IEC contactor, TeSys Deca, nonreversing, 80A, 60HP at 480VAC, up to 100kA SCCR, 3 phase, 3 NO, 380VAC 50/60Hz coil, open

IEC contactor, TeSys Deca, nonreversing, 80A, 60HP at 480VAC, up to 100kA SCCR, 3 phase, 3 NO, 380VAC 50/60Hz coil, open

SQDLC1D80Q7 LC1D80Q7 3389110442861
417.31 / EA
http://schema.org/OutOfStock
  • Warranty Length: 18 mth
TeSys Deca contactor, 3 poles (3NO), for motor control applications up to 80A/1000V AC-3/AC-3e (37kW@400V). They can be used to create motor starters for almost any type of application. It provides a 380V 50/60Hz AC coil, 1NO+1NC built-in auxiliary contacts (NC mirror certified), power connection by screw terminals, control connection by screw clamp terminals. For operating rates until 3600 cycles/hour and environments until 60°C, it procures high reliability and durability. Compact (85mm width), DIN-rail mounting or screw fixing. Contactor is rated for 25HP at 200 to 208VAC, 30HP at 240VAC, 60HP at 480VAC and 60HP at 600VAC three phase. Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine). When used with a 480VAC up to 150A circuit breaker, this contactor can have a SCCR up to 100kA. When used with up to a 600VAC 175A Class J or CC fuse, this contactor can have a SCCR up to 100kA. Contactor is supplied with a 380 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 5.00 inches tall, 3.35 inches wide and 5.12 inches deep. It weighs 3.51 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards.
QTY
  • Product Description
  • Features
  • Specifications
TeSys Deca contactor, 3 poles (3NO), for motor control applications up to 80A/1000V AC-3/AC-3e (37kW@400V). They can be used to create motor starters for almost any type of application. It provides a 380V 50/60Hz AC coil, 1NO+1NC built-in auxiliary contacts (NC mirror certified), power connection by screw terminals, control connection by screw clamp terminals. For operating rates until 3600 cycles/hour and environments until 60°C, it procures high reliability and durability. Compact (85mm width), DIN-rail mounting or screw fixing. Contactor is rated for 25HP at 200 to 208VAC, 30HP at 240VAC, 60HP at 480VAC and 60HP at 600VAC three phase. Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine). When used with a 480VAC up to 150A circuit breaker, this contactor can have a SCCR up to 100kA. When used with up to a 600VAC 175A Class J or CC fuse, this contactor can have a SCCR up to 100kA. Contactor is supplied with a 380 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 5.00 inches tall, 3.35 inches wide and 5.12 inches deep. It weighs 3.51 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards.
  • Prop 65
    • WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
  • Conformance Attributes
    • Standards : EN 60947-4-1, EN 60947-5-1, IEC 60947-4-1, IEC 60947-5-1, CSA C22.2 No 14, UL 60947-4-1, IEC 60335-2-40:Annex JJ, IEC 60335-2-40:Annex JJ, UL 60335-2-40:Annex JJ, UL 60335-2-40:Annex JJ, IEC 60335-1:Clause 30.2, IEC 60335-1:Clause 30.2
  • Complementary Attributes
    • Control Circuit Type : AC 50/60 Hz, AC 50/60 Hz
    • Control Circuit Voltage Limits : 0.85...1.1 Uc (-40-55 °C):operational AC 60 Hz, 0.85...1.1 Uc (-40-55 °C):operational AC 60 Hz, 0.85...1.1 Uc (-40-55 °C):operational AC 60 Hz, 0.85...1.1 Uc (-40-55 °C):operational AC 60 Hz, 0.85...1.1 Uc (-40-55 °C):operational AC 60 Hz, 0.3...0.6 Uc (-40-70 °C):drop-out AC 50/60 Hz, 0.3...0.6 Uc (-40-70 °C):drop-out AC 50/60 Hz, 0.3...0.6 Uc (-40-70 °C):drop-out AC 50/60 Hz, 0.3...0.6 Uc (-40-70 °C):drop-out AC 50/60 Hz, 0.3...0.6 Uc (-40-70 °C):drop-out AC 50/60 Hz, 0.8...1.1 Uc (-40-55 °C):operational AC 50 Hz, 0.8...1.1 Uc (-40-55 °C):operational AC 50 Hz, 0.8...1.1 Uc (-40-55 °C):operational AC 50 Hz, 0.8...1.1 Uc (-40-55 °C):operational AC 50 Hz, 0.8...1.1 Uc (-40-55 °C):operational AC 50 Hz, 1...1.1 Uc (55-70 °C):operational AC 50/60 Hz, 1...1.1 Uc (55-70 °C):operational AC 50/60 Hz, 1...1.1 Uc (55-70 °C):operational AC 50/60 Hz, 1...1.1 Uc (55-70 °C):operational AC 50/60 Hz, 1...1.1 Uc (55-70 °C):operational AC 50/60 Hz
    • IRMS Rated Making Capacity : 140 A AC for signalling circuit conforming to IEC 60947-5-1, 140 A AC for signalling circuit conforming to IEC 60947-5-1, 140 A AC for signalling circuit conforming to IEC 60947-5-1, 140 A AC for signalling circuit conforming to IEC 60947-5-1, 250 A DC for signalling circuit conforming to IEC 60947-5-1, 250 A DC for signalling circuit conforming to IEC 60947-5-1, 250 A DC for signalling circuit conforming to IEC 60947-5-1, 250 A DC for signalling circuit conforming to IEC 60947-5-1, 1100 A at 440 V for power circuit conforming to IEC 60947, 1100 A at 440 V for power circuit conforming to IEC 60947, 1100 A at 440 V for power circuit conforming to IEC 60947, 1100 A at 440 V for power circuit conforming to IEC 60947
    • Maximum Horse Power Rating : 7.5 hp at 120 V AC 50/60 Hz for 1 phase motors, 7.5 hp at 120 V AC 50/60 Hz for 1 phase motors, 7.5 hp at 120 V AC 50/60 Hz for 1 phase motors, 7.5 hp at 120 V AC 50/60 Hz for 1 phase motors, 7.5 hp at 120 V AC 50/60 Hz for 1 phase motors, 15 hp at 230/240 V AC 50/60 Hz for 1 phase motors, 15 hp at 230/240 V AC 50/60 Hz for 1 phase motors, 15 hp at 230/240 V AC 50/60 Hz for 1 phase motors, 15 hp at 230/240 V AC 50/60 Hz for 1 phase motors, 15 hp at 230/240 V AC 50/60 Hz for 1 phase motors, 30 hp at 200/208 V AC 50/60 Hz for 3 phase motors, 30 hp at 200/208 V AC 50/60 Hz for 3 phase motors, 30 hp at 200/208 V AC 50/60 Hz for 3 phase motors, 30 hp at 200/208 V AC 50/60 Hz for 3 phase motors, 30 hp at 200/208 V AC 50/60 Hz for 3 phase motors, 30 hp at 230/240 V AC 50/60 Hz for 3 phase motors, 30 hp at 230/240 V AC 50/60 Hz for 3 phase motors, 30 hp at 230/240 V AC 50/60 Hz for 3 phase motors, 30 hp at 230/240 V AC 50/60 Hz for 3 phase motors, 30 hp at 230/240 V AC 50/60 Hz for 3 phase motors, 60 hp at 460/480 V AC 50/60 Hz for 3 phase motors, 60 hp at 460/480 V AC 50/60 Hz for 3 phase motors, 60 hp at 460/480 V AC 50/60 Hz for 3 phase motors, 60 hp at 460/480 V AC 50/60 Hz for 3 phase motors, 60 hp at 460/480 V AC 50/60 Hz for 3 phase motors, 60 hp at 575/600 V AC 50/60 Hz for 3 phase motors, 60 hp at 575/600 V AC 50/60 Hz for 3 phase motors, 60 hp at 575/600 V AC 50/60 Hz for 3 phase motors, 60 hp at 575/600 V AC 50/60 Hz for 3 phase motors, 60 hp at 575/600 V AC 50/60 Hz for 3 phase motors
    • Maximum Operating Rate : 3600 cyc/h at 60 °C, 3600 cyc/h at 60 °C
    • Minimum Switching Current : 5 mA for signalling circuit, 5 mA for signalling circuit
    • Minimum Switching Voltage : 17 V for signalling circuit, 17 V for signalling circuit
    • Rated Breaking Capacity : 1100 A at 440 V for power circuit conforming to IEC 60947, 1100 A at 440 V for power circuit conforming to IEC 60947, 1100 A at 440 V for power circuit conforming to IEC 60947, 1100 A at 440 V for power circuit conforming to IEC 60947
    • ICW Rated Short Time Withstand Current : 640 A 40 °C - 10 s for power circuit, 640 A 40 °C - 10 s for power circuit, 640 A 40 °C - 10 s for power circuit, 640 A 40 °C - 10 s for power circuit, 990 A 40 °C - 1 s for power circuit, 990 A 40 °C - 1 s for power circuit, 990 A 40 °C - 1 s for power circuit, 990 A 40 °C - 1 s for power circuit, 135 A 40 °C - 10 min for power circuit, 135 A 40 °C - 10 min for power circuit, 135 A 40 °C - 10 min for power circuit, 135 A 40 °C - 10 min for power circuit, 320 A 40 °C - 1 min for power circuit, 320 A 40 °C - 1 min for power circuit, 320 A 40 °C - 1 min for power circuit, 320 A 40 °C - 1 min for power circuit, 100 A - 1 s for signalling circuit, 100 A - 1 s for signalling circuit, 100 A - 1 s for signalling circuit, 120 A - 500 ms for signalling circuit, 120 A - 500 ms for signalling circuit, 120 A - 500 ms for signalling circuit, 140 A - 100 ms for signalling circuit, 140 A - 100 ms for signalling circuit, 140 A - 100 ms for signalling circuit
    • IE Rated Operational Current : 125 A (at <60 °C) at <= 1000 V AC AC-1 for power circuit, 125 A (at <60 °C) at <= 1000 V AC AC-1 for power circuit, 125 A (at <60 °C) at <= 1000 V AC AC-1 for power circuit, 125 A (at <60 °C) at <= 1000 V AC AC-1 for power circuit, 125 A (at <60 °C) at <= 1000 V AC AC-1 for power circuit, 125 A (at <60 °C) at <= 1000 V AC AC-1 for power circuit, 80 A (at <60 °C) at <= 440 V AC AC-3 for power circuit, 80 A (at <60 °C) at <= 440 V AC AC-3 for power circuit, 80 A (at <60 °C) at <= 440 V AC AC-3 for power circuit, 80 A (at <60 °C) at <= 440 V AC AC-3 for power circuit, 80 A (at <60 °C) at <= 440 V AC AC-3 for power circuit, 80 A (at <60 °C) at <= 440 V AC AC-3 for power circuit, 80 A (at <60 °C) at <= 440 V AC AC-3e for power circuit, 80 A (at <60 °C) at <= 440 V AC AC-3e for power circuit, 80 A (at <60 °C) at <= 440 V AC AC-3e for power circuit, 80 A (at <60 °C) at <= 440 V AC AC-3e for power circuit, 80 A (at <60 °C) at <= 440 V AC AC-3e for power circuit, 80 A (at <60 °C) at <= 440 V AC AC-3e for power circuit
    • UC Control Circuit Voltage : 380 V AC 50/60 Hz, 380 V AC 50/60 Hz, 380 V AC 50/60 Hz
    • UE Rated Operational Voltage : power circuit <= 300 V DC 25...400 Hz, power circuit <= 300 V DC 25...400 Hz, power circuit <= 300 V DC 25...400 Hz, power circuit <= 300 V DC 25...400 Hz, power circuit <= 690 V AC, power circuit <= 690 V AC, power circuit <= 690 V AC
    • UI Rated Insulation Voltage : power circuit 600 V CSA, power circuit 600 V CSA, power circuit 600 V CSA, power circuit 600 V UL, power circuit 600 V UL, power circuit 600 V UL, power circuit 1000 V IEC 60947-4-1, power circuit 1000 V IEC 60947-4-1, power circuit 1000 V IEC 60947-4-1, signalling circuit 690 V IEC 60947-1, signalling circuit 690 V IEC 60947-1, signalling circuit 690 V IEC 60947-1, signalling circuit 600 V CSA, signalling circuit 600 V CSA, signalling circuit 600 V CSA, signalling circuit 600 V UL, signalling circuit 600 V UL, signalling circuit 600 V UL
    • UIMP Rated Impulse Withstand Voltage : 8 kV IEC 60947, 8 kV IEC 60947
    • Maximum Motor Phase Current : 80 A
  • Important Information Attributes
    • Persona Type Ids : EU, LC, OM, OM8, PB, SI
    • Persona Type Names : End User, Contractor, Original Equipment Manufacturer, OEM - Control Panelbuilder, Panel Builder, System Integrator
    • Market Segmentation Id : COMMERCIAL, INDUSTRIAL
    • Market Segmentation : Commercial, Industrial
    • Associated Fuse Rating : 10 A gG for signalling circuit conforming to IEC 60947-5-1, 10 A gG for signalling circuit conforming to IEC 60947-5-1, 10 A gG for signalling circuit conforming to IEC 60947-5-1, 10 A gG for signalling circuit conforming to IEC 60947-5-1, 200 A gG at <= 690 V coordination type 1 for power circuit, 200 A gG at <= 690 V coordination type 1 for power circuit, 200 A gG at <= 690 V coordination type 1 for power circuit, 200 A gG at <= 690 V coordination type 1 for power circuit, 200 A gG at <= 690 V coordination type 1 for power circuit, 160 A gG at <= 690 V coordination type 2 for power circuit, 160 A gG at <= 690 V coordination type 2 for power circuit, 160 A gG at <= 690 V coordination type 2 for power circuit, 160 A gG at <= 690 V coordination type 2 for power circuit, 160 A gG at <= 690 V coordination type 2 for power circuit
    • Average Impedance : 0.8 mOhm - Ith 125 A 50 Hz for power circuit, 0.8 mOhm - Ith 125 A 50 Hz for power circuit, 0.8 mOhm - Ith 125 A 50 Hz for power circuit, 0.8 mOhm - Ith 125 A 50 Hz for power circuit
    • Contactor Application : resistive load, motor control
    • Electrical Durability : 0.8 Mcycles 125 A AC-1 <= 440 V, 0.8 Mcycles 125 A AC-1 <= 440 V, 0.8 Mcycles 125 A AC-1 <= 440 V, 0.8 Mcycles 125 A AC-1 <= 440 V, 1.5 Mcycles 80 A AC-3 <= 440 V, 1.5 Mcycles 80 A AC-3 <= 440 V, 1.5 Mcycles 80 A AC-3 <= 440 V, 1.5 Mcycles 80 A AC-3 <= 440 V, 1.5 Mcycles 80 A AC-3e <= 440 V, 1.5 Mcycles 80 A AC-3e <= 440 V, 1.5 Mcycles 80 A AC-3e <= 440 V, 1.5 Mcycles 80 A AC-3e <= 440 V
    • Fire Resistance : 850 °C IEC 60695-2-1, 850 °C IEC 60695-2-1
    • Flame Retardance : V1 conforming to UL 94, V1 conforming to UL 94
    • Heat Dissipation : 6-10 W at 50/60 Hz, 6-10 W at 50/60 Hz
    • Hold In Power Consumption In VA : 26-26 VA 60 Hz cos phi 0.3 (at 20 °C), 26-26 VA 60 Hz cos phi 0.3 (at 20 °C), 26-26 VA 60 Hz cos phi 0.3 (at 20 °C), 26-26 VA 60 Hz cos phi 0.3 (at 20 °C), 26-26 VA 50 Hz cos phi 0.3 (at 20 °C), 26-26 VA 50 Hz cos phi 0.3 (at 20 °C), 26-26 VA 50 Hz cos phi 0.3 (at 20 °C), 26-26 VA 50 Hz cos phi 0.3 (at 20 °C)
    • Inrush Power In VA : 245-245 VA 60 Hz cos phi 0.75 (at 20 °C), 245-245 VA 60 Hz cos phi 0.75 (at 20 °C), 245-245 VA 60 Hz cos phi 0.75 (at 20 °C), 245-245 VA 60 Hz cos phi 0.75 (at 20 °C), 245-245 VA 50 Hz cos phi 0.75 (at 20 °C), 245-245 VA 50 Hz cos phi 0.75 (at 20 °C), 245-245 VA 50 Hz cos phi 0.75 (at 20 °C), 245-245 VA 50 Hz cos phi 0.75 (at 20 °C)
    • Insulation Resistance : > 10 MOhm for signalling circuit, > 10 MOhm for signalling circuit
    • Mechanical Robustness : vibrations contactor open 2 Gn, 5...300 Hz), vibrations contactor open 2 Gn, 5...300 Hz), vibrations contactor open 2 Gn, 5...300 Hz), shocks contactor open 8 Gn for 11 ms), shocks contactor open 8 Gn for 11 ms), shocks contactor open 8 Gn for 11 ms), vibrations contactor closed 3 Gn, 5...300 Hz), vibrations contactor closed 3 Gn, 5...300 Hz), vibrations contactor closed 3 Gn, 5...300 Hz), shocks contactor closed 10 Gn for 11 ms), shocks contactor closed 10 Gn for 11 ms), shocks contactor closed 10 Gn for 11 ms)
    • Motor Power KW : 22 kW at 220...230 V AC 50/60 Hz (AC-3), 22 kW at 220...230 V AC 50/60 Hz (AC-3), 22 kW at 220...230 V AC 50/60 Hz (AC-3), 22 kW at 220...230 V AC 50/60 Hz (AC-3), 22 kW at 220...230 V AC 50/60 Hz (AC-3), 37 kW at 380...400 V AC 50/60 Hz (AC-3), 37 kW at 380...400 V AC 50/60 Hz (AC-3), 37 kW at 380...400 V AC 50/60 Hz (AC-3), 37 kW at 380...400 V AC 50/60 Hz (AC-3), 37 kW at 380...400 V AC 50/60 Hz (AC-3), 45 kW at 415...440 V AC 50/60 Hz (AC-3), 45 kW at 415...440 V AC 50/60 Hz (AC-3), 45 kW at 415...440 V AC 50/60 Hz (AC-3), 45 kW at 415...440 V AC 50/60 Hz (AC-3), 45 kW at 415...440 V AC 50/60 Hz (AC-3), 55 kW at 500 V AC 50/60 Hz (AC-3), 55 kW at 500 V AC 50/60 Hz (AC-3), 55 kW at 500 V AC 50/60 Hz (AC-3), 55 kW at 500 V AC 50/60 Hz (AC-3), 55 kW at 500 V AC 50/60 Hz (AC-3), 45 kW at 660...690 V AC 50/60 Hz (AC-3), 45 kW at 660...690 V AC 50/60 Hz (AC-3), 45 kW at 660...690 V AC 50/60 Hz (AC-3), 45 kW at 660...690 V AC 50/60 Hz (AC-3), 45 kW at 660...690 V AC 50/60 Hz (AC-3), 15 kW at 400 V AC 50/60 Hz (AC-4), 15 kW at 400 V AC 50/60 Hz (AC-4), 15 kW at 400 V AC 50/60 Hz (AC-4), 15 kW at 400 V AC 50/60 Hz (AC-4), 15 kW at 400 V AC 50/60 Hz (AC-4), 22 kW at 220...230 V AC 50/60 Hz (AC-3e), 22 kW at 220...230 V AC 50/60 Hz (AC-3e), 22 kW at 220...230 V AC 50/60 Hz (AC-3e), 22 kW at 220...230 V AC 50/60 Hz (AC-3e), 22 kW at 220...230 V AC 50/60 Hz (AC-3e), 37 kW at 380...400 V AC 50/60 Hz (AC-3e), 37 kW at 380...400 V AC 50/60 Hz (AC-3e), 37 kW at 380...400 V AC 50/60 Hz (AC-3e), 37 kW at 380...400 V AC 50/60 Hz (AC-3e), 37 kW at 380...400 V AC 50/60 Hz (AC-3e), 45 kW at 415...440 V AC 50/60 Hz (AC-3e), 45 kW at 415...440 V AC 50/60 Hz (AC-3e), 45 kW at 415...440 V AC 50/60 Hz (AC-3e), 45 kW at 415...440 V AC 50/60 Hz (AC-3e), 45 kW at 415...440 V AC 50/60 Hz (AC-3e), 55 kW at 500 V AC 50/60 Hz (AC-3e), 55 kW at 500 V AC 50/60 Hz (AC-3e), 55 kW at 500 V AC 50/60 Hz (AC-3e), 55 kW at 500 V AC 50/60 Hz (AC-3e), 55 kW at 500 V AC 50/60 Hz (AC-3e), 45 kW at 660...690 V AC 50/60 Hz (AC-3e), 45 kW at 660...690 V AC 50/60 Hz (AC-3e), 45 kW at 660...690 V AC 50/60 Hz (AC-3e), 45 kW at 660...690 V AC 50/60 Hz (AC-3e), 45 kW at 660...690 V AC 50/60 Hz (AC-3e)
    • Non Overlap Time : 1.5 ms on de-energisation between NC and NO contact, 1.5 ms on de-energisation between NC and NO contact, 1.5 ms on de-energisation between NC and NO contact, 1.5 ms on energisation between NC and NO contact, 1.5 ms on energisation between NC and NO contact, 1.5 ms on energisation between NC and NO contact
    • Operating Time : 20...35 ms closing, 20...35 ms closing, 6...20 ms opening, 6...20 ms opening
    • Power Dissipation Per Pole : 5.1 W AC-3, 5.1 W AC-3, 12.5 W AC-1, 12.5 W AC-1, 5.1 W AC-3e, 5.1 W AC-3e
    • Protective Treatment : THIEC 60068-2-30, THIEC 60068-2-30
    • Safety Reliability Level : B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1, B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1, B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1, B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1, B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1, B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1, B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1, B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
    • Tightening Torque : control circuit 1.2 N.m screw clamp terminals flat Ø 6 mm, control circuit 1.2 N.m screw clamp terminals flat Ø 6 mm, control circuit 1.2 N.m screw clamp terminals flat Ø 6 mm, control circuit 1.2 N.m screw clamp terminals flat Ø 6 mm, control circuit 1.2 N.m screw clamp terminals Philips No 2, control circuit 1.2 N.m screw clamp terminals Philips No 2, control circuit 1.2 N.m screw clamp terminals Philips No 2, control circuit 1.2 N.m screw clamp terminals Philips No 2, power circuit 12 N.m connector flat Ø 6 to Ø 8 mm, power circuit 12 N.m connector flat Ø 6 to Ø 8 mm, power circuit 12 N.m connector flat Ø 6 to Ø 8 mm, power circuit 12 N.m connector flat Ø 6 to Ø 8 mm, power circuit 12 N.m connector hexagonal 4 mm, power circuit 12 N.m connector hexagonal 4 mm, power circuit 12 N.m connector hexagonal 4 mm, power circuit 12 N.m connector hexagonal 4 mm, power circuit 12 N.m connector hexagonal 4 mm, control circuit 1.2 N.m screw clamp terminals pozidriv No 2, control circuit 1.2 N.m screw clamp terminals pozidriv No 2, control circuit 1.2 N.m screw clamp terminals pozidriv No 2, control circuit 1.2 N.m screw clamp terminals pozidriv No 2
    • ICW Rated Short Time Withstand Current : 640 A 40 °C - 10 s for power circuit, 640 A 40 °C - 10 s for power circuit, 640 A 40 °C - 10 s for power circuit, 640 A 40 °C - 10 s for power circuit, 990 A 40 °C - 1 s for power circuit, 990 A 40 °C - 1 s for power circuit, 990 A 40 °C - 1 s for power circuit, 990 A 40 °C - 1 s for power circuit, 135 A 40 °C - 10 min for power circuit, 135 A 40 °C - 10 min for power circuit, 135 A 40 °C - 10 min for power circuit, 135 A 40 °C - 10 min for power circuit, 320 A 40 °C - 1 min for power circuit, 320 A 40 °C - 1 min for power circuit, 320 A 40 °C - 1 min for power circuit, 320 A 40 °C - 1 min for power circuit, 100 A - 1 s for signalling circuit, 100 A - 1 s for signalling circuit, 100 A - 1 s for signalling circuit, 120 A - 500 ms for signalling circuit, 120 A - 500 ms for signalling circuit, 120 A - 500 ms for signalling circuit, 140 A - 100 ms for signalling circuit, 140 A - 100 ms for signalling circuit, 140 A - 100 ms for signalling circuit
    • IE Rated Operational Current : 125 A (at <60 °C) at <= 1000 V AC AC-1 for power circuit, 125 A (at <60 °C) at <= 1000 V AC AC-1 for power circuit, 125 A (at <60 °C) at <= 1000 V AC AC-1 for power circuit, 125 A (at <60 °C) at <= 1000 V AC AC-1 for power circuit, 125 A (at <60 °C) at <= 1000 V AC AC-1 for power circuit, 125 A (at <60 °C) at <= 1000 V AC AC-1 for power circuit, 80 A (at <60 °C) at <= 440 V AC AC-3 for power circuit, 80 A (at <60 °C) at <= 440 V AC AC-3 for power circuit, 80 A (at <60 °C) at <= 440 V AC AC-3 for power circuit, 80 A (at <60 °C) at <= 440 V AC AC-3 for power circuit, 80 A (at <60 °C) at <= 440 V AC AC-3 for power circuit, 80 A (at <60 °C) at <= 440 V AC AC-3 for power circuit, 80 A (at <60 °C) at <= 440 V AC AC-3e for power circuit, 80 A (at <60 °C) at <= 440 V AC AC-3e for power circuit, 80 A (at <60 °C) at <= 440 V AC AC-3e for power circuit, 80 A (at <60 °C) at <= 440 V AC AC-3e for power circuit, 80 A (at <60 °C) at <= 440 V AC AC-3e for power circuit, 80 A (at <60 °C) at <= 440 V AC AC-3e for power circuit
    • ITH Conventional Free Air Thermal Current : 10 A (at 60 °C) for signalling circuit, 10 A (at 60 °C) for signalling circuit, 10 A (at 60 °C) for signalling circuit, 125 A (at 60 °C) for power circuit, 125 A (at 60 °C) for power circuit, 125 A (at 60 °C) for power circuit
    • Carbon Footprint Of The Distribution Phase A4 : 0.21622581342878092, 0.2 kg CO2 eq.
    • Carbon Footprint Of The End Of Life Phase C1 To C4 : 4.088997647987764, 4 kg CO2 eq.
    • Carbon Footprint Of The Installation Phase A5 : 0.3 kg CO2 eq., 0.31002666931072853
    • Carbon Footprint Of The Manufacturing Phase A1 To A3 : 11 kg CO2 eq., 10.960713361237987
    • Carbon Footprint Of The Use Phase B2 B3 B4 B6 : 81 kg CO2 eq., 81.20896739130431
    • Connections Terminals : control circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end, control circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end, control circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end, control circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end, control circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end, control circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end, control circuit: screw clamp terminals 1 1-2.5 mm² - cable stiffness: flexible with cable end, control circuit: screw clamp terminals 1 1-2.5 mm² - cable stiffness: flexible with cable end, control circuit: screw clamp terminals 1 1-2.5 mm² - cable stiffness: flexible with cable end, control circuit: screw clamp terminals 1 1-2.5 mm² - cable stiffness: flexible with cable end, control circuit: screw clamp terminals 1 1-2.5 mm² - cable stiffness: flexible with cable end, control circuit: screw clamp terminals 1 1-2.5 mm² - cable stiffness: flexible with cable end, control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end, control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end, control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end, control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end, control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end, control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end, control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: flexible without cable end, control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: flexible without cable end, control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: flexible without cable end, control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: flexible without cable end, control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: flexible without cable end, control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: flexible without cable end, control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: solid without cable end, control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: solid without cable end, control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: solid without cable end, control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: solid without cable end, control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: solid without cable end, control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: solid without cable end, control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: solid without cable end, control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: solid without cable end, control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: solid without cable end, control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: solid without cable end, control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: solid without cable end, control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: solid without cable end, power circuit: connector 1 4-50 mm² - cable stiffness: flexible without cable end, power circuit: connector 1 4-50 mm² - cable stiffness: flexible without cable end, power circuit: connector 1 4-50 mm² - cable stiffness: flexible without cable end, power circuit: connector 1 4-50 mm² - cable stiffness: flexible without cable end, power circuit: connector 1 4-50 mm² - cable stiffness: flexible without cable end, power circuit: connector 1 4-50 mm² - cable stiffness: flexible without cable end, power circuit: connector 2 4-25 mm² - cable stiffness: flexible without cable end, power circuit: connector 2 4-25 mm² - cable stiffness: flexible without cable end, power circuit: connector 2 4-25 mm² - cable stiffness: flexible without cable end, power circuit: connector 2 4-25 mm² - cable stiffness: flexible without cable end, power circuit: connector 2 4-25 mm² - cable stiffness: flexible without cable end, power circuit: connector 2 4-25 mm² - cable stiffness: flexible without cable end, power circuit: connector 1 4-50 mm² - cable stiffness: flexible with cable end, power circuit: connector 1 4-50 mm² - cable stiffness: flexible with cable end, power circuit: connector 1 4-50 mm² - cable stiffness: flexible with cable end, power circuit: connector 1 4-50 mm² - cable stiffness: flexible with cable end, power circuit: connector 1 4-50 mm² - cable stiffness: flexible with cable end, power circuit: connector 1 4-50 mm² - cable stiffness: flexible with cable end, power circuit: connector 2 4-16 mm² - cable stiffness: flexible with cable end, power circuit: connector 2 4-16 mm² - cable stiffness: flexible with cable end, power circuit: connector 2 4-16 mm² - cable stiffness: flexible with cable end, power circuit: connector 2 4-16 mm² - cable stiffness: flexible with cable end, power circuit: connector 2 4-16 mm² - cable stiffness: flexible with cable end, power circuit: connector 2 4-16 mm² - cable stiffness: flexible with cable end, power circuit: connector 1 4-50 mm² - cable stiffness: solid without cable end, power circuit: connector 1 4-50 mm² - cable stiffness: solid without cable end, power circuit: connector 1 4-50 mm² - cable stiffness: solid without cable end, power circuit: connector 1 4-50 mm² - cable stiffness: solid without cable end, power circuit: connector 1 4-50 mm² - cable stiffness: solid without cable end, power circuit: connector 1 4-50 mm² - cable stiffness: solid without cable end, power circuit: connector 2 4-25 mm² - cable stiffness: solid without cable end, power circuit: connector 2 4-25 mm² - cable stiffness: solid without cable end, power circuit: connector 2 4-25 mm² - cable stiffness: solid without cable end, power circuit: connector 2 4-25 mm² - cable stiffness: solid without cable end, power circuit: connector 2 4-25 mm² - cable stiffness: solid without cable end, power circuit: connector 2 4-25 mm² - cable stiffness: solid without cable end
    • Auxiliaries : LADN22, LADN11, LADN20, LAD8N11, LADT2, LADN40, LADN31, LADN02, LADT0, LAD8N20
    • Local Data Status : Publishable
    • Local Publishable Date : 2025-02-26
    • Device Type : LV equipment - LV contactor
    • Serviceability : No
    • Traceability : No
    • Field Service Division : PPIBS
    • Average Life Duration : 20 year(s)
    • Legacy WEEE Scope : In
    • Scope Perimeter : At least in Europe
    • EOLI Availability Display : No need of specific recycling operations
    • Reach Full Compliance Status : Free of Substances of Very High Concern above the threshold
    • Reach Full Compliance Status Id : NOT_CONTAINING_SVHC
    • Reach Compliance Directive : Free of Substances of Very High Concern above the threshold
    • ROHS EUR In Scope : Yes
    • ROHS EUR Status : Compliant
    • ROHS EUR Full Compliance Status : Compliant
    • ROHS EUR Full Compliance Status Id : COMPLIANT
    • China ROHS In Scope : No
    • Green Premium Status For Reporting : Green Premium product
    • With Recycled Cardboard : Yes
    • Without Single Use Plastic : Yes
    • Product Contributes To Saved And Avoided Emissions : No
    • Return Indicator : N
    • WD Status : 1 - GSC certified
    • Function Option Id : STANDARD
    • Function Option : Standard
    • Coil Technology : without built-in suppressor module
    • Compatibility Code : LC1D
    • Contact Compatibility : M11
    • Device Short Name : LC1D
    • Package Weight Lbs : 1.544 kg
    • Product Availability : Stock - Normally stocked in distribution facility
    • Product Or Component Type : contactor
    • Range : TeSys
    • Range Of Product : TeSys Deca
    • Returnability : No
    • Signalling Circuit Frequency : 25...400 Hz
    • Sustainable Packaging : Yes
    • Total Lifecycle Carbon Footprint : 97 kg CO2 eq.
    • Weee Label : The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
    • Relationship Type : Compatible relationship
    • Pep Code : ENVPEP1102005EN
    • Pep Verification Date : 2025-08-05
    • PCR Version : PEP-PCR-ed4-2021 09 06
    • PSR Version : PSR-0005-ed2-2016 03 29
    • Type Of Verification For The Pep : Independent internal review
    • Functional Unit Description : Switch on and off during 20 years electrical power supply of a downstream installation with an electrical and/or mechanical control. The functional unit is characterized by a type 3P(3NO), a control circuit voltage 230V AC, a power circuit voltage 690V and a rated operational current 80A
    • Functional Unit Unit : unit
    • Product Kit Identifier : N
  • Environment Attributes Main
    • Climatic Withstand : IACS E10 exposure to damp heat, IACS E10 exposure to damp heat
    • EU ROHS Directive : Compliant​, Compliant
    • IP Degree Of Protection : IP20 front face IEC 60529, IP20 front face IEC 60529, IP20 front face IEC 60529
    • Permissible Ambient Air Temperature Around The Device : -40-60 °C, 60-70 °C with derating, 60-70 °C with derating
    • Reach Regulation : Free of Substances of Very High Concern above the threshold, Free of Substances of Very High Concern above the threshold
    • ROHS Exemption Information : Yes
    • Take Back : No
    • Reach Free SHVC : Yes
    • Recycled Metal Content At Cr Level : 0 %
    • China ROHS Regulation : Pro-active China RoHS declaration (out of China RoHS legal scope)
    • Toxic Heavy Metal Free : Yes
    • Mercury Free : Yes
    • Carbon Footprint : 96.78493088326958
    • Environmental Disclosure : ENVPEP1102005EN
    • Operating Altitude : 0...9842.52 ft (0...3000 m)
    • Packaging Made With Recycled Cardboard : Yes
    • Packaging Without Single Use Plastic : Yes
    • Reach Free Of SVHC : Yes
    • Pep Code : ENVPEP1102005EN
    • Pep Verification Date : 2025-08-05
    • PCR Version : PEP-PCR-ed4-2021 09 06
    • PSR Version : PSR-0005-ed2-2016 03 29
    • Type Of Verification For The Pep : Independent internal review
  • General Attributes
    • Product Or Component Type : contactor
    • Range Of Product : TeSys Deca
  • Contractual Warranty Attributes
    • Warranty Period : 18 months
    • Warranty : 18 months