IEC contactor, TeSys D, nonreversing, 80A, 60HP at 480VAC, 3 phase, 3 pole, 3 NO, 24VDC coil, open style

IEC contactor, TeSys D, nonreversing, 80A, 60HP at 480VAC, 3 phase, 3 pole, 3 NO, 24VDC coil, open style

SQDLC1D806BD LC1D806BD 785901459880
488.95 / EACH
  • Certifications: BV, CCC, CSA, DNV, GL, GOST, LROS (Lloyds Register Of Shipping), RINA, UL
  • Contact Configuration: 1 NO + 1 NC
  • Contact Configuration: 3 NO
  • Depth: 186 mm
  • Height: 127 mm
  • Impedance: 0.8 MOhm - Ith 125 A 50 Hz Power Circuit
  • Net Weight: 2.59 kg
  • Standard: CSA C22.2 No 14, EN 60947-4-1, EN 60947-5-1, IEC 60947-4-1, IEC 60947-5-1, UL 508
  • Storage Temperature: -60-80 °C
  • Warranty Length: 18 mth
  • Width: 85 mm
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 80A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 25HP at 200 to 208VAC, 30HP at 240VAC, 60HP at 480VAC and 60HP at 600VAC three phase. Contactor is also rated for 7.5HP at 115VAC and 15HP at 240VAC single phase. Contactor is supplied with a 24 VDC coil with transient suppressor module. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Ring-lug screw terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 5.00 inches tall, 3.35 inches wide and 7.32 inches deep. It weighs 5.71 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
  • Product Description
  • Specifications
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 80A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 25HP at 200 to 208VAC, 30HP at 240VAC, 60HP at 480VAC and 60HP at 600VAC three phase. Contactor is also rated for 7.5HP at 115VAC and 15HP at 240VAC single phase. Contactor is supplied with a 24 VDC coil with transient suppressor module. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Ring-lug screw terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 5.00 inches tall, 3.35 inches wide and 7.32 inches deep. It weighs 5.71 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
  • Contractual warranty
    • Warranty : 18 months
  • Offer Sustainability
    • Eu Rohs Directive : Compliant
    • Reach Free Of Svhc : Yes
    • Rohs Exemption Information : Yes
    • Weee : The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
    • Reach Regulation : Free of Substances of Very High Concern above the threshold
    • Sustainable Offer Status : Green Premium product
    • Pvc Free : Yes
    • Toxic Heavy Metal Free : Yes
    • California Proposition 65 : WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
    • Mercury Free : Yes
    • China Rohs Regulation : Pro-active China RoHS declaration (out of China RoHS legal scope)
    • Environmental Disclosure : ENVPEP110205EN
  • Control Circuit Type : DC standard
  • [Uimp] Rated Impulse Withstand Voltage : 8 kV IEC 60947
  • Mechanical Durability : 75 Mcycles
  • [Ie] Rated Operational Current : 125 A 60 °C) <= 440 V AC AC-1 power circuit || 80 A 60 °C) <= 440 V AC AC-3 power circuit
  • Irms Rated Making Capacity : 140 A AC signalling circuit IEC 60947-5-1 || 250 A DC signalling circuit IEC 60947-5-1 || 1100 A 440 V power circuit IEC 60947
  • Contactor Application : resistive load || motor control
  • Tightening Torque : control circuit 1.2 N.m lugs-ring terminals flat Ø 6 mm M3.5 || control circuit 1.2 N.m lugs-ring terminals Philips No 2 M3.5 || power circuit 12 N.m lugs-ring terminals flat Ø 8 mm M6 || power circuit 12 N.m lugs-ring terminals hexagonal 10 mm M6 || power circuit 12 N.m bars flat Ø 8 mm M6 || power circuit 12 N.m bars hexagonal 10 mm M6
  • [Uc] Control Circuit Voltage : 24 V DC
  • Electrical Durability : 0.8 Mcycles 125 A AC-1 <= 440 V || 1.5 Mcycles 80 A AC-3 <= 440 V
  • Power Dissipation Per Pole : 5.1 W AC-3 || 12.5 W AC-1
  • Utilisation Category : AC-3 || AC-4 || AC-1
  • Product Or Component Type : contactor
  • Product Name : TeSys D
  • Average Impedance : 0.8 mOhm - Ith 125 A 50 Hz power circuit
  • Safety Reliability Level : B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
  • Device Short Name : LC1D
  • Maximum Operating Rate : 3600 cyc/h 60 °C
  • Product Certifications : LROS (Lloyds register of shipping) || CCC || DNV || GL || GOST || RINA || BV || UL || CSA
  • Operating Time : 95...130 ms closing || 20...35 ms opening
  • Range : TeSys
  • Rated Breaking Capacity : 1100 A 440 V power circuit IEC 60947
  • Associated Fuse Rating : 10 A gG signalling circuit IEC 60947-5-1 || 200 A gG <= 690 V type 1 power circuit || 160 A gG <= 690 V type 2 power circuit
  • [Ui] Rated Insulation Voltage : power circuit 600 V CSA || power circuit 600 V UL || power circuit 1000 V IEC 60947-4-1 || signalling circuit 690 V IEC 60947-1 || signalling circuit 600 V CSA || signalling circuit 600 V UL
  • Maximum Horse Power Rating : 20 hp 200/208 V at AC 50/60 Hz for 3 phase || 7.5 hp 115 V at AC 50/60 Hz for 1 phase || 15 hp 230/240 V at AC 50/60 Hz for 1 phase || 25 hp 230/240 V at AC 50/60 Hz for 3 phase || 60 hp 460/480 V at AC 50/60 Hz for 3 phase || 60 hp 575/600 V at AC 50/60 Hz for 3 phase
  • [Ue] Rated Operational Voltage : power circuit <= 300 V DC 25...400 Hz || power circuit <= 690 V AC
  • Poles Description : 3P
  • Standards : CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508
  • [Ith] Conventional Free Air Thermal Current : 10 A 60 °C signalling circuit || 125 A 60 °C power circuit
  • Motor Power Kw : 22 kW 220...230 V AC 50/60 Hz AC-3) || 37 kW 380...400 V AC 50/60 Hz AC-3) || 45 kW 415...440 V AC 50/60 Hz AC-3) || 55 kW 500 V AC 50/60 Hz AC-3) || 45 kW 660...690 V AC 50/60 Hz AC-3) || 45 kW 1000 V AC 50/60 Hz AC-3) || 15 kW 400 V AC 50/60 Hz AC-4)
  • Pole Contact Composition : 3 NO
  • Connections - Terminals : control circuit lugs-ring terminals 8 mm) || power circuit bars 1 3 x 16 mm || power circuit lugs-ring terminals 17 mm)
  • [Icw] Rated Short-Time Withstand Current : 640 A 40 °C - 10 s power circuit || 990 A 40 °C - 1 s power circuit || 135 A 40 °C - 10 min power circuit || 320 A 40 °C - 1 min power circuit || 100 A - 1 s signalling circuit || 120 A - 500 ms signalling circuit || 140 A - 100 ms signalling circuit
  • Protective Cover : with
  • Overvoltage Category : III
  • Auxiliary Contact Composition : 1 NO + 1 NC
  • Mounting Support : rail || plate
  • Environment
    • Ip Degree Of Protection : IP20 front face IEC 60529
    • Maximum Height : 127 mm
    • Protective Treatment : TH IEC 60068-2-30
    • Mechanical Robustness : vibrations contactor open2 Gn, 5...300 Hz || shocks contactor open8 Gn for 11 ms || vibrations contactor closed3 Gn, 5...300 Hz || shocks contactor closed10 Gn for 11 ms
    • Fire Resistance : 850 °C IEC 60695-2-1
    • Flame Retardance : V1 conforming to UL 94
    • Ambient Air Temperature For Storage : -60-80 °C
    • Pollution Degree : 3
    • Maximum Width : 85 mm
    • Maximum Depth : 186 mm
    • Ambient Air Temperature For Operation : -40-60 °C || 60-70 °C with derating
    • Operating Altitude : 0...9842.52 ft (0...3000 m)
    • Net Weight : 2.59 kg
  • Complementary
    • Control Circuit Voltage Limits : 0.1...0.3 Uc -40-70 °C drop-out DC || 0.85...1.1 Uc -40-55 °C operational DC || 1...1.1 Uc 55-70 °C operational DC
    • Coil Technology : without built-in suppressor module
    • Inrush Power In W : 22-22 W 20 °C)
    • Non-Overlap Time : 1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
    • Auxiliary Contacts Type : mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
    • Minimum Switching Voltage : 17 V signalling circuit
    • Time Constant : 75 ms
    • Insulation Resistance : > 10 MOhm signalling circuit
    • Minimum Switching Current : 5 mA signalling circuit
    • Hold-In Power Consumption In W : 22-22 W 20 °C
    • Signalling Circuit Frequency : 25...400 Hz