IEC contactor, TeSys D, nonreversing, 80A, 60HP at 480VAC, up to 100kA SCCR, 3 phase, 3 NO, 220VDC coil, open style

IEC contactor, TeSys D, nonreversing, 80A, 60HP at 480VAC, up to 100kA SCCR, 3 phase, 3 NO, 220VDC coil, open style

SQDLC1D80MD LC1D80MD 785901695721
488.95 / EACH
  • Certifications: BV, CCC, CSA, DNV, GL, GOST, LROS (Lloyds Register Of Shipping), RINA, UL
  • Contact Configuration: 3 NO
  • Contact Configuration: 1 NO + 1 NC
  • Depth: 186 mm
  • Height: 127 mm
  • Impedance: 0.8 MOhm - Ith 125 A 50 Hz Power Circuit
  • Net Weight: 2.59 kg
  • Standard: CSA C22.2 No 14, EN 60947-4-1, EN 60947-5-1, IEC 60947-4-1, IEC 60947-5-1, UL 508
  • Storage Temperature: -60-80 °C
  • Warranty Length: 18 mth
  • Width: 85 mm
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 80A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 25HP at 200 to 208VAC, 30HP at 240VAC, 60HP at 480VAC and 60HP at 600VAC three phase. Contactor is also rated for 7.5HP at 115VAC and 15HP at 240VAC single phase. When used with a 480VAC up to 150A circuit breaker, this contactor can have a SCCR up to 100kA. When used with up to a 600VAC 175A Class J or CC fuse, this contactor can have a SCCR up to 100kA. Contactor is supplied with a 220 VDC coil with transient suppressor module. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 5.00 inches tall, 3.35 inches wide and 7.32 inches deep. It weighs 5.71 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
  • Product Description
  • Specifications
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 80A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 25HP at 200 to 208VAC, 30HP at 240VAC, 60HP at 480VAC and 60HP at 600VAC three phase. Contactor is also rated for 7.5HP at 115VAC and 15HP at 240VAC single phase. When used with a 480VAC up to 150A circuit breaker, this contactor can have a SCCR up to 100kA. When used with up to a 600VAC 175A Class J or CC fuse, this contactor can have a SCCR up to 100kA. Contactor is supplied with a 220 VDC coil with transient suppressor module. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 5.00 inches tall, 3.35 inches wide and 7.32 inches deep. It weighs 5.71 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
  • Product Or Component Type : contactor
  • Maximum Horse Power Rating : 20 hp 200/208 V at AC 50/60 Hz for 3 phase || 7.5 hp 115 V at AC 50/60 Hz for 1 phase || 15 hp 230/240 V at AC 50/60 Hz for 1 phase || 25 hp 230/240 V at AC 50/60 Hz for 3 phase || 60 hp 460/480 V at AC 50/60 Hz for 3 phase || 60 hp 575/600 V at AC 50/60 Hz for 3 phase
  • Motor Power Kw : 22 kW 220...230 V AC 50/60 Hz AC-3) || 37 kW 380...400 V AC 50/60 Hz AC-3) || 45 kW 415...440 V AC 50/60 Hz AC-3) || 55 kW 500 V AC 50/60 Hz AC-3) || 45 kW 660...690 V AC 50/60 Hz AC-3) || 45 kW 1000 V AC 50/60 Hz AC-3) || 15 kW 400 V AC 50/60 Hz AC-4)
  • Safety Reliability Level : B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
  • Associated Fuse Rating : 10 A gG signalling circuit IEC 60947-5-1 || 200 A gG <= 690 V type 1 power circuit || 160 A gG <= 690 V type 2 power circuit
  • Overvoltage Category : III
  • [Ie] Rated Operational Current : 125 A 60 °C) <= 440 V AC AC-1 power circuit || 80 A 60 °C) <= 440 V AC AC-3 power circuit
  • Operating Time : 95...130 ms closing || 20...35 ms opening
  • Auxiliary Contact Composition : 1 NO + 1 NC
  • [Uc] Control Circuit Voltage : 220 V DC
  • Standards : CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508
  • [Ith] Conventional Free Air Thermal Current : 10 A 60 °C signalling circuit || 125 A 60 °C power circuit
  • Range : TeSys
  • Device Short Name : LC1D
  • [Uimp] Rated Impulse Withstand Voltage : 8 kV IEC 60947
  • Poles Description : 3P
  • Mechanical Durability : 4 Mcycles
  • Connections - Terminals : control circuit screw clamp terminals 2 1-2.5 mm²flexible with cable end || control circuit screw clamp terminals 1 1-2.5 mm²flexible with cable end || control circuit screw clamp terminals 1 1-4 mm²flexible without cable end || control circuit screw clamp terminals 2 1-4 mm²flexible without cable end || control circuit screw clamp terminals 1 1-4 mm²solid without cable end || control circuit screw clamp terminals 2 1-4 mm²solid without cable end || power circuit connector 1 4-50 mm²flexible without cable end || power circuit connector 2 4-25 mm²flexible without cable end || power circuit connector 1 4-50 mm²flexible with cable end || power circuit connector 2 4-16 mm²flexible with cable end || power circuit connector 1 4-50 mm²solid without cable end || power circuit connector 2 4-25 mm²solid without cable end
  • [Icw] Rated Short-Time Withstand Current : 640 A 40 °C - 10 s power circuit || 990 A 40 °C - 1 s power circuit || 135 A 40 °C - 10 min power circuit || 320 A 40 °C - 1 min power circuit || 100 A - 1 s signalling circuit || 120 A - 500 ms signalling circuit || 140 A - 100 ms signalling circuit
  • Electrical Durability : 0.8 Mcycles 125 A AC-1 <= 440 V || 1.5 Mcycles 80 A AC-3 <= 440 V
  • Irms Rated Making Capacity : 140 A AC signalling circuit IEC 60947-5-1 || 250 A DC signalling circuit IEC 60947-5-1 || 1100 A 440 V power circuit IEC 60947
  • Average Impedance : 0.8 mOhm - Ith 125 A 50 Hz power circuit
  • Power Dissipation Per Pole : 5.1 W AC-3 || 12.5 W AC-1
  • Pole Contact Composition : 3 NO
  • [Ui] Rated Insulation Voltage : power circuit 600 V CSA || power circuit 600 V UL || power circuit 1000 V IEC 60947-4-1 || signalling circuit 690 V IEC 60947-1 || signalling circuit 600 V CSA || signalling circuit 600 V UL
  • Utilisation Category : AC-1 || AC-3 || AC-4
  • Rated Breaking Capacity : 1100 A 440 V power circuit IEC 60947
  • Product Name : TeSys D
  • Tightening Torque : control circuit 1.2 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.2 N.m screw clamp terminals Philips No 2 || power circuit 12 N.m connector flat Ø 6 to Ø 8 mm || power circuit 12 N.m connector hexagonal 4 mm
  • Maximum Operating Rate : 3600 cyc/h 60 °C
  • Protective Cover : with
  • Mounting Support : plate || rail
  • [Ue] Rated Operational Voltage : power circuit <= 300 V DC 25...400 Hz || power circuit <= 690 V AC
  • Control Circuit Type : DC standard
  • Product Certifications : BV || LROS (Lloyds register of shipping) || DNV || GL || UL || CSA || CCC || RINA || GOST
  • Contactor Application : motor control || resistive load
  • Complementary
    • Time Constant : 75 ms
    • Auxiliary Contacts Type : mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
    • Minimum Switching Voltage : 17 V signalling circuit
    • Signalling Circuit Frequency : 25...400 Hz
    • Coil Technology : without built-in suppressor module
    • Inrush Power In W : 22-22 W 20 °C)
    • Non-Overlap Time : 1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
    • Control Circuit Voltage Limits : 0.1...0.3 Uc -40-70 °C drop-out DC || 0.85...1.1 Uc -40-55 °C operational DC || 1...1.1 Uc 55-70 °C operational DC
    • Hold-In Power Consumption In W : 22-22 W 20 °C
    • Insulation Resistance : > 10 MOhm signalling circuit
    • Minimum Switching Current : 5 mA signalling circuit
  • Environment
    • Pollution Degree : 3
    • Maximum Height : 127 mm
    • Ip Degree Of Protection : IP20 front face IEC 60529
    • Maximum Depth : 186 mm
    • Maximum Width : 85 mm
    • Protective Treatment : TH IEC 60068-2-30
    • Mechanical Robustness : vibrations contactor open2 Gn, 5...300 Hz || shocks contactor open8 Gn for 11 ms || vibrations contactor closed3 Gn, 5...300 Hz || shocks contactor closed10 Gn for 11 ms
    • Ambient Air Temperature For Operation : -40-60 °C || 60-70 °C with derating
    • Operating Altitude : 0...9842.52 ft (0...3000 m)
    • Ambient Air Temperature For Storage : -60-80 °C
    • Net Weight : 2.59 kg
    • Fire Resistance : 850 °C IEC 60695-2-1
    • Flame Retardance : V1 conforming to UL 94
  • Offer Sustainability
    • Mercury Free : Yes
    • Reach Regulation : Free of Substances of Very High Concern above the threshold
    • Sustainable Offer Status : Green Premium product
    • China Rohs Regulation : Pro-active China RoHS declaration (out of China RoHS legal scope)
    • Eu Rohs Directive : Compliant
    • Environmental Disclosure : ENVPEP110205EN
    • Pvc Free : Yes
    • Reach Free Of Svhc : Yes
    • Weee : The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
    • Rohs Exemption Information : Yes
    • California Proposition 65 : WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
    • Toxic Heavy Metal Free : Yes
  • Contractual warranty
    • Warranty : 18 months