Schneider Electric at Mayer

IEC contactor, TeSys D, nonreversing, 40A resistive, 4 pole, 2 NO and 2 NC, 48VAC 50/60Hz coil, open style

CONTACTOR 600VAC 25AMP IEC +OP

SQDLC1D258E7 LC1D258E7 785901676355
224.25 / EACH
  • Certifications: BV, CCC, CSA, DNV, GL, GOST, LROS (Lloyds Register Of Shipping), RINA, UKCA, UL
  • Contact Configuration: 1 NO + 1 NC, 2 NO + 2 NC
  • Depth: 99 mm
  • Height: 105 mm
  • Impedance: 2 MOhm - Ith 40 A 50 Hz Power Circuit
  • Net Weight: 0.425 kg
  • Standard: CSA C22.2 No 14, EN 60947-4-1, EN 60947-5-1, IEC 60335-1, IEC 60947-4-1, IEC 60947-5-1, UL 508
  • Storage Temperature: -60-80 °C
  • Warranty Length: 18 mth
  • Width: 45 mm
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 4 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactor has two normally open and two normally closed power contacts. Power contacts have a 40A resistive load rating. Contactor is supplied with a 48 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 4.13 inches tall, 1.77 inches wide and 3.90 inches deep. It weighs 0.94 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
  • Product Description
  • Specifications
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 4 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactor has two normally open and two normally closed power contacts. Power contacts have a 40A resistive load rating. Contactor is supplied with a 48 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 4.13 inches tall, 1.77 inches wide and 3.90 inches deep. It weighs 0.94 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
  • Contractual warranty
    • Warranty : 18 months
  • Complementary
    • Signalling Circuit Frequency : 25...400 Hz
    • Minimum Switching Voltage : 17 V signalling circuit
    • Inrush Power In Va : 70-70 VA 60 Hz 0.75 20 °C) || 70-70 VA 50 Hz 0.75 20 °C)
    • Minimum Switching Current : 5 mA signalling circuit
    • Coil Technology : without built-in suppressor module
    • Hold-In Power Consumption In Va : 7.5-7.5 VA 60 Hz 0.3 20 °C) || 7-7 VA 50 Hz 0.3 20 °C)
    • Auxiliary Contacts Type : mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
    • Heat Dissipation : 2-3 W 50/60 Hz
    • Non-Overlap Time : 1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
    • Control Circuit Voltage Limits : 0.3...0.6 Uc -40-70 °C drop-out AC 50/60 Hz || 0.8...1.1 Uc -40-60 °C operational AC 50 Hz || 0.85...1.1 Uc -40-60 °C operational AC 60 Hz || 1...1.1 Uc 60-70 °C operational AC 50/60 Hz
    • Insulation Resistance : > 10 MOhm signalling circuit
  • Associated Fuse Rating : 10 A gG signalling circuit IEC 60947-5-1 || 63 A gG <= 690 V type 1 power circuit || 40 A gG <= 690 V type 2 power circuit
  • Maximum Operating Rate : 3600 cyc/h 60 °C
  • Device Short Name : LC1D
  • Mounting Support : rail || plate
  • [Ui] Rated Insulation Voltage : power circuit 690 V IEC 60947-4-1 || power circuit 600 V CSA || power circuit 600 V UL || signalling circuit 690 V IEC 60947-1 || signalling circuit 600 V CSA || signalling circuit 600 V UL
  • Protective Cover : with
  • [Uimp] Rated Impulse Withstand Voltage : 6 kV IEC 60947
  • Tightening Torque : control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || power circuit 1.8 N.m connector flat Ø 6 mm || power circuit 1.8 N.m connector Philips No 2 || control circuit 1.7 N.m screw clamp terminals pozidriv No 2 || power circuit 2.5 N.m screw clamp terminals pozidriv No 2
  • Rated Breaking Capacity : 450 A 440 V power circuit IEC 60947
  • Pole Contact Composition : 2 NO + 2 NC
  • Product Certifications : DNV || RINA || GL || CCC || CSA || GOST || BV || LROS (Lloyds register of shipping) || UL || UKCA
  • Average Impedance : 2 mOhm - Ith 40 A 50 Hz power circuit
  • [Uc] Control Circuit Voltage : 48 V AC 50/60 Hz
  • Product Name : TeSys D || TeSys Deca
  • Overvoltage Category : III
  • [Ue] Rated Operational Voltage : power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
  • Electrical Durability : 1.4 Mcycles 40 A AC-1 <= 440 V
  • Range : TeSys || TeSys Deca
  • [Icw] Rated Short-Time Withstand Current : 240 A 40 °C - 10 s power circuit || 380 A 40 °C - 1 s power circuit || 50 A 40 °C - 10 min power circuit || 120 A 40 °C - 1 min power circuit || 100 A - 1 s signalling circuit || 120 A - 500 ms signalling circuit || 140 A - 100 ms signalling circuit
  • Contactor Application : resistive load
  • Poles Description : 4P
  • Mechanical Durability : 15 Mcycles
  • Product Or Component Type : contactor
  • [Ith] Conventional Free Air Thermal Current : 10 A 60 °C signalling circuit || 40 A 60 °C power circuit
  • Standards : CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508 || IEC 60335-1
  • Power Dissipation Per Pole : 3.2 W AC-1
  • Utilisation Category : AC-1
  • Control Circuit Type : AC 50/60 Hz
  • Irms Rated Making Capacity : 140 A AC signalling circuit IEC 60947-5-1 || 250 A DC signalling circuit IEC 60947-5-1 || 450 A 440 V power circuit IEC 60947
  • Operating Time : 12...22 ms closing || 4...19 ms opening
  • [Ie] Rated Operational Current : 40 A 60 °C) <= 440 V AC AC-1 power circuit
  • Auxiliary Contact Composition : 1 NO + 1 NC
  • Connections - Terminals : control circuit screw clamp terminals 1 1-4 mm²flexible without cable end || control circuit screw clamp terminals 2 1-4 mm²flexible without cable end || control circuit screw clamp terminals 1 1-4 mm²flexible with cable end || control circuit screw clamp terminals 2 1-2.5 mm²flexible with cable end || control circuit screw clamp terminals 1 1-4 mm²solid without cable end || control circuit screw clamp terminals 2 1-4 mm²solid without cable end || power circuit connector 1 2.5-10 mm²flexible without cable end || power circuit connector 2 2.5-10 mm²flexible without cable end || power circuit connector 1 2.5-10 mm²flexible with cable end || power circuit connector 2 2.5-10 mm²flexible with cable end || power circuit connector 1 2.5-16 mm²solid without cable end || power circuit connector 2 2.5-16 mm²solid without cable end
  • Safety Reliability Level : B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
  • Offer Sustainability
    • Mercury Free : Yes
    • Circularity Profile : ENVEOLI1102029EN
    • Environmental Disclosure : ENVPEP110229EN
    • Eu Rohs Directive : Compliant
    • Toxic Heavy Metal Free : Yes
    • Reach Free Of Svhc : Yes
    • Sustainable Offer Status : Green Premium product
    • China Rohs Regulation : Pro-active China RoHS declaration (out of China RoHS legal scope)
    • Reach Regulation : Free of Substances of Very High Concern above the threshold
    • Weee : The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
    • Pvc Free : Yes
    • California Proposition 65 : WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
    • Rohs Exemption Information : Yes
  • Environment
    • Ip Degree Of Protection : IP20 front face IEC 60529
    • Mechanical Robustness : vibrations contactor open2 Gn, 5...300 Hz || vibrations contactor closed4 Gn, 5...300 Hz || shocks contactor closed15 Gn for 11 ms || shocks contactor open8 Gn for 11 ms
    • Height : 105 mm
    • Pollution Degree : 3
    • Ambient Air Temperature For Storage : -60-80 °C
    • Width : 45 mm
    • Net Weight : 0.425 kg
    • Protective Treatment : TH IEC 60068-2-30
    • Ambient Air Temperature For Operation : -40-60 °C || 60-70 °C with derating
    • Depth : 99 mm
    • Flame Retardance : V1 conforming to UL 94
    • Fire Resistance : 850 °C IEC 60695-2-1
    • Operating Altitude : 0...9842.52 ft (0...3000 m)