Schneider Electric at Mayer

IEC contactor, TeSys D, nonreversing, 38A, 20HP at 480VAC, up to 100kA SCCR, 3 phase, 3 NO, 110VAC 50/60Hz coil, open

CONTACTOR 575VAC 38AMP IEC +OP

SQDLC1D38F7 LC1D38F7 785901422921
211.11 / EACH
  • Certifications: BV, CCC, CSA, DNV, GL, GOST, LROS (Lloyds Register Of Shipping), RINA, UKCA, UL
  • Contact Configuration: 1 NO + 1 NC
  • Contact Configuration: 3 NO
  • Depth: 92 mm
  • Height: 85 mm
  • Impedance: 2 MOhm - Ith 50 A 50 Hz Power Circuit
  • Net Weight: 0.38 kg
  • Standard: CSA C22.2 No 14, EN 60947-4-1, EN 60947-5-1, IEC 60947-4-1, IEC 60947-5-1, UL 508
  • Storage Temperature: -60-80 °C
  • Warranty Length: 18 mth
  • Width: 45 mm
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 38A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 10HP at 200 to 208VAC, 10HP at 240VAC, 20HP at 480VAC and 25HP at 600VAC three phase. Contactor is also rated for 2HP at 115VAC and 5HP at 240VAC single phase. When used with a 480VAC up to 60A circuit breaker, this contactor can have a SCCR up to 85kA. When used with up to a 600VAC 80A Class J or CC fuse, this contactor can have a SCCR up to 100kA. Contactor is supplied with a 110 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.35 inches tall, 1.77 inches wide and 3.62 inches deep. It weighs 0.84 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
  • Product Description
  • Specifications
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 38A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 10HP at 200 to 208VAC, 10HP at 240VAC, 20HP at 480VAC and 25HP at 600VAC three phase. Contactor is also rated for 2HP at 115VAC and 5HP at 240VAC single phase. When used with a 480VAC up to 60A circuit breaker, this contactor can have a SCCR up to 85kA. When used with up to a 600VAC 80A Class J or CC fuse, this contactor can have a SCCR up to 100kA. Contactor is supplied with a 110 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.35 inches tall, 1.77 inches wide and 3.62 inches deep. It weighs 0.84 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
  • Offer Sustainability
    • China Rohs Regulation : Pro-active China RoHS declaration (out of China RoHS legal scope)
    • Sustainable Offer Status : Green Premium product
    • Environmental Disclosure : ENVPEP110229EN
    • Weee : The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
    • Rohs Exemption Information : Yes
    • Eu Rohs Directive : Compliant
    • California Proposition 65 : WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
    • Circularity Profile : ENVEOLI1102029EN
    • Mercury Free : Yes
    • Pvc Free : Yes
    • Toxic Heavy Metal Free : Yes
    • Reach Free Of Svhc : Yes
    • Reach Regulation : Free of Substances of Very High Concern above the threshold
  • Product Name : TeSys D
  • Associated Fuse Rating : 10 A gG signalling circuit IEC 60947-5-1 || 63 A gG <= 690 V type 1 power circuit || 63 A gG <= 690 V type 2 power circuit
  • Device Short Name : LC1D
  • [Uc] Control Circuit Voltage : 110 V AC 50/60 Hz
  • [Ie] Rated Operational Current : 50 A 60 °C) <= 440 V AC AC-1 power circuit || 38 A 60 °C) <= 440 V AC AC-3 power circuit
  • Pole Contact Composition : 3 NO
  • Product Or Component Type : contactor
  • Safety Reliability Level : B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
  • Utilisation Category : AC-3 || AC-1
  • Average Impedance : 2 mOhm - Ith 50 A 50 Hz power circuit
  • [Ui] Rated Insulation Voltage : power circuit 600 V CSA || power circuit 600 V UL || signalling circuit 690 V IEC 60947-1 || signalling circuit 600 V CSA || signalling circuit 600 V UL || power circuit 690 V IEC 60947-4-1
  • Rated Breaking Capacity : 550 A 440 V power circuit IEC 60947
  • Maximum Operating Rate : 3600 cyc/h 60 °C
  • Irms Rated Making Capacity : 140 A AC signalling circuit IEC 60947-5-1 || 250 A DC signalling circuit IEC 60947-5-1 || 550 A 440 V power circuit IEC 60947
  • [Icw] Rated Short-Time Withstand Current : 60 A 40 °C - 10 min power circuit || 430 A 40 °C - 1 s power circuit || 150 A 40 °C - 1 min power circuit || 310 A 40 °C - 10 s power circuit || 100 A - 1 s signalling circuit || 120 A - 500 ms signalling circuit || 140 A - 100 ms signalling circuit
  • Maximum Horse Power Rating : 10 hp 230/240 V at AC 50/60 Hz for 3 phase || 10 hp 200/208 V at AC 50/60 Hz for 3 phase || 5 hp 240 V at AC 50/60 Hz for 1 phase || 20 hp 480 V at AC 50/60 Hz for 3 phase || 25 hp 600 V at AC 50/60 Hz for 3 phase
  • Product Certifications : UL || DNV || RINA || BV || CCC || CSA || LROS (Lloyds register of shipping) || GL || GOST || UKCA
  • Auxiliary Contact Composition : 1 NO + 1 NC
  • Operating Time : 4...19 ms opening || 12...22 ms closing
  • Power Dissipation Per Pole : 5 W AC-1 || 3 W AC-3
  • Control Circuit Type : AC 50/60 Hz
  • Protective Cover : with
  • Tightening Torque : control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || power circuit 2.5 N.m screw clamp terminals flat Ø 6 mm || power circuit 2.5 N.m screw clamp terminals Philips No 2
  • [Uimp] Rated Impulse Withstand Voltage : 6 kV IEC 60947
  • Range : TeSys
  • Connections - Terminals : control circuit screw clamp terminals 2 1-2.5 mm²flexible with cable end || control circuit screw clamp terminals 1 1-4 mm²flexible without cable end || control circuit screw clamp terminals 2 1-4 mm²flexible without cable end || control circuit screw clamp terminals 1 1-4 mm²flexible with cable end || control circuit screw clamp terminals 1 1-4 mm²solid without cable end || control circuit screw clamp terminals 2 1-4 mm²solid without cable end || power circuit screw clamp terminals 1 2.5-10 mm²flexible without cable end || power circuit screw clamp terminals 2 2.5-10 mm²flexible without cable end || power circuit screw clamp terminals 1 1-10 mm²flexible with cable end || power circuit screw clamp terminals 2 1.5-6 mm²flexible with cable end || power circuit screw clamp terminals 1 1.5-10 mm²solid without cable end || power circuit screw clamp terminals 2 2.5-10 mm²solid without cable end
  • Mounting Support : plate || rail
  • Mechanical Durability : 15 Mcycles
  • Standards : CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508
  • Electrical Durability : 1.4 Mcycles 50 A AC-1 <= 440 V || 1.4 Mcycles 38 A AC-3 <= 440 V
  • Poles Description : 3P
  • Motor Power Kw : 18.5 kW 500 V AC 50/60 Hz || 18.5 kW 660...690 V AC 50/60 Hz || 18.5 kW 380...400 V AC 50/60 Hz || 9 kW 220...230 V AC 50/60 Hz || 18.5 kW 415...440 V AC 50/60 Hz
  • [Ue] Rated Operational Voltage : power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
  • [Ith] Conventional Free Air Thermal Current : 10 A 60 °C signalling circuit || 50 A 60 °C power circuit
  • Contactor Application : resistive load || motor control
  • Overvoltage Category : III
  • Contractual warranty
    • Warranty : 18 months
  • Environment
    • Height : 85 mm
    • Flame Retardance : V1 conforming to UL 94
    • Ambient Air Temperature For Storage : -60-80 °C
    • Depth : 92 mm
    • Mechanical Robustness : vibrations contactor open2 Gn, 5...300 Hz || vibrations contactor closed4 Gn, 5...300 Hz || shocks contactor closed15 Gn for 11 ms || shocks contactor open8 Gn for 11 ms
    • Net Weight : 0.38 kg
    • Pollution Degree : 3
    • Width : 45 mm
    • Protective Treatment : TH IEC 60068-2-30
    • Ip Degree Of Protection : IP20 front face IEC 60529
    • Ambient Air Temperature For Operation : -40-60 °C || 60-70 °C with derating
    • Fire Resistance : 850 °C IEC 60695-2-1
    • Operating Altitude : 0...9842.52 ft (0...3000 m)
  • Complementary
    • Hold-In Power Consumption In Va : 7.5-7.5 VA 60 Hz 0.3 20 °C) || 7-7 VA 50 Hz 0.3 20 °C)
    • Signalling Circuit Frequency : 25...400 Hz
    • Minimum Switching Current : 5 mA signalling circuit
    • Insulation Resistance : > 10 MOhm signalling circuit
    • Coil Technology : without built-in suppressor module
    • Inrush Power In Va : 70-70 VA 60 Hz 0.75 20 °C) || 70-70 VA 50 Hz 0.75 20 °C)
    • Auxiliary Contacts Type : mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
    • Heat Dissipation : 2-3 W 50/60 Hz
    • Minimum Switching Voltage : 17 V signalling circuit
    • Non-Overlap Time : 1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
    • Control Circuit Voltage Limits : 0.3...0.6 Uc -40-70 °C drop-out AC 50/60 Hz || 0.8...1.1 Uc -40-60 °C operational AC 50 Hz || 0.85...1.1 Uc -40-60 °C operational AC 60 Hz || 1...1.1 Uc 60-70 °C operational AC 50/60 Hz