Pole : 24 W AC-1
  • Electrical Durability : 0.8 Mcycles 200 A AC-1 <= 440 V
  • Product Certifications : UL || DNV || CCC || CSA || GOST || LROS (Lloyds register of shipping) || RINA || GL || BV || UKCA
  • Protective Cover : with
  • Pole Contact Composition : 4 NO
  • Overvoltage Category : III
  • [Uc] Control Circuit Voltage : 115 V AC 50/60 Hz
  • Operating Time : 6...20 ms opening || 20...50 ms closing
  • [Ith] Conventional Free Air Thermal Current : 200 A 60 °C power circuit
  • Product Name : TeSys D
  • Irms Rated Making Capacity : 1260 A 440 V power circuit IEC 60947
  • Contactor Application : resistive load
  • Mounting Support : plate || rail
  • Control Circuit Type : AC 50/60 Hz
  • [Uimp] Rated Impulse Withstand Voltage : 8 kV IEC 60947
  • Associated Fuse Rating : 250 A gG <= 690 V type 1 power circuit || 200 A gG <= 690 V type 2 power circuit
  • Poles Description : 4P
  • Tightening Torque : control circuit 1.2 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.2 N.m screw clamp terminals Philips No 2 || power circuit 12 N.m connector hexagonal 4 mm