IEC contactor, TeSys D, nonreversing, 25A, 15HP at 480VAC, 3 phase, 3 pole, 3 NO, low consumption 24VDC coil, open style

CONTACTOR 600VAC 25AMP IEC +OP

SQDLC1D256BL LC1D256BL 785901550990
206.74 / EACH
  • Certifications: BV, CCC, CSA, DNV, GL, GOST, LROS (Lloyds Register Of Shipping), RINA, UKCA, UL
  • Contact Configuration: 1 NO + 1 NC, 3 NO
  • Depth: 101 mm
  • Height: 85 mm
  • Impedance: 2 MOhm - Ith 40 A 50 Hz Power Circuit
  • Net Weight: 0.53 kg
  • Standard: CSA C22.2 No 14, EN 60947-4-1, EN 60947-5-1, IEC 60947-4-1, IEC 60947-5-1, UL 508
  • Storage Temperature: -60-80 °C
  • Warranty Length: 18 mth
  • Width: 45 mm
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 25A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 7.5HP at 200 to 208VAC, 7.5HP at 240VAC, 15HP at 480VAC and 20HP at 600VAC three phase. Contactor is also rated for 2HP at 115VAC and 3HP at 240VAC single phase. Contactor is supplied with a low consumption 24 VDC coil with transient suppressor module. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Ring-lug screw terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.35 inches tall, 1.77 inches wide and 3.98 inches deep. It weighs 1.17 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
  • Product Description
  • Specifications
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 25A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 7.5HP at 200 to 208VAC, 7.5HP at 240VAC, 15HP at 480VAC and 20HP at 600VAC three phase. Contactor is also rated for 2HP at 115VAC and 3HP at 240VAC single phase. Contactor is supplied with a low consumption 24 VDC coil with transient suppressor module. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Ring-lug screw terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.35 inches tall, 1.77 inches wide and 3.98 inches deep. It weighs 1.17 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
  • Environment
    • Depth : 101 mm
    • Height : 85 mm
    • Protective Treatment : TH IEC 60068-2-30
    • Mechanical Robustness : vibrations contactor open2 Gn, 5...300 Hz || vibrations contactor closed4 Gn, 5...300 Hz || shocks contactor closed15 Gn for 11 ms || shocks contactor open8 Gn for 11 ms
    • Pollution Degree : 3
    • Ambient Air Temperature For Operation : -40-60 °C || 60-70 °C with derating
    • Ambient Air Temperature For Storage : -60-80 °C
    • Flame Retardance : V1 conforming to UL 94
    • Operating Altitude : 0...9842.52 ft (0...3000 m)
    • Fire Resistance : 850 °C IEC 60695-2-1
    • Width : 45 mm
    • Ip Degree Of Protection : IP20 front face IEC 60529
    • Net Weight : 0.53 kg
  • Offer Sustainability
    • Rohs Exemption Information : Yes
    • Toxic Heavy Metal Free : Yes
    • China Rohs Regulation : Pro-active China RoHS declaration (out of China RoHS legal scope)
    • Mercury Free : Yes
    • Circularity Profile : ENVEOLI1102029EN
    • Sustainable Offer Status : Green Premium product
    • Eu Rohs Directive : Compliant
    • Weee : The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
    • Environmental Disclosure : ENVPEP110229EN
    • California Proposition 65 : WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
    • Pvc Free : Yes
    • Reach Regulation : Free of Substances of Very High Concern above the threshold
    • Reach Free Of Svhc : Yes
  • Complementary
    • Signalling Circuit Frequency : 25...400 Hz
    • Minimum Switching Voltage : 17 V signalling circuit
    • Hold-In Power Consumption In W : 2.4-2.4 W 20 °C
    • Inrush Power In W : 2.4-2.4 W 20 °C)
    • Coil Technology : built-in bidirectional peak limiting diode suppressor
    • Non-Overlap Time : 1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
    • Insulation Resistance : > 10 MOhm signalling circuit
    • Control Circuit Voltage Limits : 0.1...0.3 Uc -40-70 °C drop-out DC || 0.8...1.25 Uc -40-60 °C operational DC || 1...1.25 Uc 60-70 °C operational DC
    • Time Constant : 40 ms
    • Auxiliary Contacts Type : mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
    • Minimum Switching Current : 5 mA signalling circuit
  • Contractual warranty
    • Warranty : 18 months
  • [Icw] Rated Short-Time Withstand Current : 240 A 40 °C - 10 s power circuit || 380 A 40 °C - 1 s power circuit || 50 A 40 °C - 10 min power circuit || 120 A 40 °C - 1 min power circuit || 100 A - 1 s signalling circuit || 120 A - 500 ms signalling circuit || 140 A - 100 ms signalling circuit
  • Poles Description : 3P
  • Average Impedance : 2 mOhm - Ith 40 A 50 Hz power circuit
  • Auxiliary Contact Composition : 1 NO + 1 NC
  • Maximum Operating Rate : 3600 cyc/h 60 °C
  • [Ui] Rated Insulation Voltage : power circuit 690 V IEC 60947-4-1 || power circuit 600 V CSA || power circuit 600 V UL || signalling circuit 690 V IEC 60947-1 || signalling circuit 600 V CSA || signalling circuit 600 V UL
  • [Uc] Control Circuit Voltage : 24 V DC
  • Irms Rated Making Capacity : 140 A AC signalling circuit IEC 60947-5-1 || 250 A DC signalling circuit IEC 60947-5-1 || 450 A 440 V power circuit IEC 60947
  • Mounting Support : rail || plate
  • Safety Reliability Level : B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
  • Pole Contact Composition : 3 NO
  • Utilisation Category : AC-1 || AC-3 || AC-4
  • Overvoltage Category : III
  • Connections - Terminals : control circuit lugs-ring terminals 8 mm) || power circuit lugs-ring terminals 10 mm)
  • [Ue] Rated Operational Voltage : power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
  • Standards : CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508
  • Electrical Durability : 1.65 Mcycles 25 A AC-3 <= 440 V || 1.4 Mcycles 40 A AC-1 <= 440 V
  • Protective Cover : with
  • Product Or Component Type : contactor
  • [Uimp] Rated Impulse Withstand Voltage : 6 kV IEC 60947
  • Operating Time : 65.45...88.55 ms closing || 20...30 ms opening
  • [Ie] Rated Operational Current : 25 A 60 °C) <= 440 V AC AC-3 power circuit || 40 A 60 °C) <= 440 V AC AC-1 power circuit
  • Power Dissipation Per Pole : 3.2 W AC-1 || 1.25 W AC-3
  • Device Short Name : LC1D
  • Tightening Torque : control circuit 1.7 N.m lugs-ring terminals flat Ø 6 mm M3.5 || control circuit 1.7 N.m lugs-ring terminals Philips No 2 M3.5 || power circuit 2.5 N.m lugs-ring terminals flat Ø 8 mm M4 || power circuit 2.5 N.m lugs-ring terminals Philips No 2 M4
  • Motor Power Kw : 5.5 kW 220...230 V AC 50/60 Hz AC-3) || 11 kW 380...400 V AC 50/60 Hz AC-3) || 11 kW 415...440 V AC 50/60 Hz AC-3) || 15 kW 500 V AC 50/60 Hz AC-3) || 15 kW 660...690 V AC 50/60 Hz AC-3) || 5.5 kW 400 V AC 50/60 Hz AC-4)
  • Rated Breaking Capacity : 450 A 440 V power circuit IEC 60947
  • Range : TeSys
  • Product Certifications : GL || CSA || GOST || RINA || LROS (Lloyds register of shipping) || DNV || BV || CCC || UL || UKCA
  • Contactor Application : motor control || resistive load
  • Associated Fuse Rating : 10 A gG signalling circuit IEC 60947-5-1 || 63 A gG <= 690 V type 1 power circuit || 40 A gG <= 690 V type 2 power circuit
  • Maximum Horse Power Rating : 3 hp 230/240 V at AC 50/60 Hz for 1 phase || 2 hp 115 V at AC 50/60 Hz for 1 phase || 7.5 hp 230/240 V at AC 50/60 Hz for 3 phase || 15 hp 460/480 V at AC 50/60 Hz for 3 phase || 20 hp 575/600 V at AC 50/60 Hz for 3 phase || 7.5 hp 200/208 V at AC 50/60 Hz for 3 phase
  • Mechanical Durability : 30 Mcycles
  • [Ith] Conventional Free Air Thermal Current : 10 A 60 °C signalling circuit || 40 A 60 °C power circuit
  • Control Circuit Type : DC low consumption
  • Product Name : TeSys D