IEC contactor, TeSys D, nonreversing, 50A, 40HP at 480VAC, 3 phase, 3 pole, 3 NO, 230VAC 50/60Hz coil, open style

TeSys D 3P Everlink AC CONTR A

SQDLC1D50A6P7 LC1D50A6P7 785901606666
269.09 / EACH
  • Certifications: BV, CCC, CSA, DNV, GL, GOST, LROS (Lloyds Register Of Shipping), RINA, UKCA, UL
  • Contact Configuration: 1 NO + 1 NC, 3 NO
  • Depth: 120 mm
  • Height: 122 mm
  • Impedance: 1.5 MOhm - Ith 80 A 50 Hz Power Circuit
  • Net Weight: 0.855 kg
  • Standard: CSA C22.2 No 14, EN 60947-4-1, EN 60947-5-1, IEC 60947-4-1, IEC 60947-5-1, UL 508
  • Storage Temperature: -60-80 °C
  • Warranty Length: 18 mth
  • Width: 55 mm
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 50A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 15HP at 200 to 208VAC, 15HP at 240VAC, 40HP at 480VAC and 40HP at 600VAC three phase. Contactor is also rated for 3HP at 115VAC and 7.5HP at 240VAC single phase. Contactor is supplied with a 230 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Ring-lug screw terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 4.80 inches tall, 2.17 inches wide and 4.72 inches deep. It weighs 1.88 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
  • Product Description
  • Specifications
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 50A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 15HP at 200 to 208VAC, 15HP at 240VAC, 40HP at 480VAC and 40HP at 600VAC three phase. Contactor is also rated for 3HP at 115VAC and 7.5HP at 240VAC single phase. Contactor is supplied with a 230 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Ring-lug screw terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 4.80 inches tall, 2.17 inches wide and 4.72 inches deep. It weighs 1.88 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
  • Utilisation Category : AC-3 || AC-1 || AC-4
  • Motor Power Kw : 15 kW 220...230 V AC 50/60 Hz AC-3) || 22 kW 380...400 V AC 50/60 Hz AC-3) || 30 kW 500 V AC 50/60 Hz AC-3) || 33 kW 660...690 V AC 50/60 Hz AC-3) || 25 kW 415 V AC 50/60 Hz AC-3) || 30 kW 440 V AC 50/60 Hz AC-3) || 11 kW 400 V AC 50/60 Hz AC-4)
  • Product Certifications : DNV || LROS (Lloyds register of shipping) || CCC || GL || RINA || BV || GOST || CSA || UL || UKCA
  • Product Name : TeSys D
  • Mechanical Durability : 6 Mcycles
  • [Ue] Rated Operational Voltage : power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
  • Product Or Component Type : contactor
  • Protective Cover : with
  • Range : TeSys
  • [Ie] Rated Operational Current : 50 A 60 °C) <= 440 V AC AC-3 power circuit || 80 A 60 °C) <= 440 V AC AC-1 power circuit
  • Operating Time : 4...19 ms opening || 12...26 ms closing
  • Pole Contact Composition : 3 NO
  • Control Circuit Type : AC 50/60 Hz
  • Mounting Support : rail || plate
  • [Ui] Rated Insulation Voltage : power circuit 600 V CSA || power circuit 600 V UL || signalling circuit 690 V IEC 60947-1 || signalling circuit 600 V CSA || signalling circuit 600 V UL || power circuit 690 V IEC 60947-4-1
  • Associated Fuse Rating : 10 A gG signalling circuit IEC 60947-5-1 || 100 A gG <= 690 V type 1 power circuit || 100 A gG <= 690 V type 2 power circuit
  • Auxiliary Contact Composition : 1 NO + 1 NC
  • Irms Rated Making Capacity : 140 A AC signalling circuit IEC 60947-5-1 || 250 A DC signalling circuit IEC 60947-5-1 || 900 A 440 V power circuit IEC 60947
  • Tightening Torque : control circuit 1.7 N.m lugs-ring terminals flat Ø 6 mm M3.5 || control circuit 1.7 N.m lugs-ring terminals Philips No 2 M3.5 || power circuit 6 N.m lugs-ring terminals hexagonal 10 mm M6
  • [Uimp] Rated Impulse Withstand Voltage : 6 kV IEC 60947
  • Standards : CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508
  • Maximum Operating Rate : 3600 cyc/h 60 °C
  • Overvoltage Category : III
  • [Ith] Conventional Free Air Thermal Current : 10 A 60 °C signalling circuit || 80 A 60 °C power circuit
  • Maximum Horse Power Rating : 3 hp 115 V at AC 50/60 Hz for 1 phase || 7.5 hp 230/240 V at AC 50/60 Hz for 1 phase || 15 hp 200/208 V at AC 50/60 Hz for 3 phase || 15 hp 230/240 V at AC 50/60 Hz for 3 phase || 40 hp 460/480 V at AC 50/60 Hz for 3 phase || 40 hp 575/600 V at AC 50/60 Hz for 3 phase
  • Electrical Durability : 1.45 Mcycles 50 A AC-3 <= 440 V || 1.1 Mcycles 80 A AC-1 <= 440 V
  • Rated Breaking Capacity : 900 A 440 V power circuit IEC 60947
  • Power Dissipation Per Pole : 3.7 W AC-3 || 9.6 W AC-1
  • [Icw] Rated Short-Time Withstand Current : 400 A 40 °C - 10 s power circuit || 810 A 40 °C - 1 s power circuit || 84 A 40 °C - 10 min power circuit || 208 A 40 °C - 1 min power circuit || 100 A - 1 s signalling circuit || 120 A - 500 ms signalling circuit || 140 A - 100 ms signalling circuit
  • Poles Description : 3P
  • [Uc] Control Circuit Voltage : 230 V AC 50/60 Hz
  • Connections - Terminals : control circuit lugs-ring terminals 8 mm) || power circuit lugs-ring terminals 16.5 mm)
  • Contactor Application : resistive load || motor control
  • Average Impedance : 1.5 mOhm - Ith 80 A 50 Hz power circuit
  • Device Short Name : LC1D
  • Safety Reliability Level : B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
  • Contractual warranty
    • Warranty : 18 months
  • Offer Sustainability
    • Eu Rohs Directive : Compliant
    • Circularity Profile : ENVEOLI1503009EN
    • Pvc Free : Yes
    • Mercury Free : Yes
    • Sustainable Offer Status : Green Premium product
    • Toxic Heavy Metal Free : Yes
    • Rohs Exemption Information : Yes
    • Environmental Disclosure : ENVPEP1503009EN
    • China Rohs Regulation : Pro-active China RoHS declaration (out of China RoHS legal scope)
    • Weee : The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
    • Reach Free Of Svhc : Yes
    • Reach Regulation : Free of Substances of Very High Concern above the threshold
    • California Proposition 65 : WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
  • Environment
    • Width : 55 mm
    • Mechanical Robustness : vibrations contactor open2 Gn, 5...300 Hz || vibrations contactor closed4 Gn, 5...300 Hz || shocks contactor closed15 Gn for 11 ms || shocks contactor open10 Gn for 11 ms
    • Fire Resistance : 850 °C IEC 60695-2-1
    • Ambient Air Temperature For Operation : -40-60 °C || 60-70 °C with derating
    • Height : 122 mm
    • Ip Degree Of Protection : IP20 front face IEC 60529
    • Depth : 120 mm
    • Pollution Degree : 3
    • Flame Retardance : V1 conforming to UL 94
    • Ambient Air Temperature For Storage : -60-80 °C
    • Net Weight : 0.855 kg
    • Operating Altitude : 0...9842.52 ft (0...3000 m)
    • Protective Treatment : TH IEC 60068-2-30
  • Complementary
    • Control Circuit Voltage Limits : 0.3...0.6 Uc -40-70 °C drop-out AC 50/60 Hz || 0.8...1.1 Uc -40-60 °C operational AC 50 Hz || 0.85...1.1 Uc -40-60 °C operational AC 60 Hz || 1...1.1 Uc 60-70 °C operational AC 50/60 Hz
    • Heat Dissipation : 4-5 W 50/60 Hz
    • Insulation Resistance : > 10 MOhm signalling circuit
    • Inrush Power In Va : 140-140 VA 60 Hz 0.75 20 °C) || 160-160 VA 50 Hz 0.75 20 °C)
    • Minimum Switching Current : 5 mA signalling circuit
    • Auxiliary Contacts Type : mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
    • Hold-In Power Consumption In Va : 13-13 VA 60 Hz 0.3 20 °C) || 15-15 VA 50 Hz 0.3 20 °C)
    • Coil Technology : without built-in suppressor module
    • Signalling Circuit Frequency : 25...400 Hz
    • Minimum Switching Voltage : 17 V signalling circuit
    • Non-Overlap Time : 1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact