IEC contactor, TeSys D, nonreversing, 9A, 5HP at 480VAC, 3 phase, 3 pole, 3 NO, low consumption 24VDC coil, open style

IEC contactor, TeSys D, nonreversing, 9A, 5HP at 480VAC, 3 phase, 3 pole, 3 NO, low consumption 24VDC coil, open style

SQDLC1D093BL LC1D093BL 785901234326
130.17 / EACH
  • Certifications: BV, CCC, CSA, DNV, GL, GOST, LROS (Lloyds Register Of Shipping), RINA, UKCA, UL
  • Contact Configuration: 1 NO + 1 NC
  • Contact Configuration: 3 NO
  • Depth: 95 mm
  • Height: 99 mm
  • Impedance: 2.5 MOhm - Ith 16 A 50 Hz Power Circuit
  • Net Weight: 0.48 kg
  • Standard: CSA C22.2 No 14, EN 60947-4-1, EN 60947-5-1, IEC 60947-4-1, IEC 60947-5-1, UL 508
  • Storage Temperature: -60-80 °C
  • Warranty Length: 18 mth
  • Width: 45 mm
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 9A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 2HP at 200 to 208VAC, 2HP at 240VAC, 5HP at 480VAC and 7.5HP at 600VAC three phase. Contactor is also rated for 0.33HP at 115VAC and 1HP at 240VAC single phase. Contactor is supplied with a low consumption 24 VDC coil with transient suppressor module. Contactor has one normally open and one normally closed auxiliary contact built-in as stanard. The NC contact is mirror certified. Spring terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.15 inches tall, 1.77 inches wide and 3.74 inches deep. It weighs 1.06 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
  • Product Description
  • Specifications
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 9A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 2HP at 200 to 208VAC, 2HP at 240VAC, 5HP at 480VAC and 7.5HP at 600VAC three phase. Contactor is also rated for 0.33HP at 115VAC and 1HP at 240VAC single phase. Contactor is supplied with a low consumption 24 VDC coil with transient suppressor module. Contactor has one normally open and one normally closed auxiliary contact built-in as stanard. The NC contact is mirror certified. Spring terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.15 inches tall, 1.77 inches wide and 3.74 inches deep. It weighs 1.06 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
  • Offer Sustainability
    • Reach Regulation : Free of Substances of Very High Concern above the threshold
    • Pvc Free : Yes
    • China Rohs Regulation : Pro-active China RoHS declaration (out of China RoHS legal scope)
    • Toxic Heavy Metal Free : Yes
    • Circularity Profile : ENVEOLI1501004EN
    • Rohs Exemption Information : Yes
    • Weee : The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
    • Reach Free Of Svhc : Yes
    • Eu Rohs Directive : Compliant
    • Sustainable Offer Status : Green Premium product
    • Environmental Disclosure : ENVPEP1501004EN
    • Mercury Free : Yes
    • California Proposition 65 : WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
  • Complementary
    • Minimum Switching Current : 5 mA signalling circuit
    • Hold-In Power Consumption In W : 2.4-2.4 W 20 °C
    • Non-Overlap Time : 1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
    • Minimum Switching Voltage : 17 V signalling circuit
    • Auxiliary Contacts Type : mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
    • Inrush Power In W : 2.4-2.4 W 20 °C)
    • Time Constant : 40 ms
    • Insulation Resistance : > 10 MOhm signalling circuit
    • Signalling Circuit Frequency : 25...400 Hz
    • Control Circuit Voltage Limits : 0.1...0.3 Uc -40-70 °C drop-out DC || 0.8...1.25 Uc -40-60 °C operational DC || 1...1.25 Uc 60-70 °C operational DC
    • Coil Technology : built-in bidirectional peak limiting diode suppressor
  • Contractual warranty
    • Warranty : 18 months
  • Environment
    • Net Weight : 0.48 kg
    • Fire Resistance : 850 °C IEC 60695-2-1
    • Ip Degree Of Protection : IP20 front face IEC 60529
    • Operating Altitude : 0...9842.52 ft (0...3000 m)
    • Ambient Air Temperature For Operation : -40-60 °C || 60-70 °C with derating
    • Protective Treatment : TH IEC 60068-2-30
    • Depth : 95 mm
    • Pollution Degree : 3
    • Flame Retardance : V1 conforming to UL 94
    • Height : 99 mm
    • Width : 45 mm
    • Mechanical Robustness : vibrations contactor open2 Gn, 5...300 Hz || vibrations contactor closed4 Gn, 5...300 Hz || shocks contactor open10 Gn for 11 ms || shocks contactor closed15 Gn for 11 ms
    • Ambient Air Temperature For Storage : -60-80 °C
  • [Ie] Rated Operational Current : 9 A 60 °C) <= 440 V AC AC-3 power circuit || 25 A 60 °C) <= 440 V AC AC-1 power circuit
  • Contactor Application : resistive load || motor control
  • Pole Contact Composition : 3 NO
  • Product Certifications : UL || GOST || CSA || CCC || GL || BV || LROS (Lloyds register of shipping) || DNV || RINA || UKCA
  • Range : TeSys
  • Connections - Terminals : power circuit spring terminals 1 2.5-2.5 mm²flexible without cable end || power circuit spring terminals 2 2.5-2.5 mm²flexible without cable end || control circuit spring terminals 1 2.5-2.5 mm²flexible without cable end || control circuit spring terminals 2 2.5-2.5 mm²flexible without cable end
  • Power Dissipation Per Pole : 1.56 W AC-1 || 0.2 W AC-3
  • Motor Power Kw : 2.2 kW 220...230 V AC 50/60 Hz AC-3) || 4 kW 380...400 V AC 50/60 Hz AC-3) || 4 kW 415...440 V AC 50/60 Hz AC-3) || 5.5 kW 500 V AC 50/60 Hz AC-3) || 5.5 kW 660...690 V AC 50/60 Hz AC-3) || 2.2 kW 400 V AC 50/60 Hz AC-4)
  • Product Or Component Type : contactor
  • Rated Breaking Capacity : 250 A 440 V power circuit IEC 60947
  • Product Name : TeSys D
  • [Ith] Conventional Free Air Thermal Current : 10 A 60 °C signalling circuit || 16 A 60 °C power circuit
  • Auxiliary Contact Composition : 1 NO + 1 NC
  • Utilisation Category : AC-1 || AC-3 || AC-4
  • Maximum Horse Power Rating : 1 hp 230/240 V at AC 50/60 Hz for 1 phase || 2 hp 200/208 V at AC 50/60 Hz for 3 phase || 2 hp 230/240 V at AC 50/60 Hz for 3 phase || 5 hp 460/480 V at AC 50/60 Hz for 3 phase || 7.5 hp 575/600 V at AC 50/60 Hz for 3 phase || 0.33 hp 115 V at AC 50/60 Hz for 1 phase
  • Mounting Support : rail || plate
  • [Ui] Rated Insulation Voltage : power circuit 690 V IEC 60947-4-1 || power circuit 600 V CSA || power circuit 600 V UL || signalling circuit 690 V IEC 60947-1 || signalling circuit 600 V CSA || signalling circuit 600 V UL
  • [Icw] Rated Short-Time Withstand Current : 105 A 40 °C - 10 s power circuit || 210 A 40 °C - 1 s power circuit || 30 A 40 °C - 10 min power circuit || 61 A 40 °C - 1 min power circuit || 100 A - 1 s signalling circuit || 120 A - 500 ms signalling circuit || 140 A - 100 ms signalling circuit
  • Maximum Operating Rate : 3600 cyc/h 60 °C
  • Operating Time : 65.45...88.55 ms closing || 20...30 ms opening
  • Mechanical Durability : 30 Mcycles
  • [Ue] Rated Operational Voltage : power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
  • [Uc] Control Circuit Voltage : 24 V DC
  • [Uimp] Rated Impulse Withstand Voltage : 6 kV IEC 60947
  • Electrical Durability : 0.6 Mcycles 25 A AC-1 <= 440 V || 2 Mcycles 9 A AC-3 <= 440 V
  • Safety Reliability Level : B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
  • Control Circuit Type : DC low consumption
  • Overvoltage Category : III
  • Associated Fuse Rating : 10 A gG signalling circuit IEC 60947-5-1 || 25 A gG <= 690 V type 1 power circuit || 20 A gG <= 690 V type 2 power circuit
  • Protective Cover : with
  • Irms Rated Making Capacity : 250 A 440 V power circuit IEC 60947 || 140 A AC signalling circuit IEC 60947-5-1 || 250 A DC signalling circuit IEC 60947-5-1
  • Poles Description : 3P
  • Device Short Name : LC1D
  • Average Impedance : 2.5 mOhm - Ith 16 A 50 Hz power circuit
  • Standards : CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508