IEC contactor, TeSys D, nonreversing, 40A, 30HP at 480VAC, up to 100kA SCCR, 3 phase, 3 NO, 125VDC coil, open style

TeSys D 3P Everlink DC CONTR A

SQDLC1D40AGD LC1D40AGD 338911940852
300.82 / EA
  • Certifications: CCC, CSA, GOST, UL
  • Contact Configuration: 1 NO + 1 NC, 3 NO
  • Depth: 120 mm
  • Height: 122 mm
  • Impedance: 1.5 MOhm - Ith 60 A 50 Hz Power Circuit
  • Net Weight: 0.925 kg
  • Standard: CSA C22.2 No 14, EN 60947-4-1, EN 60947-5-1, IEC 60335-1, IEC 60947-4-1, IEC 60947-5-1, UL 508
  • Storage Temperature: -60-80 °C
  • Warranty Length: 18 mth
  • Width: 55 mm
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 40A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 10HP at 200 to 208VAC, 10HP at 240VAC, 30HP at 480VAC and 30HP at 600VAC three phase. Contactor is also rated for 3HP at 115VAC and 5HP at 240VAC single phase. When used with a 480VAC up to 110A circuit breaker, this contactor can have a SCCR up to 100kA. When used with up to a 600VAC 90A Class J or CC fuse, this contactor can have a SCCR up to 100kA. Contactor is supplied with a 125 VDC coil with transient suppressor module. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 4.80 inches tall, 2.17 inches wide and 4.72 inches deep. It weighs 1.87 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
  • Product Description
  • Specifications
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 40A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 10HP at 200 to 208VAC, 10HP at 240VAC, 30HP at 480VAC and 30HP at 600VAC three phase. Contactor is also rated for 3HP at 115VAC and 5HP at 240VAC single phase. When used with a 480VAC up to 110A circuit breaker, this contactor can have a SCCR up to 100kA. When used with up to a 600VAC 90A Class J or CC fuse, this contactor can have a SCCR up to 100kA. Contactor is supplied with a 125 VDC coil with transient suppressor module. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 4.80 inches tall, 2.17 inches wide and 4.72 inches deep. It weighs 1.87 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
  • [Ui] Rated Insulation Voltage : power circuit 600 V CSA || power circuit 600 V UL || signalling circuit 690 V IEC 60947-1 || signalling circuit 600 V CSA || signalling circuit 600 V UL || power circuit 690 V IEC 60947-4-1
  • Mechanical Durability : 10 Mcycles
  • Utilisation Category : AC-3 || AC-4 || AC-1
  • Product Name : TeSys D || TeSys Deca
  • Operating Time : 42.5...57.5 ms closing || 16...24 ms opening
  • Connections - Terminals : control circuit screw clamp terminals 2 1-2.5 mm²flexible with cable end || control circuit screw clamp terminals 1 1-4 mm²flexible without cable end || control circuit screw clamp terminals 2 1-4 mm²flexible without cable end || control circuit screw clamp terminals 1 1-4 mm²flexible with cable end || control circuit screw clamp terminals 1 1-4 mm²solid without cable end || control circuit screw clamp terminals 2 1-4 mm²solid without cable end || power circuit EverLink BTR screw connectors 1 1-35 mm²flexible without cable end || power circuit EverLink BTR screw connectors 2 1-25 mm²flexible without cable end || power circuit EverLink BTR screw connectors 1 1-35 mm²flexible with cable end || power circuit EverLink BTR screw connectors 2 1-25 mm²flexible with cable end || power circuit EverLink BTR screw connectors 1 1-35 mm²solid without cable end || power circuit EverLink BTR screw connectors 2 1-25 mm²solid without cable end
  • Irms Rated Making Capacity : 140 A AC signalling circuit IEC 60947-5-1 || 250 A DC signalling circuit IEC 60947-5-1 || 800 A 440 V power circuit IEC 60947
  • Control Circuit Type : DC standard
  • Maximum Operating Rate : 3600 cyc/h 60 °C
  • [Icw] Rated Short-Time Withstand Current : 320 A 40 °C - 10 s power circuit || 720 A 40 °C - 1 s power circuit || 72 A 40 °C - 10 min power circuit || 165 A 40 °C - 1 min power circuit || 100 A - 1 s signalling circuit || 120 A - 500 ms signalling circuit || 140 A - 100 ms signalling circuit
  • Power Dissipation Per Pole : 2.4 W AC-3 || 5.4 W AC-1
  • [Ie] Rated Operational Current : 60 A 60 °C) <= 440 V AC AC-1 power circuit || 40 A 60 °C) <= 440 V AC AC-3 power circuit
  • Device Short Name : LC1D
  • Maximum Horse Power Rating : 5 hp 230/240 V at AC 50/60 Hz for 1 phase || 10 hp 230/240 V at AC 50/60 Hz for 3 phase || 30 hp 575/600 V at AC 50/60 Hz for 3 phase || 10 hp 200/208 V at AC 50/60 Hz for 3 phase || 3 hp 115 V at AC 50/60 Hz for 1 phase || 30 hp 460/480 V at AC 50/60 Hz for 3 phase
  • Product Certifications : UL || GOST || CCC || CSA
  • Standards : CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508 || IEC 60335-1
  • Associated Fuse Rating : 10 A gG signalling circuit IEC 60947-5-1 || 80 A gG <= 690 V type 1 power circuit || 80 A gG <= 690 V type 2 power circuit
  • Mounting Support : rail || plate
  • Motor Power Kw : 18.5 kW 380...400 V AC 50/60 Hz AC-3) || 11 kW 220...230 V AC 50/60 Hz AC-3) || 22 kW 415...440 V AC 50/60 Hz AC-3) || 22 kW 500 V AC 50/60 Hz AC-3) || 30 kW 660...690 V AC 50/60 Hz AC-3) || 9 kW 400 V AC 50/60 Hz AC-4)
  • Poles Description : 3P
  • Contactor Application : resistive load || motor control
  • Rated Breaking Capacity : 800 A 440 V power circuit IEC 60947
  • Overvoltage Category : III
  • Pole Contact Composition : 3 NO
  • Electrical Durability : 0.7 Mcycles 60 A AC-1 <= 440 V || 1.5 Mcycles 40 A AC-3 <= 440 V
  • Average Impedance : 1.5 mOhm - Ith 60 A 50 Hz power circuit
  • Auxiliary Contact Composition : 1 NO + 1 NC
  • Range : TeSys || TeSys Deca
  • [Ue] Rated Operational Voltage : power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
  • [Ith] Conventional Free Air Thermal Current : 10 A 60 °C signalling circuit || 60 A 60 °C power circuit
  • [Uimp] Rated Impulse Withstand Voltage : 6 kV IEC 60947
  • Safety Reliability Level : B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
  • Product Or Component Type : contactor
  • [Uc] Control Circuit Voltage : 125 V DC
  • Protective Cover : with
  • Tightening Torque : control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || power circuit 8 N.m EverLink BTR screw connectors 25-35 mm² hexagonal 4 mm || power circuit 5 N.m EverLink BTR screw connectors 1-25 mm² hexagonal 4 mm || control circuit 1.7 N.m screw clamp terminals pozidriv No 2 || power circuit 2.5 N.m screw clamp terminals pozidriv No 2
  • Environment
    • Ambient Air Temperature For Storage : -60-80 °C
    • Height : 122 mm
    • Width : 55 mm
    • Ip Degree Of Protection : IP20 front face IEC 60529
    • Pollution Degree : 3
    • Mechanical Robustness : vibrations contactor open2 Gn, 5...300 Hz || vibrations contactor closed4 Gn, 5...300 Hz || shocks contactor closed15 Gn for 11 ms || shocks contactor open10 Gn for 11 ms
    • Ambient Air Temperature For Operation : -40-60 °C || 60-70 °C with derating
    • Operating Altitude : 0...9842.52 ft (0...3000 m)
    • Depth : 120 mm
    • Flame Retardance : V1 conforming to UL 94
    • Fire Resistance : 850 °C IEC 60695-2-1
    • Protective Treatment : TH IEC 60068-2-30
    • Net Weight : 0.925 kg
  • Complementary
    • Minimum Switching Voltage : 17 V signalling circuit
    • Inrush Power In W : 19-19 W 20 °C)
    • Auxiliary Contacts Type : mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
    • Signalling Circuit Frequency : 25...400 Hz
    • Minimum Switching Current : 5 mA signalling circuit
    • Hold-In Power Consumption In W : 7.4-7.4 W 20 °C
    • Non-Overlap Time : 1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
    • Control Circuit Voltage Limits : 0.1...0.3 Uc -40-70 °C drop-out DC || 0.75...1.25 Uc -40-60 °C operational DC || 1...1.25 Uc 60-70 °C operational DC
    • Insulation Resistance : > 10 MOhm signalling circuit
    • Coil Technology : built-in bidirectional peak limiting diode suppressor
    • Time Constant : 34 ms
  • Contractual warranty
    • Warranty : 18 months
  • Offer Sustainability
    • California Proposition 65 : WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
    • Reach Regulation : Free of Substances of Very High Concern above the threshold
    • Weee : The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
    • Reach Free Of Svhc : Yes
    • Eu Rohs Directive : Compliant
    • Toxic Heavy Metal Free : Yes
    • Environmental Disclosure : ENVPEP1503009EN
    • China Rohs Regulation : Pro-active China RoHS declaration (out of China RoHS legal scope)
    • Sustainable Offer Status : Green Premium product
    • Rohs Exemption Information : Yes
    • Circularity Profile : ENVEOLI1503009EN
    • Pvc Free : Yes
    • Mercury Free : Yes