IEC contactor, TeSys D, nonreversing, 150A, 100HP at 480VAC, up to 100kA SCCR, 3 phase, 3 NO, 72VDC coil, open style

CONTACTOR 600V AC 150 AMP IEC

SQDLC1D150SD LC1D150SD 785901402930
761.32 / EA
  • Certifications: BV, CCC, CSA, DNV, GL, GOST, LROS (Lloyds Register Of Shipping), RINA, UKCA, UL
  • Contact Configuration: 1 NO + 1 NC, 3 NO
  • Depth: 136 mm
  • Height: 158 mm
  • Impedance: 0.6 MOhm - Ith 200 A 50 Hz Power Circuit
  • Net Weight: 2.5 kg
  • Standard: CSA C22.2 No 14, EN 60947-4-1, EN 60947-5-1, IEC 60947-4-1, IEC 60947-5-1, UL 508
  • Storage Temperature: -60-80 °C
  • Warranty Length: 18 mth
  • Width: 120 mm
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 150A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 40HP at 200 to 208VAC, 50HP at 240VAC, 100HP at 480VAC and 125HP at 600VAC three phase. When used with a 480VAC up to 250A circuit breaker, this contactor can have a SCCR up to 100kA. When used with up to a 600VAC 300A Class J or CC fuse, this contactor can have a SCCR up to 100kA. Contactor is supplied with a 72 VDC coil with transient suppressor module. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 6.22 inches tall, 4.72 inches wide and 5.35 inches deep. It weighs 5.51 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
  • Product Description
  • Specifications
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 150A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 40HP at 200 to 208VAC, 50HP at 240VAC, 100HP at 480VAC and 125HP at 600VAC three phase. When used with a 480VAC up to 250A circuit breaker, this contactor can have a SCCR up to 100kA. When used with up to a 600VAC 300A Class J or CC fuse, this contactor can have a SCCR up to 100kA. Contactor is supplied with a 72 VDC coil with transient suppressor module. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 6.22 inches tall, 4.72 inches wide and 5.35 inches deep. It weighs 5.51 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
  • Offer Sustainability
    • Circularity Profile : ENVEOLI100405EN
    • Weee : The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
    • Rohs Exemption Information : Yes
    • Mercury Free : Yes
    • Sustainable Offer Status : Green Premium product
    • China Rohs Regulation : Product out of China RoHS scope. Substance declaration for your information.
    • Pvc Free : Yes
    • Eu Rohs Directive : Compliant
    • Environmental Disclosure : ENVPEP060301EN
    • California Proposition 65 : WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
    • Reach Regulation : Free of Substances of Very High Concern above the threshold
  • Complementary
    • Inrush Power In W : 270-365 W 20 °C)
    • Signalling Circuit Frequency : 25...400 Hz
    • Insulation Resistance : > 10 MOhm signalling circuit
    • Time Constant : 25 ms
    • Minimum Switching Current : 5 mA signalling circuit
    • Auxiliary Contacts Type : mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
    • Hold-In Power Consumption In W : 2.4-5.1 W 20 °C
    • Control Circuit Voltage Limits : 0.75...1.2 Uc -40-55 °C operational DC || 0.15...0.4 Uc -40-70 °C drop-out DC || 1...1.2 Uc 55-70 °C operational DC
    • Coil Technology : with integral suppression device
    • Non-Overlap Time : 1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
    • Minimum Switching Voltage : 17 V signalling circuit
  • Contractual warranty
    • Warranty : 18 months
  • Maximum Operating Rate : 1200 cyc/h 60 °C
  • Control Circuit Type : DC standard
  • Product Name : TeSys D
  • Poles Description : 3P
  • Mechanical Durability : 8 Mcycles
  • Tightening Torque : control circuit 1.2 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.2 N.m screw clamp terminals Philips No 2 || power circuit 12 N.m connector hexagonal 4 mm
  • Protective Cover : with
  • Standards : CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508
  • Motor Power Kw : 40 kW 220...230 V AC 50/60 Hz AC-3) || 75 kW 380...400 V AC 50/60 Hz AC-3) || 80 kW 415...440 V AC 50/60 Hz AC-3) || 90 kW 500 V AC 50/60 Hz AC-3) || 100 kW 660...690 V AC 50/60 Hz AC-3) || 75 kW 1000 V AC 50/60 Hz AC-3) || 22 kW 400 V AC 50/60 Hz AC-4)
  • Overvoltage Category : III
  • [Ui] Rated Insulation Voltage : power circuit 600 V CSA || power circuit 600 V UL || power circuit 1000 V IEC 60947-4-1 || signalling circuit 690 V IEC 60947-1 || signalling circuit 600 V CSA || signalling circuit 600 V UL
  • Operating Time : 20...35 ms closing || 40...75 ms opening
  • Mounting Support : plate || rail
  • Associated Fuse Rating : 10 A gG signalling circuit IEC 60947-5-1 || 315 A gG <= 690 V type 1 power circuit || 250 A gG <= 690 V type 2 power circuit
  • Maximum Horse Power Rating : 40 hp 200/208 V at AC 50/60 Hz for 3 phase || 50 hp 230/240 V at AC 50/60 Hz for 3 phase || 100 hp 460/480 V at AC 50/60 Hz for 3 phase || 125 hp 575/600 V at AC 50/60 Hz for 3 phase
  • [Icw] Rated Short-Time Withstand Current : 250 A 40 °C - 10 min power circuit || 580 A 40 °C - 1 min power circuit || 1200 A 40 °C - 10 s power circuit || 1400 A 40 °C - 1 s power circuit || 100 A - 1 s signalling circuit || 120 A - 500 ms signalling circuit || 140 A - 100 ms signalling circuit
  • Connections - Terminals : control circuit screw clamp terminals 2 1-2.5 mm²flexible with cable end || control circuit screw clamp terminals 1 1-2.5 mm²flexible with cable end || control circuit screw clamp terminals 1 1-2.5 mm²flexible without cable end || control circuit screw clamp terminals 2 1-2.5 mm²flexible without cable end || control circuit screw clamp terminals 1 1-2.5 mm²solid without cable end || control circuit screw clamp terminals 2 1-2.5 mm²solid without cable end || power circuit connector 1 10-120 mm²flexible without cable end || power circuit connector 2 10-50 mm²flexible without cable end || power circuit connector 1 10-120 mm²flexible with cable end || power circuit connector 2 10-50 mm²flexible with cable end || power circuit connector 1 10-120 mm²solid without cable end || power circuit connector 2 10-50 mm²solid without cable end
  • [Uc] Control Circuit Voltage : 72 V DC
  • [Ue] Rated Operational Voltage : power circuit <= 1000 V AC 25...400 Hz || power circuit <= 300 V DC
  • Average Impedance : 0.6 mOhm - Ith 200 A 50 Hz power circuit
  • Product Certifications : GOST || BV || CSA || UL || GL || CCC || DNV || LROS (Lloyds register of shipping) || RINA || UKCA
  • Product Or Component Type : contactor
  • Irms Rated Making Capacity : 140 A AC signalling circuit IEC 60947-5-1 || 250 A DC signalling circuit IEC 60947-5-1 || 1660 A 440 V power circuit IEC 60947
  • Auxiliary Contact Composition : 1 NO + 1 NC
  • Electrical Durability : 0.85 Mcycles 150 A AC-3 <= 440 V || 1 Mcycles 200 A AC-1 <= 440 V
  • Rated Breaking Capacity : 1400 A 440 V power circuit IEC 60947
  • [Ith] Conventional Free Air Thermal Current : 200 A 60 °C power circuit
  • Device Short Name : LC1D
  • Range : TeSys
  • Safety Reliability Level : B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
  • Contactor Application : motor control || resistive load
  • [Uimp] Rated Impulse Withstand Voltage : 8 kV IEC 60947
  • [Ie] Rated Operational Current : 200 A 60 °C) <= 440 V AC AC-1 power circuit || 150 A 60 °C) <= 440 V AC AC-3 power circuit
  • Power Dissipation Per Pole : 24 W AC-1 || 13.5 W AC-3
  • Utilisation Category : AC-4 || AC-1 || AC-3
  • Pole Contact Composition : 3 NO
  • Environment
    • Protective Treatment : TH IEC 60068-2-30
    • Ambient Air Temperature For Storage : -60-80 °C
    • Height : 158 mm
    • Pollution Degree : 3
    • Ambient Air Temperature For Operation : -40-60 °C || 60-70 °C with derating
    • Net Weight : 2.5 kg
    • Ip Degree Of Protection : IP20 front face IEC 60529
    • Flame Retardance : V1 conforming to UL 94
    • Width : 120 mm
    • Mechanical Robustness : vibrations contactor open2 Gn, 5...300 Hz || vibrations contactor closed4 Gn, 5...300 Hz || shocks contactor closed15 Gn for 11 ms || shocks contactor open6 Gn for 11 ms
    • Fire Resistance : 850 °C IEC 60695-2-1
    • Depth : 136 mm
    • Operating Altitude : 0...9842.52 ft (0...3000 m)