IEC contactor, TeSys D, nonreversing, 20A resistive, 4 pole, 2 NO and 2 NC, 48VDC coil, open style

CONTACTOR 600VAC 9AMP IEC +OPT

SQDLC1D098ED LC1D098ED 338911040325
0.00 / EA
  • Certifications: BV, CCC, CSA, DNV, GL, GOST, LROS (Lloyds Register Of Shipping), RINA, UKCA, UL
  • Contact Configuration: 1 NO + 1 NC, 2 NO + 2 NC
  • Depth: 99 mm
  • Height: 85 mm
  • Impedance: 2.5 MOhm - Ith 25 A 50 Hz Power Circuit
  • Net Weight: 0.525 kg
  • Standard: CSA C22.2 No 14, EN 60947-4-1, EN 60947-5-1, IEC 60335-1, IEC 60947-4-1, IEC 60947-5-1, UL 508
  • Storage Temperature: -60-80 °C
  • Warranty Length: 18 mth
  • Width: 45 mm
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 4 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactor has two normally open and two normally closed power contacts. Power contacts have a 20A resistive load rating. Contactor is supplied with a 48 VDC coil with transient suppressor module. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Pressure wire connectors are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.35 inches tall, 1.77 inches wide and 3.90 inches deep. It weighs 1.16 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
  • Product Description
  • Specifications
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 4 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactor has two normally open and two normally closed power contacts. Power contacts have a 20A resistive load rating. Contactor is supplied with a 48 VDC coil with transient suppressor module. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Pressure wire connectors are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.35 inches tall, 1.77 inches wide and 3.90 inches deep. It weighs 1.16 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
  • Environment
    • Pollution Degree : 3
    • Protective Treatment : TH IEC 60068-2-30
    • Ip Degree Of Protection : IP20 front face IEC 60529
    • Net Weight : 0.525 kg
    • Width : 45 mm
    • Ambient Air Temperature For Operation : -40-60 °C || 60-70 °C with derating
    • Ambient Air Temperature For Storage : -60-80 °C
    • Mechanical Robustness : vibrations contactor open2 Gn, 5...300 Hz || vibrations contactor closed4 Gn, 5...300 Hz || shocks contactor open10 Gn for 11 ms || shocks contactor closed15 Gn for 11 ms
    • Flame Retardance : V1 conforming to UL 94
    • Operating Altitude : 0...9842.52 ft (0...3000 m)
    • Fire Resistance : 850 °C IEC 60695-2-1
    • Height : 85 mm
    • Depth : 99 mm
  • Contactor Application : resistive load
  • Average Impedance : 2.5 mOhm - Ith 25 A 50 Hz power circuit
  • Maximum Operating Rate : 3600 cyc/h 60 °C
  • Irms Rated Making Capacity : 250 A 440 V power circuit IEC 60947 || 140 A AC signalling circuit IEC 60947-5-1 || 250 A DC signalling circuit IEC 60947-5-1
  • Mounting Support : rail || plate
  • Device Short Name : LC1D
  • Rated Breaking Capacity : 250 A 440 V power circuit IEC 60947
  • Overvoltage Category : III
  • [Uimp] Rated Impulse Withstand Voltage : 6 kV IEC 60947
  • Connections - Terminals : power circuit screw clamp terminals 1 1-4 mm²flexible without cable end || power circuit screw clamp terminals 2 1-4 mm²flexible without cable end || power circuit screw clamp terminals 1 1-4 mm²flexible with cable end || power circuit screw clamp terminals 2 1-2.5 mm²flexible with cable end || power circuit screw clamp terminals 1 1-4 mm²solid without cable end || power circuit screw clamp terminals 2 1-4 mm²solid without cable end || control circuit screw clamp terminals 1 1-4 mm²flexible without cable end || control circuit screw clamp terminals 2 1-4 mm²flexible without cable end || control circuit screw clamp terminals 1 1-4 mm²flexible with cable end || control circuit screw clamp terminals 2 1-2.5 mm²flexible with cable end || control circuit screw clamp terminals 1 1-4 mm²solid without cable end || control circuit screw clamp terminals 2 1-4 mm²solid without cable end
  • Product Name : TeSys D || TeSys Deca
  • [Ue] Rated Operational Voltage : power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
  • [Ith] Conventional Free Air Thermal Current : 25 A 60 °C power circuit || 10 A 60 °C signalling circuit
  • Electrical Durability : 0.6 Mcycles 25 A AC-1 <= 440 V
  • Pole Contact Composition : 2 NO + 2 NC
  • Safety Reliability Level : B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
  • Associated Fuse Rating : 10 A gG signalling circuit IEC 60947-5-1 || 25 A gG <= 690 V type 1 power circuit || 20 A gG <= 690 V type 2 power circuit
  • [Icw] Rated Short-Time Withstand Current : 105 A 40 °C - 10 s power circuit || 210 A 40 °C - 1 s power circuit || 30 A 40 °C - 10 min power circuit || 61 A 40 °C - 1 min power circuit || 100 A - 1 s signalling circuit || 120 A - 500 ms signalling circuit || 140 A - 100 ms signalling circuit
  • Poles Description : 4P
  • Utilisation Category : AC-1
  • Protective Cover : with
  • Product Certifications : UL || GL || CCC || DNV || GOST || RINA || LROS (Lloyds register of shipping) || BV || CSA || UKCA
  • Power Dissipation Per Pole : 1.56 W AC-1
  • Operating Time : 53.55...72.45 ms closing || 16...24 ms opening
  • Auxiliary Contact Composition : 1 NO + 1 NC
  • Tightening Torque : power circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || power circuit 1.7 N.m screw clamp terminals Philips No 2 || control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || control circuit 1.7 N.m screw clamp terminals pozidriv No 2 || power circuit 2.5 N.m screw clamp terminals pozidriv No 2
  • [Ie] Rated Operational Current : 25 A 60 °C) <= 440 V AC AC-1 power circuit
  • Range : TeSys || TeSys Deca
  • Product Or Component Type : contactor
  • [Uc] Control Circuit Voltage : 48 V DC
  • Mechanical Durability : 30 Mcycles
  • Control Circuit Type : DC standard
  • [Ui] Rated Insulation Voltage : power circuit 690 V IEC 60947-4-1 || power circuit 600 V CSA || power circuit 600 V UL || signalling circuit 690 V IEC 60947-1 || signalling circuit 600 V CSA || signalling circuit 600 V UL
  • Standards : CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508 || IEC 60335-1
  • Contractual warranty
    • Warranty : 18 months
  • Offer Sustainability
    • Pvc Free : Yes
    • Rohs Exemption Information : Yes
    • Sustainable Offer Status : Green Premium product
    • China Rohs Regulation : Product out of China RoHS scope. Substance declaration for your information.
    • Weee : The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
    • Environmental Disclosure : ENVPEP110230EN
    • Mercury Free : Yes
    • Reach Regulation : Free of Substances of Very High Concern above the threshold
    • Eu Rohs Directive : Compliant
    • California Proposition 65 : WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
    • Circularity Profile : ENVEOLI1102030EN
  • Complementary
    • Hold-In Power Consumption In W : 5.4-5.4 W 20 °C
    • Insulation Resistance : > 10 MOhm signalling circuit
    • Inrush Power In W : 5.4-5.4 W 20 °C)
    • Minimum Switching Voltage : 17 V signalling circuit
    • Minimum Switching Current : 5 mA signalling circuit
    • Auxiliary Contacts Type : mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
    • Time Constant : 28 ms
    • Coil Technology : built-in bidirectional peak limiting diode suppressor
    • Control Circuit Voltage Limits : 0.1...0.25 Uc -40-70 °C drop-out DC || 0.7...1.25 Uc -40-60 °C operational DC || 1...1.25 Uc 60-70 °C operational DC
    • Non-Overlap Time : 1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
    • Signalling Circuit Frequency : 25...400 Hz