Schneider Electric at Mayer

IEC contactor, TeSys D, nonreversing, 80A, 60HP at 480VAC, 3 phase, 3 pole, 3 NO, 220VAC 50/60Hz coil, open style

CONTACTOR 600VAC 80AMP IEC + O

SQDLC1D806M7 LC1D806M7 338911051710
0.00 / EA
  • Certifications: BV, CCC, CSA, DNV, GL, GOST, LROS (Lloyds Register Of Shipping), RINA, UKCA, UL
  • Contact Configuration: 1 NO + 1 NC
  • Contact Configuration: 3 NO
  • Depth: 130 mm
  • Height: 127 mm
  • Impedance: 0.8 MOhm - Ith 125 A 50 Hz Power Circuit
  • Net Weight: 1.59 kg
  • Standard: CSA C22.2 No 14, EN 60947-4-1, EN 60947-5-1, IEC 60947-4-1, IEC 60947-5-1, UL 508
  • Storage Temperature: -60-80 °C
  • Warranty Length: 18 mth
  • Width: 85 mm
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 80A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 25HP at 200 to 208VAC, 30HP at 240VAC, 60HP at 480VAC and 60HP at 600VAC three phase. Contactor is also rated for 7.5HP at 115VAC and 15HP at 240VAC single phase. Contactor is supplied with a 220 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Ring-lug screw terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 5.00 inches tall, 3.35 inches wide and 5.12 inches deep. It weighs 3.51 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
  • Product Description
  • Specifications
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 80A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 25HP at 200 to 208VAC, 30HP at 240VAC, 60HP at 480VAC and 60HP at 600VAC three phase. Contactor is also rated for 7.5HP at 115VAC and 15HP at 240VAC single phase. Contactor is supplied with a 220 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Ring-lug screw terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 5.00 inches tall, 3.35 inches wide and 5.12 inches deep. It weighs 3.51 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
  • Contractual warranty
    • Warranty : 18 months
  • Complementary
    • Heat Dissipation : 6-10 W 50/60 Hz
    • Non-Overlap Time : 1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
    • Inrush Power In Va : 245-245 VA 60 Hz 0.75 20 °C) || 245-245 VA 50 Hz 0.75 20 °C)
    • Minimum Switching Voltage : 17 V signalling circuit
    • Control Circuit Voltage Limits : 0.85...1.1 Uc -40-55 °C operational AC 60 Hz || 0.3...0.6 Uc -40-70 °C drop-out AC 50/60 Hz || 0.8...1.1 Uc -40-55 °C operational AC 50 Hz || 1...1.1 Uc 55-70 °C operational AC 50/60 Hz
    • Insulation Resistance : > 10 MOhm signalling circuit
    • Minimum Switching Current : 5 mA signalling circuit
    • Hold-In Power Consumption In Va : 26-26 VA 60 Hz 0.3 20 °C) || 26-26 VA 50 Hz 0.3 20 °C)
    • Auxiliary Contacts Type : mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
    • Coil Technology : without built-in suppressor module
    • Signalling Circuit Frequency : 25...400 Hz
  • Offer Sustainability
    • Weee : The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
    • Environmental Disclosure : ENVPEP110205EN
    • Sustainable Offer Status : Green Premium product
    • Rohs Exemption Information : Yes
    • Toxic Heavy Metal Free : Yes
    • Mercury Free : Yes
    • China Rohs Regulation : Pro-active China RoHS declaration (out of China RoHS legal scope)
    • Eu Rohs Directive : Compliant
    • California Proposition 65 : WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
    • Reach Free Of Svhc : Yes
    • Reach Regulation : Free of Substances of Very High Concern above the threshold
    • Pvc Free : Yes
  • Environment
    • Ip Degree Of Protection : IP20 front face IEC 60529
    • Ambient Air Temperature For Operation : -40-60 °C || 60-70 °C with derating
    • Width : 85 mm
    • Height : 127 mm
    • Ambient Air Temperature For Storage : -60-80 °C
    • Depth : 130 mm
    • Pollution Degree : 3
    • Flame Retardance : V1 conforming to UL 94
    • Protective Treatment : TH IEC 60068-2-30
    • Fire Resistance : 850 °C IEC 60695-2-1
    • Net Weight : 1.59 kg
    • Mechanical Robustness : vibrations contactor open2 Gn, 5...300 Hz || shocks contactor open8 Gn for 11 ms || vibrations contactor closed3 Gn, 5...300 Hz || shocks contactor closed10 Gn for 11 ms
    • Operating Altitude : 0...9842.52 ft (0...3000 m)
  • Connections - Terminals : control circuit lugs-ring terminals 8 mm) || power circuit bars 1 3 x 16 mm || power circuit lugs-ring terminals 17 mm)
  • Contactor Application : motor control || resistive load
  • Poles Description : 3P
  • Maximum Horse Power Rating : 20 hp 200/208 V at AC 50/60 Hz for 3 phase || 7.5 hp 115 V at AC 50/60 Hz for 1 phase || 15 hp 230/240 V at AC 50/60 Hz for 1 phase || 25 hp 230/240 V at AC 50/60 Hz for 3 phase || 60 hp 460/480 V at AC 50/60 Hz for 3 phase || 60 hp 575/600 V at AC 50/60 Hz for 3 phase
  • Device Short Name : LC1D
  • [Uc] Control Circuit Voltage : 220 V AC 50/60 Hz
  • Control Circuit Type : AC 50/60 Hz
  • [Uimp] Rated Impulse Withstand Voltage : 8 kV IEC 60947
  • Overvoltage Category : III
  • Range : TeSys
  • Product Certifications : DNV || CCC || CSA || RINA || GL || UL || LROS (Lloyds register of shipping) || BV || GOST || UKCA
  • Protective Cover : with
  • Associated Fuse Rating : 10 A gG signalling circuit IEC 60947-5-1 || 200 A gG <= 690 V type 1 power circuit || 160 A gG <= 690 V type 2 power circuit
  • Average Impedance : 0.8 mOhm - Ith 125 A 50 Hz power circuit
  • Tightening Torque : control circuit 1.2 N.m lugs-ring terminals flat Ø 6 mm M3.5 || control circuit 1.2 N.m lugs-ring terminals Philips No 2 M3.5 || power circuit 12 N.m lugs-ring terminals flat Ø 8 mm M6 || power circuit 12 N.m lugs-ring terminals hexagonal 10 mm M6 || power circuit 12 N.m bars flat Ø 8 mm M6 || power circuit 12 N.m bars hexagonal 10 mm M6
  • [Ui] Rated Insulation Voltage : power circuit 600 V CSA || power circuit 600 V UL || power circuit 1000 V IEC 60947-4-1 || signalling circuit 690 V IEC 60947-1 || signalling circuit 600 V CSA || signalling circuit 600 V UL
  • [Icw] Rated Short-Time Withstand Current : 640 A 40 °C - 10 s power circuit || 990 A 40 °C - 1 s power circuit || 135 A 40 °C - 10 min power circuit || 320 A 40 °C - 1 min power circuit || 100 A - 1 s signalling circuit || 120 A - 500 ms signalling circuit || 140 A - 100 ms signalling circuit
  • Mechanical Durability : 4 Mcycles
  • [Ie] Rated Operational Current : 125 A 60 °C) <= 440 V AC AC-1 power circuit || 80 A 60 °C) <= 440 V AC AC-3 power circuit
  • Operating Time : 20...35 ms closing || 6...20 ms opening
  • Power Dissipation Per Pole : 5.1 W AC-3 || 12.5 W AC-1
  • Safety Reliability Level : B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
  • Rated Breaking Capacity : 1100 A 440 V power circuit IEC 60947
  • Auxiliary Contact Composition : 1 NO + 1 NC
  • [Ue] Rated Operational Voltage : power circuit <= 300 V DC 25...400 Hz || power circuit <= 690 V AC
  • Motor Power Kw : 22 kW 220...230 V AC 50/60 Hz AC-3) || 37 kW 380...400 V AC 50/60 Hz AC-3) || 45 kW 415...440 V AC 50/60 Hz AC-3) || 55 kW 500 V AC 50/60 Hz AC-3) || 45 kW 660...690 V AC 50/60 Hz AC-3) || 45 kW 1000 V AC 50/60 Hz AC-3) || 15 kW 400 V AC 50/60 Hz AC-4)
  • Maximum Operating Rate : 3600 cyc/h 60 °C
  • Product Name : TeSys D
  • Electrical Durability : 0.8 Mcycles 125 A AC-1 <= 440 V || 1.5 Mcycles 80 A AC-3 <= 440 V
  • Standards : CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508
  • Pole Contact Composition : 3 NO
  • [Ith] Conventional Free Air Thermal Current : 10 A 60 °C signalling circuit || 125 A 60 °C power circuit
  • Mounting Support : rail || plate
  • Utilisation Category : AC-4 || AC-3 || AC-1
  • Product Or Component Type : contactor
  • Irms Rated Making Capacity : 140 A AC signalling circuit IEC 60947-5-1 || 250 A DC signalling circuit IEC 60947-5-1 || 1100 A 440 V power circuit IEC 60947