IEC contactor, TeSys D, nonreversing, 20A resistive, 4 pole, 4 NO, 110VDC coil, open style

IEC contactor, TeSys D, nonreversing, 20A resistive, 4 pole, 4 NO, 110VDC coil, open style

SQDLC1DT20FD LC1DT20FD 785901631347
145.48 / EA
  • Certifications: BV, CCC, CSA, DNV, GL, GOST, LROS (Lloyds Register Of Shipping), RINA, UL
  • Contact Configuration: 1 NO + 1 NC
  • Contact Configuration: 4 NO
  • Depth: 99 mm
  • Height: 85 mm
  • Impedance: 2.5 MOhm - Ith 20 A 50 Hz Power Circuit
  • Net Weight: 0.365 kg
  • Standard: CSA C22.2 No 14, EN 60947-4-1, EN 60947-5-1, IEC 60947-4-1, IEC 60947-5-1, UL 508
  • Storage Temperature: -60-80 °C
  • Warranty Length: 18 mth
  • Width: 45 mm
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 4 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactor has four normally open power contacts. Power contacts have a 20A resistive load rating. Contactor is supplied with a 110 VDC coil with transient suppressor module. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.35 inches tall, 1.77 inches wide and 3.90 inches deep. It weighs 0.80 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
  • Product Description
  • Specifications
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 4 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactor has four normally open power contacts. Power contacts have a 20A resistive load rating. Contactor is supplied with a 110 VDC coil with transient suppressor module. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.35 inches tall, 1.77 inches wide and 3.90 inches deep. It weighs 0.80 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
  • Offer Sustainability
    • Reach Regulation : Free of Substances of Very High Concern above the threshold
    • Circularity Profile : ENVEOLI1102030EN
    • California Proposition 65 : WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
    • Eu Rohs Directive : Compliant
    • Environmental Disclosure : ENVPEP110230EN
    • Sustainable Offer Status : Green Premium product
    • Rohs Exemption Information : Yes
    • Mercury Free : Yes
    • China Rohs Regulation : Product out of China RoHS scope. Substance declaration for your information.
    • Weee : The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
    • Pvc Free : Yes
  • Environment
    • Ip Degree Of Protection : IP20 front face IEC 60529
    • Ambient Air Temperature For Operation : -40-60 °C || 60-70 °C with derating
    • Mechanical Robustness : vibrations contactor open2 Gn, 5...300 Hz || vibrations contactor closed4 Gn, 5...300 Hz || shocks contactor closed15 Gn for 11 ms || shocks contactor open10 Gn for 11 ms
    • Maximum Depth : 99 mm
    • Maximum Height : 85 mm
    • Operating Altitude : 0...9842.52 ft (0...3000 m)
    • Protective Treatment : TH IEC 60068-2-30
    • Pollution Degree : 3
    • Fire Resistance : 850 °C IEC 60695-2-1
    • Flame Retardance : V1 conforming to UL 94
    • Ambient Air Temperature For Storage : -60-80 °C
    • Net Weight : 0.365 kg
    • Maximum Width : 45 mm
  • Product Or Component Type : contactor
  • Utilisation Category : AC-1
  • Mounting Support : rail || plate
  • Overvoltage Category : III
  • Standards : CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508
  • Connections - Terminals : control circuit screw clamp terminals 2 1-2.5 mm²flexible with cable end || control circuit screw clamp terminals 1 1-4 mm²flexible without cable end || control circuit screw clamp terminals 2 1-4 mm²flexible without cable end || control circuit screw clamp terminals 1 1-4 mm²flexible with cable end || control circuit screw clamp terminals 1 1-4 mm²solid without cable end || control circuit screw clamp terminals 2 1-4 mm²solid without cable end || power circuit screw clamp terminals 1 1-4 mm²flexible without cable end || power circuit screw clamp terminals 2 1-4 mm²flexible without cable end || power circuit screw clamp terminals 1 1-4 mm²flexible with cable end || power circuit screw clamp terminals 2 1-2.5 mm²flexible with cable end || power circuit screw clamp terminals 1 1-4 mm²solid without cable end || power circuit screw clamp terminals 2 1-4 mm²solid without cable end
  • [Ue] Rated Operational Voltage : power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
  • Associated Fuse Rating : 10 A gG signalling circuit IEC 60947-5-1 || 25 A gG <= 690 V type 1 power circuit || 20 A gG <= 690 V type 2 power circuit
  • Operating Time : 16...24 ms opening || 53.55...72.45 ms closing
  • Contactor Application : resistive load
  • Maximum Operating Rate : 3600 cyc/h 60 °C
  • Average Impedance : 2.5 mOhm - Ith 20 A 50 Hz power circuit
  • [Uc] Control Circuit Voltage : 110 V DC
  • Irms Rated Making Capacity : 140 A AC signalling circuit IEC 60947-5-1 || 250 A DC signalling circuit IEC 60947-5-1 || 250 A 440 V power circuit IEC 60947
  • Control Circuit Type : DC standard
  • [Icw] Rated Short-Time Withstand Current : 30 A 40 °C - 10 min power circuit || 61 A 40 °C - 1 min power circuit || 105 A 40 °C - 10 s power circuit || 210 A 40 °C - 1 s power circuit || 100 A - 1 s signalling circuit || 120 A - 500 ms signalling circuit || 140 A - 100 ms signalling circuit
  • Power Dissipation Per Pole : 1.56 W AC-1
  • [Ie] Rated Operational Current : 20 A 60 °C) <= 440 V AC AC-1 power circuit
  • Product Certifications : DNV || GOST || BV || UL || CCC || GL || LROS (Lloyds register of shipping) || RINA || CSA
  • Product Name : TeSys D
  • [Uimp] Rated Impulse Withstand Voltage : 6 kV IEC 60947
  • Safety Reliability Level : B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
  • [Ui] Rated Insulation Voltage : power circuit 600 V CSA || power circuit 600 V UL || signalling circuit 690 V IEC 60947-1 || signalling circuit 600 V CSA || signalling circuit 600 V UL || power circuit 690 V IEC 60947-4-1
  • Mechanical Durability : 30 Mcycles
  • Auxiliary Contact Composition : 1 NO + 1 NC
  • [Ith] Conventional Free Air Thermal Current : 10 A 60 °C signalling circuit || 20 A 60 °C power circuit
  • Pole Contact Composition : 4 NO
  • Tightening Torque : control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || power circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || power circuit 1.7 N.m screw clamp terminals Philips No 2
  • Protective Cover : with
  • Poles Description : 4P
  • Rated Breaking Capacity : 250 A 440 V power circuit IEC 60947
  • Device Short Name : LC1D
  • Range : TeSys
  • Complementary
    • Minimum Switching Current : 5 mA signalling circuit
    • Time Constant : 28 ms
    • Non-Overlap Time : 1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
    • Signalling Circuit Frequency : 25...400 Hz
    • Inrush Power In W : 5.4-5.4 W 20 °C)
    • Coil Technology : built-in bidirectional peak limiting diode suppressor
    • Control Circuit Voltage Limits : 0.1...0.25 Uc -40-70 °C drop-out DC || 0.7...1.25 Uc -40-60 °C operational DC || 1...1.25 Uc 60-70 °C operational DC
    • Hold-In Power Consumption In W : 5.4-5.4 W 20 °C
    • Insulation Resistance : > 10 MOhm signalling circuit
    • Auxiliary Contacts Type : mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
    • Minimum Switching Voltage : 17 V signalling circuit
  • Contractual warranty
    • Warranty : 18 months