IEC contactor, TeSys D, nonreversing, 32A resistive, 4 pole, 2 NO and 2 NC, 240VAC 50/60HZ coil, open style

IEC contactor, TeSys D, nonreversing, 32A resistive, 4 pole, 2 NO and 2 NC, 240VAC 50/60HZ coil, open style

SQDLC1D188U7 LC1D188U7 785901072782
177.20 / EACH
  • Certifications: BV, CCC, CSA, DNV, GL, GOST, LROS (Lloyds Register Of Shipping), RINA, UKCA, UL
  • Contact Configuration: 1 NO + 1 NC
  • Contact Configuration: 2 NO + 2 NC
  • Depth: 99 mm
  • Height: 105 mm
  • Impedance: 2.5 MOhm - Ith 32 A 50 Hz Power Circuit
  • Net Weight: 0.425 kg
  • Standard: CSA C22.2 No 14, EN 60947-4-1, EN 60947-5-1, IEC 60947-4-1, IEC 60947-5-1, UL 508
  • Storage Temperature: -60-80 °C
  • Warranty Length: 18 mth
  • Width: 45 mm
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 4 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactor has two normally open and two normally closed power contacts. Power contacts have a 32A resistive load rating. Contactor is supplied with a 240 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 4.13 inches tall, 1.77 inches wide and 3.90 inches deep. It weighs 0.94 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
  • Product Description
  • Specifications
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 4 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactor has two normally open and two normally closed power contacts. Power contacts have a 32A resistive load rating. Contactor is supplied with a 240 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 4.13 inches tall, 1.77 inches wide and 3.90 inches deep. It weighs 0.94 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
  • [Ue] Rated Operational Voltage : power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
  • Power Dissipation Per Pole : 2.5 W AC-1
  • Device Short Name : LC1D
  • Mechanical Durability : 15 Mcycles
  • [Ith] Conventional Free Air Thermal Current : 10 A 60 °C signalling circuit || 32 A 60 °C power circuit
  • Operating Time : 12...22 ms closing || 4...19 ms opening
  • Connections - Terminals : control circuit screw clamp terminals 1 1-4 mm²flexible without cable end || control circuit screw clamp terminals 2 1-4 mm²flexible without cable end || control circuit screw clamp terminals 1 1-4 mm²flexible with cable end || control circuit screw clamp terminals 2 1-2.5 mm²flexible with cable end || control circuit screw clamp terminals 1 1-4 mm²solid without cable end || control circuit screw clamp terminals 2 1-4 mm²solid without cable end || power circuit connector 1 2.5-10 mm²flexible without cable end || power circuit connector 2 2.5-10 mm²flexible without cable end || power circuit connector 1 2.5-10 mm²flexible with cable end || power circuit connector 2 2.5-10 mm²flexible with cable end || power circuit connector 1 2.5-16 mm²solid without cable end || power circuit connector 2 2.5-16 mm²solid without cable end
  • Range : TeSys
  • Standards : CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508
  • Maximum Operating Rate : 3600 cyc/h 60 °C
  • Product Certifications : DNV || CSA || UL || BV || GOST || LROS (Lloyds register of shipping) || GL || RINA || CCC || UKCA
  • Contactor Application : resistive load
  • Control Circuit Type : AC 50/60 Hz
  • [Ui] Rated Insulation Voltage : power circuit 690 V IEC 60947-4-1 || power circuit 600 V CSA || power circuit 600 V UL || signalling circuit 690 V IEC 60947-1 || signalling circuit 600 V CSA || signalling circuit 600 V UL
  • [Uc] Control Circuit Voltage : 240 V AC 50/60 Hz
  • [Icw] Rated Short-Time Withstand Current : 145 A 40 °C - 10 s power circuit || 240 A 40 °C - 1 s power circuit || 40 A 40 °C - 10 min power circuit || 84 A 40 °C - 1 min power circuit || 100 A - 1 s signalling circuit || 120 A - 500 ms signalling circuit || 140 A - 100 ms signalling circuit
  • Utilisation Category : AC-1
  • Electrical Durability : 1 Mcycles 32 A AC-1 <= 440 V
  • Associated Fuse Rating : 10 A gG signalling circuit IEC 60947-5-1 || 50 A gG <= 690 V type 1 power circuit || 35 A gG <= 690 V type 2 power circuit
  • Pole Contact Composition : 2 NO + 2 NC
  • Tightening Torque : control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || power circuit 1.7 N.m connector flat Ø 6 mm || power circuit 1.7 N.m connector Philips No 2
  • Overvoltage Category : III
  • Product Or Component Type : contactor
  • Safety Reliability Level : B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
  • Poles Description : 4P
  • Irms Rated Making Capacity : 140 A AC signalling circuit IEC 60947-5-1 || 250 A DC signalling circuit IEC 60947-5-1 || 300 A 440 V power circuit IEC 60947
  • Product Name : TeSys D
  • Auxiliary Contact Composition : 1 NO + 1 NC
  • [Uimp] Rated Impulse Withstand Voltage : 6 kV IEC 60947
  • Average Impedance : 2.5 mOhm - Ith 32 A 50 Hz power circuit
  • Protective Cover : with
  • [Ie] Rated Operational Current : 32 A 60 °C) <= 440 V AC AC-1 power circuit
  • Mounting Support : plate || rail
  • Rated Breaking Capacity : 300 A 440 V power circuit IEC 60947
  • Contractual warranty
    • Warranty : 18 months
  • Complementary
    • Heat Dissipation : 2-3 W 50/60 Hz
    • Coil Technology : without built-in suppressor module
    • Insulation Resistance : > 10 MOhm signalling circuit
    • Inrush Power In Va : 70-70 VA 60 Hz 0.75 20 °C) || 70-70 VA 50 Hz 0.75 20 °C)
    • Minimum Switching Voltage : 17 V signalling circuit
    • Control Circuit Voltage Limits : 0.3...0.6 Uc -40-70 °C drop-out AC 50/60 Hz || 0.8...1.1 Uc -40-60 °C operational AC 50 Hz || 0.85...1.1 Uc -40-60 °C operational AC 60 Hz || 1...1.1 Uc 60-70 °C operational AC 50/60 Hz
    • Non-Overlap Time : 1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
    • Auxiliary Contacts Type : mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
    • Signalling Circuit Frequency : 25...400 Hz
    • Hold-In Power Consumption In Va : 7.5-7.5 VA 60 Hz 0.3 20 °C) || 7-7 VA 50 Hz 0.3 20 °C)
    • Minimum Switching Current : 5 mA signalling circuit
  • Environment
    • Operating Altitude : 0...9842.52 ft (0...3000 m)
    • Fire Resistance : 850 °C IEC 60695-2-1
    • Ambient Air Temperature For Storage : -60-80 °C
    • Protective Treatment : TH IEC 60068-2-30
    • Width : 45 mm
    • Ambient Air Temperature For Operation : -40-60 °C || 60-70 °C with derating
    • Mechanical Robustness : vibrations contactor open2 Gn, 5...300 Hz || vibrations contactor closed4 Gn, 5...300 Hz || shocks contactor open10 Gn for 11 ms || shocks contactor closed15 Gn for 11 ms
    • Depth : 99 mm
    • Height : 105 mm
    • Flame Retardance : V1 conforming to UL 94
    • Pollution Degree : 3
    • Ip Degree Of Protection : IP20 front face IEC 60529
    • Net Weight : 0.425 kg
  • Offer Sustainability
    • Reach Free Of Svhc : Yes
    • China Rohs Regulation : Pro-active China RoHS declaration (out of China RoHS legal scope)
    • Weee : The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
    • Reach Regulation : Free of Substances of Very High Concern above the threshold
    • Sustainable Offer Status : Green Premium product
    • California Proposition 65 : WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
    • Pvc Free : Yes
    • Eu Rohs Directive : Compliant
    • Mercury Free : Yes
    • Rohs Exemption Information : Yes
    • Toxic Heavy Metal Free : Yes
    • Environmental Disclosure : ENVPEP1501004EN
    • Circularity Profile : ENVEOLI1501004EN