IEC contactor, TeSys D, nonreversing, 20A resistive, 4 pole, 2 NO and 2 NC, 48VAC 50/60Hz coil, open style

CONTACTOR 600VAC 9AMP IEC +OPT

SQDLC1D098E7 LC1D098E7 338911024996
0.00 / EA
  • Certifications: BV, CCC, CSA, DNV, GL, GOST, LROS (Lloyds Register Of Shipping), RINA, UKCA, UL
  • Contact Configuration: 1 NO + 1 NC, 2 NO + 2 NC
  • Depth: 92 mm
  • Height: 85 mm
  • Impedance: 2.5 MOhm - Ith 25 A 50 Hz Power Circuit
  • Net Weight: 0.365 kg
  • Standard: CSA C22.2 No 14, EN 60947-4-1, EN 60947-5-1, IEC 60335-1, IEC 60947-4-1, IEC 60947-5-1, UL 508
  • Storage Temperature: -60-80 °C
  • Warranty Length: 18 mth
  • Width: 45 mm
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 4 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactor has two normally open and two normally closed power contacts. Power contacts have a 20A resistive load rating. Contactor is supplied with a 48 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Pressure wire connectors are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.35 inches tall, 1.77 inches wide and 3.62 inches deep. It weighs 0.80 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
  • Product Description
  • Specifications
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 4 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactor has two normally open and two normally closed power contacts. Power contacts have a 20A resistive load rating. Contactor is supplied with a 48 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Pressure wire connectors are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.35 inches tall, 1.77 inches wide and 3.62 inches deep. It weighs 0.80 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
  • Contractual warranty
    • Warranty : 18 months
  • Safety Reliability Level : B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
  • Auxiliary Contact Composition : 1 NO + 1 NC
  • [Ie] Rated Operational Current : 20 A 60 °C) <= 440 V AC AC-1 power circuit
  • Product Name : TeSys D || TeSys Deca
  • Control Circuit Type : AC 50/60 Hz
  • Utilisation Category : AC-1
  • Product Or Component Type : contactor
  • Overvoltage Category : III
  • Product Certifications : UL || GOST || DNV || CCC || CSA || BV || RINA || LROS (Lloyds register of shipping) || GL || UKCA
  • Power Dissipation Per Pole : 1.56 W AC-1
  • [Icw] Rated Short-Time Withstand Current : 105 A 40 °C - 10 s power circuit || 210 A 40 °C - 1 s power circuit || 30 A 40 °C - 10 min power circuit || 61 A 40 °C - 1 min power circuit || 100 A - 1 s signalling circuit || 120 A - 500 ms signalling circuit || 140 A - 100 ms signalling circuit
  • Electrical Durability : 0.6 Mcycles 25 A AC-1 <= 440 V
  • Connections - Terminals : power circuit screw clamp terminals 1 1-4 mm²flexible without cable end || power circuit screw clamp terminals 2 1-4 mm²flexible without cable end || power circuit screw clamp terminals 1 1-4 mm²flexible with cable end || power circuit screw clamp terminals 2 1-2.5 mm²flexible with cable end || power circuit screw clamp terminals 1 1-4 mm²solid without cable end || power circuit screw clamp terminals 2 1-4 mm²solid without cable end || control circuit screw clamp terminals 1 1-4 mm²flexible without cable end || control circuit screw clamp terminals 2 1-4 mm²flexible without cable end || control circuit screw clamp terminals 1 1-4 mm²flexible with cable end || control circuit screw clamp terminals 2 1-2.5 mm²flexible with cable end || control circuit screw clamp terminals 1 1-4 mm²solid without cable end || control circuit screw clamp terminals 2 1-4 mm²solid without cable end
  • Associated Fuse Rating : 10 A gG signalling circuit IEC 60947-5-1 || 25 A gG <= 690 V type 1 power circuit || 20 A gG <= 690 V type 2 power circuit
  • Average Impedance : 2.5 mOhm - Ith 25 A 50 Hz power circuit
  • [Ith] Conventional Free Air Thermal Current : 25 A 60 °C power circuit || 10 A 60 °C signalling circuit
  • Maximum Operating Rate : 3600 cyc/h 60 °C
  • [Uc] Control Circuit Voltage : 48 V AC 50/60 Hz
  • Operating Time : 12...22 ms closing || 4...19 ms opening
  • Tightening Torque : power circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || power circuit 1.7 N.m screw clamp terminals Philips No 2 || control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || control circuit 1.7 N.m screw clamp terminals pozidriv No 2 || power circuit 2.5 N.m screw clamp terminals pozidriv No 2
  • Irms Rated Making Capacity : 250 A 440 V power circuit IEC 60947 || 140 A AC signalling circuit IEC 60947-5-1 || 250 A DC signalling circuit IEC 60947-5-1
  • Poles Description : 4P
  • Protective Cover : with
  • Device Short Name : LC1D
  • Range : TeSys || TeSys Deca
  • Standards : CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508 || IEC 60335-1
  • [Uimp] Rated Impulse Withstand Voltage : 6 kV IEC 60947
  • Contactor Application : resistive load
  • Pole Contact Composition : 2 NO + 2 NC
  • Mechanical Durability : 15 Mcycles
  • Mounting Support : plate || rail
  • [Ui] Rated Insulation Voltage : power circuit 690 V IEC 60947-4-1 || power circuit 600 V CSA || power circuit 600 V UL || signalling circuit 690 V IEC 60947-1 || signalling circuit 600 V CSA || signalling circuit 600 V UL
  • [Ue] Rated Operational Voltage : power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
  • Rated Breaking Capacity : 250 A 440 V power circuit IEC 60947
  • Environment
    • Net Weight : 0.365 kg
    • Operating Altitude : 0...9842.52 ft (0...3000 m)
    • Mechanical Robustness : vibrations contactor open2 Gn, 5...300 Hz || vibrations contactor closed4 Gn, 5...300 Hz || shocks contactor open10 Gn for 11 ms || shocks contactor closed15 Gn for 11 ms
    • Width : 45 mm
    • Height : 85 mm
    • Protective Treatment : TH IEC 60068-2-30
    • Flame Retardance : V1 conforming to UL 94
    • Pollution Degree : 3
    • Fire Resistance : 850 °C IEC 60695-2-1
    • Ambient Air Temperature For Operation : -40-60 °C || 60-70 °C with derating
    • Ip Degree Of Protection : IP20 front face IEC 60529
    • Depth : 92 mm
    • Ambient Air Temperature For Storage : -60-80 °C
  • Offer Sustainability
    • Reach Free Of Svhc : Yes
    • Reach Regulation : Free of Substances of Very High Concern above the threshold
    • Pvc Free : Yes
    • Environmental Disclosure : ENVPEP1501004EN
    • Circularity Profile : ENVEOLI1501004EN
    • Mercury Free : Yes
    • Toxic Heavy Metal Free : Yes
    • Rohs Exemption Information : Yes
    • Eu Rohs Directive : Compliant
    • California Proposition 65 : WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
    • China Rohs Regulation : Pro-active China RoHS declaration (out of China RoHS legal scope)
    • Weee : The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
    • Sustainable Offer Status : Green Premium product
  • Complementary
    • Inrush Power In Va : 70-70 VA 60 Hz 0.75 20 °C) || 70-70 VA 50 Hz 0.75 20 °C)
    • Hold-In Power Consumption In Va : 7.5-7.5 VA 60 Hz 0.3 20 °C) || 7-7 VA 50 Hz 0.3 20 °C)
    • Signalling Circuit Frequency : 25...400 Hz
    • Minimum Switching Current : 5 mA signalling circuit
    • Auxiliary Contacts Type : mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
    • Minimum Switching Voltage : 17 V signalling circuit
    • Coil Technology : without built-in suppressor module
    • Insulation Resistance : > 10 MOhm signalling circuit
    • Heat Dissipation : 2-3 W 50/60 Hz
    • Control Circuit Voltage Limits : 0.3...0.6 Uc -40-70 °C drop-out AC 50/60 Hz || 0.8...1.1 Uc -40-60 °C operational AC 50 Hz || 0.85...1.1 Uc -40-60 °C operational AC 60 Hz || 1...1.1 Uc 60-70 °C operational AC 50/60 Hz
    • Non-Overlap Time : 1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact