Schneider Electric at Mayer

IEC contactor, TeSys D, nonreversing, 150A, 100HP at 480VAC, 3 phase, 3 pole, 3 NO, 24VAC 50/60Hz coil, open style

CONTACTOR 600VAC 150AMP IEC +O

SQDLC1D1506B7 LC1D1506B7 785901429807
761.32 / EACH
  • Certifications: BV, CCC, CSA, DNV, GL, GOST, LROS (Lloyds Register Of Shipping), RINA, UKCA, UL
  • Contact Configuration: 1 NO + 1 NC
  • Contact Configuration: 3 NO
  • Depth: 136 mm
  • Height: 158 mm
  • Impedance: 0.6 MOhm - Ith 200 A 50 Hz Power Circuit
  • Net Weight: 2.5 kg
  • Standard: CSA C22.2 No 14, EN 60947-4-1, EN 60947-5-1, IEC 60947-4-1, IEC 60947-5-1, UL 508
  • Storage Temperature: -60-80 °C
  • Warranty Length: 18 mth
  • Width: 120 mm
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 150A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 40HP at 200 to 208VAC, 50HP at 240VAC, 100HP at 480VAC and 125HP at 600VAC three phase. Contactor is supplied with a 24 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Ring-lug screw terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 6.22 inches tall, 4.72 inches wide and 5.35 inches deep. It weighs 5.51 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
  • Product Description
  • Specifications
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 150A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 40HP at 200 to 208VAC, 50HP at 240VAC, 100HP at 480VAC and 125HP at 600VAC three phase. Contactor is supplied with a 24 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Ring-lug screw terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 6.22 inches tall, 4.72 inches wide and 5.35 inches deep. It weighs 5.51 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
  • Contractual warranty
    • Warranty : 18 months
  • Environment
    • Width : 120 mm
    • Net Weight : 2.5 kg
    • Mechanical Robustness : vibrations contactor open2 Gn, 5...300 Hz || vibrations contactor closed4 Gn, 5...300 Hz || shocks contactor closed15 Gn for 11 ms || shocks contactor open6 Gn for 11 ms
    • Protective Treatment : TH IEC 60068-2-30
    • Pollution Degree : 3
    • Depth : 136 mm
    • Ambient Air Temperature For Storage : -60-80 °C
    • Flame Retardance : V1 conforming to UL 94
    • Fire Resistance : 850 °C IEC 60695-2-1
    • Height : 158 mm
    • Operating Altitude : 0...9842.52 ft (0...3000 m)
    • Ip Degree Of Protection : IP20 front face IEC 60529
    • Ambient Air Temperature For Operation : -40-60 °C || 60-70 °C with derating
  • [Uimp] Rated Impulse Withstand Voltage : 8 kV IEC 60947
  • Safety Reliability Level : B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
  • Range : TeSys
  • Contactor Application : motor control || resistive load
  • Tightening Torque : control circuit 1.2 N.m lugs-ring terminals flat Ø 6 mm M3.5 || control circuit 1.2 N.m lugs-ring terminals Philips No 2 M3.5 || power circuit 12 N.m lugs-ring terminals hexagonal 13 mm M8 || power circuit 12 N.m bars hexagonal 13 mm M8
  • Device Short Name : LC1D
  • [Icw] Rated Short-Time Withstand Current : 250 A 40 °C - 10 min power circuit || 580 A 40 °C - 1 min power circuit || 1200 A 40 °C - 10 s power circuit || 1400 A 40 °C - 1 s power circuit || 100 A - 1 s signalling circuit || 120 A - 500 ms signalling circuit || 140 A - 100 ms signalling circuit
  • Product Certifications : UL || LROS (Lloyds register of shipping) || DNV || GOST || RINA || CSA || CCC || BV || GL || UKCA
  • Product Or Component Type : contactor
  • Mechanical Durability : 8 Mcycles
  • Operating Time : 20...35 ms closing || 40...75 ms opening
  • Motor Power Kw : 40 kW 220...230 V AC 50/60 Hz AC-3) || 75 kW 380...400 V AC 50/60 Hz AC-3) || 80 kW 415...440 V AC 50/60 Hz AC-3) || 90 kW 500 V AC 50/60 Hz AC-3) || 100 kW 660...690 V AC 50/60 Hz AC-3) || 75 kW 1000 V AC 50/60 Hz AC-3) || 22 kW 400 V AC 50/60 Hz AC-4)
  • [Uc] Control Circuit Voltage : 24 V AC 50/60 Hz
  • Mounting Support : rail || plate
  • Product Name : TeSys D
  • Auxiliary Contact Composition : 1 NO + 1 NC
  • [Ith] Conventional Free Air Thermal Current : 200 A 60 °C power circuit
  • Pole Contact Composition : 3 NO
  • [Ue] Rated Operational Voltage : power circuit <= 1000 V AC 25...400 Hz || power circuit <= 300 V DC
  • Standards : CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508
  • Rated Breaking Capacity : 1400 A 440 V power circuit IEC 60947
  • Connections - Terminals : control circuit lugs-ring terminals 8 mm) || power circuit lugs-ring terminals 25 mm) || power circuit bars 1 5 x 25 mm
  • Average Impedance : 0.6 mOhm - Ith 200 A 50 Hz power circuit
  • Poles Description : 3P
  • [Ie] Rated Operational Current : 200 A 60 °C) <= 440 V AC AC-1 power circuit || 150 A 60 °C) <= 440 V AC AC-3 power circuit
  • Maximum Operating Rate : 1200 cyc/h 60 °C
  • [Ui] Rated Insulation Voltage : power circuit 600 V CSA || power circuit 600 V UL || power circuit 1000 V IEC 60947-4-1 || signalling circuit 690 V IEC 60947-1 || signalling circuit 600 V CSA || signalling circuit 600 V UL
  • Overvoltage Category : III
  • Associated Fuse Rating : 10 A gG signalling circuit IEC 60947-5-1 || 315 A gG <= 690 V type 1 power circuit || 250 A gG <= 690 V type 2 power circuit
  • Electrical Durability : 0.85 Mcycles 150 A AC-3 <= 440 V || 1 Mcycles 200 A AC-1 <= 440 V
  • Power Dissipation Per Pole : 24 W AC-1 || 13.5 W AC-3
  • Protective Cover : with
  • Utilisation Category : AC-3 || AC-1 || AC-4
  • Control Circuit Type : AC 50/60 Hz
  • Maximum Horse Power Rating : 40 hp 200/208 V at AC 50/60 Hz for 3 phase || 50 hp 230/240 V at AC 50/60 Hz for 3 phase || 100 hp 460/480 V at AC 50/60 Hz for 3 phase || 125 hp 575/600 V at AC 50/60 Hz for 3 phase
  • Irms Rated Making Capacity : 140 A AC signalling circuit IEC 60947-5-1 || 250 A DC signalling circuit IEC 60947-5-1 || 1660 A 440 V power circuit IEC 60947
  • Offer Sustainability
    • Pvc Free : Yes
    • Environmental Disclosure : ENVPEP060301EN
    • Weee : The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
    • Circularity Profile : ENVEOLI100405EN
    • Sustainable Offer Status : Green Premium product
    • Reach Regulation : Free of Substances of Very High Concern above the threshold
    • California Proposition 65 : WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
    • Rohs Exemption Information : Yes
    • China Rohs Regulation : Product out of China RoHS scope. Substance declaration for your information.
    • Mercury Free : Yes
    • Eu Rohs Directive : Compliant
  • Complementary
    • Signalling Circuit Frequency : 25...400 Hz
    • Hold-In Power Consumption In Va : 2-18 VA 60 Hz 0.9 20 °C) || 2-18 VA 50 Hz 0.9 20 °C)
    • Insulation Resistance : > 10 MOhm signalling circuit
    • Auxiliary Contacts Type : mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
    • Minimum Switching Current : 5 mA signalling circuit
    • Non-Overlap Time : 1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
    • Coil Technology : built-in bidirectional peak limiting diode suppressor
    • Inrush Power In Va : 280-350 VA 60 Hz 0.9 20 °C) || 280-350 VA 50 Hz 0.9 20 °C)
    • Minimum Switching Voltage : 17 V signalling circuit
    • Control Circuit Voltage Limits : 0.3...0.5 Uc -40-70 °C drop-out AC 50/60 Hz || 0.8...1.15 Uc -40-55 °C operational AC 50/60 Hz || 1...1.15 Uc 55-70 °C operational AC 50/60 Hz
    • Heat Dissipation : 3-4.5 W 50/60 Hz