IEC contactor, TeSys D, nonreversing, 80A, 60HP at 480VAC, up to 100kA SCCR, 3 phase, 3 NO, 48VDC coil, open style

IEC contactor, TeSys D, nonreversing, 80A, 60HP at 480VAC, up to 100kA SCCR, 3 phase, 3 NO, 48VDC coil, open style

SQDLC1D80ED LC1D80ED 338911044033
0.00 / EA
  • Certifications: BV, CCC, CSA, DNV, GL, GOST, LROS (Lloyds Register Of Shipping), RINA, UL
  • Contact Configuration: 3 NO
  • Contact Configuration: 1 NO + 1 NC
  • Depth: 186 mm
  • Height: 127 mm
  • Impedance: 0.8 MOhm - Ith 125 A 50 Hz Power Circuit
  • Net Weight: 2.59 kg
  • Standard: CSA C22.2 No 14, EN 60947-4-1, EN 60947-5-1, IEC 60947-4-1, IEC 60947-5-1, UL 508
  • Storage Temperature: -60-80 °C
  • Warranty Length: 18 mth
  • Width: 85 mm
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 80A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 25HP at 200 to 208VAC, 30HP at 240VAC, 60HP at 480VAC and 60HP at 600VAC three phase. Contactor is also rated for 7.5HP at 115VAC and 15HP at 240VAC single phase. When used with a 480VAC up to 150A circuit breaker, this contactor can have a SCCR up to 100kA. When used with up to a 600VAC 175A Class J or CC fuse, this contactor can have a SCCR up to 100kA. Contactor is supplied with a 48 VDC coil with transient suppressor module. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 5.00 inches tall, 3.35 inches wide and 7.32 inches deep. It weighs 5.71 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
  • Product Description
  • Specifications
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 80A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 25HP at 200 to 208VAC, 30HP at 240VAC, 60HP at 480VAC and 60HP at 600VAC three phase. Contactor is also rated for 7.5HP at 115VAC and 15HP at 240VAC single phase. When used with a 480VAC up to 150A circuit breaker, this contactor can have a SCCR up to 100kA. When used with up to a 600VAC 175A Class J or CC fuse, this contactor can have a SCCR up to 100kA. Contactor is supplied with a 48 VDC coil with transient suppressor module. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 5.00 inches tall, 3.35 inches wide and 7.32 inches deep. It weighs 5.71 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
  • Complementary
    • Non-Overlap Time : 1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
    • Minimum Switching Current : 5 mA signalling circuit
    • Minimum Switching Voltage : 17 V signalling circuit
    • Signalling Circuit Frequency : 25...400 Hz
    • Inrush Power In W : 22-22 W 20 °C)
    • Control Circuit Voltage Limits : 0.1...0.3 Uc -40-70 °C drop-out DC || 0.85...1.1 Uc -40-55 °C operational DC || 1...1.1 Uc 55-70 °C operational DC
    • Hold-In Power Consumption In W : 22-22 W 20 °C
    • Insulation Resistance : > 10 MOhm signalling circuit
    • Coil Technology : without built-in suppressor module
    • Time Constant : 75 ms
    • Auxiliary Contacts Type : mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
  • Pole Contact Composition : 3 NO
  • [Uimp] Rated Impulse Withstand Voltage : 8 kV IEC 60947
  • Product Name : TeSys D
  • Average Impedance : 0.8 mOhm - Ith 125 A 50 Hz power circuit
  • Protective Cover : with
  • Utilisation Category : AC-4 || AC-1 || AC-3
  • Mechanical Durability : 4 Mcycles
  • Product Or Component Type : contactor
  • [Ui] Rated Insulation Voltage : power circuit 600 V CSA || power circuit 600 V UL || power circuit 1000 V IEC 60947-4-1 || signalling circuit 690 V IEC 60947-1 || signalling circuit 600 V CSA || signalling circuit 600 V UL
  • Power Dissipation Per Pole : 5.1 W AC-3 || 12.5 W AC-1
  • Connections - Terminals : control circuit screw clamp terminals 2 1-2.5 mm²flexible with cable end || control circuit screw clamp terminals 1 1-2.5 mm²flexible with cable end || control circuit screw clamp terminals 1 1-4 mm²flexible without cable end || control circuit screw clamp terminals 2 1-4 mm²flexible without cable end || control circuit screw clamp terminals 1 1-4 mm²solid without cable end || control circuit screw clamp terminals 2 1-4 mm²solid without cable end || power circuit connector 1 4-50 mm²flexible without cable end || power circuit connector 2 4-25 mm²flexible without cable end || power circuit connector 1 4-50 mm²flexible with cable end || power circuit connector 2 4-16 mm²flexible with cable end || power circuit connector 1 4-50 mm²solid without cable end || power circuit connector 2 4-25 mm²solid without cable end
  • Poles Description : 3P
  • Motor Power Kw : 22 kW 220...230 V AC 50/60 Hz AC-3) || 37 kW 380...400 V AC 50/60 Hz AC-3) || 45 kW 415...440 V AC 50/60 Hz AC-3) || 55 kW 500 V AC 50/60 Hz AC-3) || 45 kW 660...690 V AC 50/60 Hz AC-3) || 45 kW 1000 V AC 50/60 Hz AC-3) || 15 kW 400 V AC 50/60 Hz AC-4)
  • Mounting Support : plate || rail
  • Maximum Operating Rate : 3600 cyc/h 60 °C
  • Standards : CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508
  • Control Circuit Type : DC standard
  • Operating Time : 95...130 ms closing || 20...35 ms opening
  • [Ith] Conventional Free Air Thermal Current : 10 A 60 °C signalling circuit || 125 A 60 °C power circuit
  • Rated Breaking Capacity : 1100 A 440 V power circuit IEC 60947
  • Associated Fuse Rating : 10 A gG signalling circuit IEC 60947-5-1 || 200 A gG <= 690 V type 1 power circuit || 160 A gG <= 690 V type 2 power circuit
  • Electrical Durability : 0.8 Mcycles 125 A AC-1 <= 440 V || 1.5 Mcycles 80 A AC-3 <= 440 V
  • Overvoltage Category : III
  • Tightening Torque : control circuit 1.2 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.2 N.m screw clamp terminals Philips No 2 || power circuit 12 N.m connector flat Ø 6 to Ø 8 mm || power circuit 12 N.m connector hexagonal 4 mm
  • Irms Rated Making Capacity : 140 A AC signalling circuit IEC 60947-5-1 || 250 A DC signalling circuit IEC 60947-5-1 || 1100 A 440 V power circuit IEC 60947
  • Safety Reliability Level : B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
  • [Ie] Rated Operational Current : 125 A 60 °C) <= 440 V AC AC-1 power circuit || 80 A 60 °C) <= 440 V AC AC-3 power circuit
  • [Icw] Rated Short-Time Withstand Current : 640 A 40 °C - 10 s power circuit || 990 A 40 °C - 1 s power circuit || 135 A 40 °C - 10 min power circuit || 320 A 40 °C - 1 min power circuit || 100 A - 1 s signalling circuit || 120 A - 500 ms signalling circuit || 140 A - 100 ms signalling circuit
  • Device Short Name : LC1D
  • [Ue] Rated Operational Voltage : power circuit <= 300 V DC 25...400 Hz || power circuit <= 690 V AC
  • Contactor Application : motor control || resistive load
  • Range : TeSys
  • Maximum Horse Power Rating : 20 hp 200/208 V at AC 50/60 Hz for 3 phase || 7.5 hp 115 V at AC 50/60 Hz for 1 phase || 15 hp 230/240 V at AC 50/60 Hz for 1 phase || 25 hp 230/240 V at AC 50/60 Hz for 3 phase || 60 hp 460/480 V at AC 50/60 Hz for 3 phase || 60 hp 575/600 V at AC 50/60 Hz for 3 phase
  • Auxiliary Contact Composition : 1 NO + 1 NC
  • [Uc] Control Circuit Voltage : 48 V DC
  • Product Certifications : UL || CSA || GOST || LROS (Lloyds register of shipping) || DNV || GL || BV || RINA || CCC
  • Environment
    • Ambient Air Temperature For Operation : -40-60 °C || 60-70 °C with derating
    • Pollution Degree : 3
    • Maximum Height : 127 mm
    • Maximum Width : 85 mm
    • Flame Retardance : V1 conforming to UL 94
    • Mechanical Robustness : vibrations contactor open2 Gn, 5...300 Hz || shocks contactor open8 Gn for 11 ms || vibrations contactor closed3 Gn, 5...300 Hz || shocks contactor closed10 Gn for 11 ms
    • Fire Resistance : 850 °C IEC 60695-2-1
    • Maximum Depth : 186 mm
    • Net Weight : 2.59 kg
    • Operating Altitude : 0...9842.52 ft (0...3000 m)
    • Ambient Air Temperature For Storage : -60-80 °C
    • Protective Treatment : TH IEC 60068-2-30
    • Ip Degree Of Protection : IP20 front face IEC 60529
  • Offer Sustainability
    • Eu Rohs Directive : Compliant
    • Sustainable Offer Status : Green Premium product
    • California Proposition 65 : WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
    • Environmental Disclosure : ENVPEP110205EN
    • Pvc Free : Yes
    • Weee : The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
    • Toxic Heavy Metal Free : Yes
    • Reach Regulation : Free of Substances of Very High Concern above the threshold
    • China Rohs Regulation : Pro-active China RoHS declaration (out of China RoHS legal scope)
    • Mercury Free : Yes
    • Rohs Exemption Information : Yes
    • Reach Free Of Svhc : Yes
  • Contractual warranty
    • Warranty : 18 months