Schneider Electric at Mayer

IEC contactor, TeSys Deca, nonreversing, 80A, 60HP at 480VAC, up to 100kA SCCR, 3 phase, 3 NO, 120VAC 60Hz coil, open style

SQD LC1D80G6 CONTACTOR 575VAC

SQDLC1D80G6 LC1D80G6 3389110440829
541.22 / EA
http://schema.org/OutOfStock
  • Country of Origin: Czechia
  • Depth: 5.12 in
  • Height: 5 in
  • Warranty Length: 18 mth
  • Width: 3.35 in
TeSys Deca contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys Deca contactors are available in 13 contactor ratings for inductive motor applicati
QTY
  • Product Description
  • Features
  • Specifications
TeSys Deca contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys Deca contactors are available in 13 contactor ratings for inductive motor applicati
  • Uc Control Circuit Voltage
    • 120 V AC 60 Hz
  • Insulation Resistance
    • > 10 MOhm for signalling circuit
  • Heat Dissipation
    • 6-10 W at 60 Hz
  • Connections Terminals
    • control circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end
    • control circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffne
  • Mounting Support
    • rail
    • plate
  • Uimp Rated Impulse Withstand Voltage
    • 8 kV IEC 60947
  • Climatic Withstand
    • IACS E10 exposure to damp heat
  • Power Dissipation Per Pole
    • 5.1 W AC-3
    • 12.5 W AC-1
    • 5.1 W AC-3e
  • Maximum Operating Rate
    • 3600 cyc/h at 60 °C
  • Prop 65
    • WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
  • Carbon Footprint Of The Installation Phase A5
    • 0.3 kg CO2 eq.
    • 0.31002666931072853
  • Non Overlap Time
    • 1.5 ms on de-energisation between NC and NO contact
    • 1.5 ms on energisation between NC and NO contact
  • Carbon Footprint Of The End Of Life Phase C1 To C4
    • 4.088997647987764
    • 4 kg CO2 eq.
  • Standards
    • EN 60947-4-1
    • EN 60947-5-1
    • IEC 60947-4-1
    • IEC 60947-5-1
    • CSA C22.2 No 14
    • UL 60947-4-1
    • IEC 60335-2-40:Annex JJ
    • UL 60335-2-40:Annex JJ
    • IEC 60335-1:Clause 30.2
  • Ue Rated Operational Voltage
    • power circuit <= 300 V DC 25...400 Hz
    • power circuit <= 690 V AC
  • Ui Rated Insulation Voltage
    • power circuit 600 V CSA
    • power circuit 600 V UL
    • power circuit 1000 V IEC 60947-4-1
    • signalli
  • Operating Time
    • 20...35 ms closing
    • 6...20 ms opening
  • Control Circuit Type
    • AC 60 Hz
  • Ip Degree Of Protection
    • IP20 front face IEC 60529
  • Minimum Switching Voltage
    • 17 V for signalling circuit
  • Carbon Footprint Of The Manufacturing Phase A1 To A3
    • 11 kg CO2 eq.
    • 10.960713361237987
  • Protective Treatment
    • THIEC 60068-2-30
  • Average Impedance
    • 0.8 mOhm - Ith 125 A 50 Hz for power circuit
  • Electrical Durability
    • 0.8 Mcycles 125 A AC-1 <= 440 V
    • 1.5 Mcycles 80 A AC-3 <= 440 V
    • 1.
  • Maximum Horse Power Rating
    • 7.5 hp at 120 V AC 50/60 Hz for 1 phase motors
    • 15 hp at 230/240 V
  • Market Segmentation
    • Commercial
    • Industrial
  • Persona Type Names
    • End User
    • Contractor
    • Original Equipment Manufacturer
    • OEM - Control Panelbuilder
    • Panel Builder
    • System Integrator
  • Fire Resistance
    • 850 °C IEC 60695-2-1
  • Contactor Application
    • motor control
    • resistive load
  • Flame Retardance
    • V1 conforming to UL 94
  • Carbon Footprint Of The Use Phase B2 B3 B4 B6
    • 81 kg CO2 eq.
    • 81.20896739130431
  • Persona Type Ids
    • EU
    • LC
    • OM
    • OM8
    • PB
    • SI
  • Auxiliaries
    • LADN22
    • LADN11
    • LADN20
    • LAD8N11
    • LADT2
    • LADN40
    • LADN31
    • LADN02
    • LADT0
    • LAD8N20
  • Safety Reliability Level
    • B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1
    • B10d = 1369863 cycles contactor with nominal load EN/ISO 13
  • Carbon Footprint Of The Distribution Phase A4
    • 0.21622581342878092
    • 0.2 kg CO2 eq.
  • Tightening Torque
    • control circuit 1.2 N.m screw clamp terminals flat Ø 6 mm
    • control circuit 1.2 N.
  • Ith Conventional Free Air Thermal Current
    • 10 A (at 60 °C) for signalling circuit
    • 125 A (at 60 °C) for power circuit
  • Irms Rated Making Capacity
    • 140 A AC for signalling circuit conforming to IEC 60947-5-1
    • 250 A DC for s
  • Mechanical Robustness
    • vibrations contactor open 2 Gn, 5...300 Hz)
    • shocks contactor open 8 Gn for 11 ms)
    • vibratio
  • Minimum Switching Current
    • 5 mA for signalling circuit
  • Motor Power Kw
    • 22 kW at 220...230 V AC 50/60 Hz (AC-3)
    • 37 kW at 380...400 V AC 50/60 Hz (AC-3)
    • 37 kW at 380..
  • Control Circuit Voltage Limits
    • 0.85...1.1 Uc (-40-55 °C):operational AC 60 Hz
    • 0.3...0.6 Uc (-40-7
  • Utilisation Category
    • AC-3
    • AC-3e
    • AC-4
    • AC-1
  • Ie Rated Operational Current
    • 125 A (at <60 °C) at <= 1000 V AC AC-1 for power circuit
    • 125 A (at <60 °C) at <= 10
  • Icw Rated Short Time Withstand Current
    • 640 A 40 °C - 10 s for power circuit
    • 990 A 40 °C - 1 s for power circuit
    • 990 A 40 °C - 1 s for power circui
  • Hold In Power Consumption In Va
    • 22-22 VA 60 Hz cos phi 0.3 (at 20 °C)
  • Market Segmentation Id
    • COMMERCIAL
    • INDUSTRIAL
  • Inrush Power In Va
    • 220-220 VA 60 Hz cos phi 0.75 (at 20 °C)
  • Associated Fuse Rating
    • 10 A gG for signalling circuit conforming to IEC 60947-5-1
    • 200 A gG at <= 690
  • Permissible Ambient Air Temperature Around The Device
    • -40-60 °C
    • 60-70 °C with derating
  • Rated Breaking Capacity
    • 1100 A at 440 V for power circuit conforming to IEC 60947
  • Product Certifications
    • CCC
    • UL
    • CB Scheme
    • CSA
    • CE
    • UKCA
    • Marine
    • EAC
  • Important Information Attributes
    • Country Id : US
    • Local Data Status : Publishable
    • Local Publishable Date : 2025-02-26
    • ETIM 10 : EC000066
    • Html Descr : TeSys D ContactorNumber of Poles: 3-PolesPole Contact Composition: 3 NORated Operational Current: 80AControl Circuit Voltage: 120V AC 50/60 HzNon-Reversing
    • Manufacturer : Schneider Electric
    • Device Type : LV equipment - LV contactor
    • Serviceability : No
    • Traceability : No
    • Field Service Division : PPIBS
    • Average Life Duration : 20 year(s)
    • Manufacturing Carbon Footprint : 10.960713361238
    • Distribution Carbon Footprint : 0.216225813428781
    • Installation Carbon Footprint : 0.310026669310729
    • Use Carbon Footprint : 81.2089673913043
    • End Of Life Carbon Footprint : 4.08899764798776
    • Legacy WEEE Scope : In
    • WEEE Product Category : 5
    • Scope Perimeter : At least in Europe
    • EOLI Availability Display : No need of specific recycling operations
    • Reach Full Compliance Status : Free of Substances of Very High Concern above the threshold
    • Reach Full Compliance Status Id : NOT_CONTAINING_SVHC
    • Reach Compliance Directive : Free of Substances of Very High Concern above the threshold
    • ROHS Eur In Scope : Yes
    • ROHS Eur Status : Compliant
    • ROHS Eur Conformity Date : 1924
    • ROHS Eur Full Compliance Status : Compliant
    • ROHS Eur Full Compliance Status Id : COMPLIANT
    • China ROHS In Scope : No
    • China ROHS Label : 1
    • With Recycled Cardboard : Yes
    • Without Single Use Plastic : Yes
    • Product Contributes To Saved And Avoided Emissions : No
    • Return Indicator : Y
    • WD Status : 1 - GSC certified
    • Tier Id : 1
    • Tier : 1
    • Function Option Id : STANDARD
    • Function Option : Standard
    • Coil Technology : without built-in suppressor module
    • Compatibility Code : LC1D
    • Contact Compatibility : M12
    • Device Short Name : LC1D
    • Mechanical Durability : 10 Mcycles
    • Overvoltage Category : III
    • Package Weight Lbs : 1.540 kg
    • Pole Contact Composition : 3 NO
    • Poles Description : 3P
    • Product Availability : Stock - Normally stocked in distribution facility
    • Product Or Component Type : contactor
    • Range : TeSys
    • Range Of Product : TeSys Deca
    • Returnability : Yes
    • Signalling Circuit Frequency : 25...400 Hz
    • Sustainable Packaging : Yes
    • Total Lifecycle Carbon Footprint : 97 kg CO2 eq.
    • Weee Label : The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
    • Carbon Footprint Kg Co2 Eq Total Life Cycle : 96.78493088326958
    • Relationshiptype : Compatible relationship
  • General Attributes
    • Product Or Component Type : contactor
    • Range Of Product : TeSys Deca
  • Environment Attributes
    • ROHS Exemption Information : Yes
    • China ROHS Url : https://checkaproduct.se.com/DistantRequestDispatcher.aspx?action=exportPdfRoHSChina&pid=4049623&lang=en-us
    • Take Back : No
    • Reach Free Shvc : Yes
    • Recycled Metal Content At Cr Level : 0 %
    • China ROHS Regulation : Pro-active China RoHS declaration (out of China RoHS legal scope)
    • Toxic Heavy Metal Free : Yes
    • Mercury Free : Yes
    • Carbon Footprint : 96.7849308832696
    • Environmental Disclosure : ENVPEP110205EN
    • Eu Rohs Directive : Compliant
    • Operating Altitude : 0...9842.52 ft (0...3000 m)
    • Packaging Made With Recycled Cardboard : Yes
    • Packaging Without Single Use Plastic : Yes
    • Reach Free Of Svhc : Yes
    • Reach Regulation : Free of Substances of Very High Concern above the threshold
  • Contractual Warranty Attributes
    • Warranty Period : 18 months
    • Warranty : 18 months
  • Specifications
    • Country of Origin : Czechia
    • Height : 5 in
    • Width : 3.35 in
    • Depth : 5.12 in