Schneider Electric at Mayer

IEC contactor, TeSys D, nonreversing, 25A, 15HP at 480VAC, 3 phase, 3 pole, 3 NO, 220VAC 50/60Hz coil, open style

CONTACTOR 600VAC 25AMP IEC +OP

SQDLC1D256M7 LC1D256M7 338911080486
0.00 / EA
  • Certifications: BV, CCC, CSA, DNV, GL, GOST, LROS (Lloyds Register Of Shipping), RINA, UKCA, UL
  • Contact Configuration: 3 NO
  • Contact Configuration: 1 NO + 1 NC
  • Depth: 92 mm
  • Height: 85 mm
  • Impedance: 2 MOhm - Ith 40 A 50 Hz Power Circuit
  • Net Weight: 0.37 kg
  • Standard: CSA C22.2 No 14, EN 60947-4-1, EN 60947-5-1, IEC 60947-4-1, IEC 60947-5-1, UL 508
  • Storage Temperature: -60-80 °C
  • Warranty Length: 18 mth
  • Width: 45 mm
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 25A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 7.5HP at 200 to 208VAC, 7.5HP at 240VAC, 15HP at 480VAC and 20HP at 600VAC three phase. Contactor is also rated for 2HP at 115VAC and 3HP at 240VAC single phase. Contactor is supplied with a 220 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Ring-lug screw terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.35 inches tall, 1.77 inches wide and 3.62 inches deep. It weighs 0.82 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
  • Product Description
  • Specifications
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 25A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 7.5HP at 200 to 208VAC, 7.5HP at 240VAC, 15HP at 480VAC and 20HP at 600VAC three phase. Contactor is also rated for 2HP at 115VAC and 3HP at 240VAC single phase. Contactor is supplied with a 220 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Ring-lug screw terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.35 inches tall, 1.77 inches wide and 3.62 inches deep. It weighs 0.82 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
  • [Uc] Control Circuit Voltage : 220 V AC 50/60 Hz
  • [Ith] Conventional Free Air Thermal Current : 10 A 60 °C signalling circuit || 40 A 60 °C power circuit
  • Power Dissipation Per Pole : 3.2 W AC-1 || 1.25 W AC-3
  • Control Circuit Type : AC 50/60 Hz
  • Average Impedance : 2 mOhm - Ith 40 A 50 Hz power circuit
  • Associated Fuse Rating : 10 A gG signalling circuit IEC 60947-5-1 || 63 A gG <= 690 V type 1 power circuit || 40 A gG <= 690 V type 2 power circuit
  • Pole Contact Composition : 3 NO
  • Overvoltage Category : III
  • [Icw] Rated Short-Time Withstand Current : 240 A 40 °C - 10 s power circuit || 380 A 40 °C - 1 s power circuit || 50 A 40 °C - 10 min power circuit || 120 A 40 °C - 1 min power circuit || 100 A - 1 s signalling circuit || 120 A - 500 ms signalling circuit || 140 A - 100 ms signalling circuit
  • Tightening Torque : control circuit 1.7 N.m lugs-ring terminals flat Ø 6 mm M3.5 || control circuit 1.7 N.m lugs-ring terminals Philips No 2 M3.5 || power circuit 2.5 N.m lugs-ring terminals flat Ø 8 mm M4 || power circuit 2.5 N.m lugs-ring terminals Philips No 2 M4
  • Product Certifications : CSA || GOST || DNV || GL || LROS (Lloyds register of shipping) || BV || CCC || RINA || UL || UKCA
  • Motor Power Kw : 5.5 kW 220...230 V AC 50/60 Hz || 11 kW 380...400 V AC 50/60 Hz || 11 kW 415...440 V AC 50/60 Hz || 15 kW 500 V AC 50/60 Hz || 15 kW 660...690 V AC 50/60 Hz
  • Electrical Durability : 1.65 Mcycles 25 A AC-3 <= 440 V || 1.4 Mcycles 40 A AC-1 <= 440 V
  • [Uimp] Rated Impulse Withstand Voltage : 6 kV IEC 60947
  • Device Short Name : LC1D
  • Mounting Support : rail || plate
  • [Ui] Rated Insulation Voltage : power circuit 690 V IEC 60947-4-1 || power circuit 600 V CSA || power circuit 600 V UL || signalling circuit 690 V IEC 60947-1 || signalling circuit 600 V CSA || signalling circuit 600 V UL
  • Contactor Application : motor control || resistive load
  • Mechanical Durability : 15 Mcycles
  • Poles Description : 3P
  • Connections - Terminals : control circuit lugs-ring terminals 8 mm) || power circuit lugs-ring terminals 10 mm)
  • Irms Rated Making Capacity : 140 A AC signalling circuit IEC 60947-5-1 || 250 A DC signalling circuit IEC 60947-5-1 || 450 A 440 V power circuit IEC 60947
  • Maximum Horse Power Rating : 3 hp 230/240 V at AC 50/60 Hz for 1 phase || 2 hp 115 V at AC 50/60 Hz for 1 phase || 7.5 hp 230/240 V at AC 50/60 Hz for 3 phase || 15 hp 460/480 V at AC 50/60 Hz for 3 phase || 20 hp 575/600 V at AC 50/60 Hz for 3 phase || 7.5 hp 200/208 V at AC 50/60 Hz for 3 phase
  • Safety Reliability Level : B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
  • Product Name : TeSys D
  • Rated Breaking Capacity : 450 A 440 V power circuit IEC 60947
  • Protective Cover : with
  • Operating Time : 12...22 ms closing || 4...19 ms opening
  • Utilisation Category : AC-1 || AC-3
  • Maximum Operating Rate : 3600 cyc/h 60 °C
  • [Ue] Rated Operational Voltage : power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
  • Auxiliary Contact Composition : 1 NO + 1 NC
  • Standards : CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508
  • Range : TeSys
  • Product Or Component Type : contactor
  • [Ie] Rated Operational Current : 25 A 60 °C) <= 440 V AC AC-3 power circuit || 40 A 60 °C) <= 440 V AC AC-1 power circuit
  • Contractual warranty
    • Warranty : 18 months
  • Environment
    • Pollution Degree : 3
    • Ambient Air Temperature For Operation : -40-60 °C || 60-70 °C with derating
    • Flame Retardance : V1 conforming to UL 94
    • Ambient Air Temperature For Storage : -60-80 °C
    • Ip Degree Of Protection : IP20 front face IEC 60529
    • Width : 45 mm
    • Height : 85 mm
    • Operating Altitude : 0...9842.52 ft (0...3000 m)
    • Protective Treatment : TH IEC 60068-2-30
    • Net Weight : 0.37 kg
    • Mechanical Robustness : vibrations contactor open2 Gn, 5...300 Hz || vibrations contactor closed4 Gn, 5...300 Hz || shocks contactor closed15 Gn for 11 ms || shocks contactor open8 Gn for 11 ms
    • Fire Resistance : 850 °C IEC 60695-2-1
    • Depth : 92 mm
  • Offer Sustainability
    • Sustainable Offer Status : Green Premium product
    • Weee : The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
    • China Rohs Regulation : Pro-active China RoHS declaration (out of China RoHS legal scope)
    • Eu Rohs Directive : Compliant
    • California Proposition 65 : WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
    • Environmental Disclosure : ENVPEP110229EN
    • Circularity Profile : ENVEOLI1102029EN
    • Reach Regulation : Free of Substances of Very High Concern above the threshold
    • Reach Free Of Svhc : Yes
    • Mercury Free : Yes
    • Rohs Exemption Information : Yes
    • Pvc Free : Yes
    • Toxic Heavy Metal Free : Yes
  • Complementary
    • Non-Overlap Time : 1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
    • Hold-In Power Consumption In Va : 7.5-7.5 VA 60 Hz 0.3 20 °C) || 7-7 VA 50 Hz 0.3 20 °C)
    • Auxiliary Contacts Type : mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
    • Insulation Resistance : > 10 MOhm signalling circuit
    • Control Circuit Voltage Limits : 0.3...0.6 Uc -40-70 °C drop-out AC 50/60 Hz || 0.8...1.1 Uc -40-60 °C operational AC 50 Hz || 0.85...1.1 Uc -40-60 °C operational AC 60 Hz || 1...1.1 Uc 60-70 °C operational AC 50/60 Hz
    • Inrush Power In Va : 70-70 VA 60 Hz 0.75 20 °C) || 70-70 VA 50 Hz 0.75 20 °C)
    • Minimum Switching Current : 5 mA signalling circuit
    • Minimum Switching Voltage : 17 V signalling circuit
    • Signalling Circuit Frequency : 25...400 Hz
    • Coil Technology : without built-in suppressor module
    • Heat Dissipation : 2-3 W 50/60 Hz