Schneider Electric at Mayer

IEC contactor, TeSys D Green, nonreversing, 40A, 30HP at 480VAC, up to 100kA SCCR, 3 phase, 3 NO, 24/60VAC/VDC coil

TESYS D CTR, 40A, 24-60VAC/DC

SQDLC1D40ABNE LC1D40ABNE 785901765080
121.42 / EA
  • Certifications: CCC, CSA, DNV-GL, EAC, KC, LROS (Lloyds Register Of Shipping), UKCA, UL
  • Contact Configuration: 1 NO + 1 NC, 3 NO
  • Depth: 120 mm
  • Height: 122 mm
  • Impedance: 1.5 MOhm - Ith 60 A 50 Hz Power Circuit
  • Net Weight: 0.992 kg
  • Standard: CSA C22.2 No 60947-4-1, EN/IEC 60947-4-1, EN/IEC 60947-5-1, IEC 60335-1, UL 60947-4-1
  • Storage Temperature: -60-80 °C
  • Warranty Length: 18 mth
  • Width: 55 mm
TeSys D Green contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 40A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 10HP at 200 to 208VAC, 10HP at 240VAC, 30HP at 480VAC and 30HP at 600VAC three phase. Contactor is also rated for 3HP at 115VAC and 5HP at 240VAC single phase. When used with a 480VAC up to 110A circuit breaker, this contactor can have a SCCR up to 100kA. When used with up to a 600VAC 90A Class J or CC fuse, this contactor can have a SCCR up to 100kA. Equipped with an electronic coil, wide band voltage 24-60V, AC/DC compatible, low consumption. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 4.80 inches tall, 2.17 inches wide and 4.72 inches deep. It weighs 2.19 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
  • Product Description
  • Specifications
TeSys D Green contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 40A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 10HP at 200 to 208VAC, 10HP at 240VAC, 30HP at 480VAC and 30HP at 600VAC three phase. Contactor is also rated for 3HP at 115VAC and 5HP at 240VAC single phase. When used with a 480VAC up to 110A circuit breaker, this contactor can have a SCCR up to 100kA. When used with up to a 600VAC 90A Class J or CC fuse, this contactor can have a SCCR up to 100kA. Equipped with an electronic coil, wide band voltage 24-60V, AC/DC compatible, low consumption. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 4.80 inches tall, 2.17 inches wide and 4.72 inches deep. It weighs 2.19 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
  • Offer Sustainability
    • Rohs Exemption Information : Yes
    • Halogen Content Performance : Halogen free plastic parts & cables product
    • Environmental Disclosure : ENVPEP1607010EN
    • Eu Rohs Directive : Compliant
    • Reach Regulation : Free of Substances of Very High Concern above the threshold
    • Weee : The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
    • Mercury Free : Yes
    • Sustainable Offer Status : Green Premium product
    • China Rohs Regulation : Product out of China RoHS scope. Substance declaration for your information.
    • Circularity Profile : ENVEOLI1607010EN
  • Operating Time : 55...65 ms closing || 20...120 ms opening >= 17221) || 20...80 ms opening >= 18011)
  • [Ie] Rated Operational Current : 60 A 60 °C) <= 440 V AC-1 power circuit || 40 A 60 °C) <= 440 V AC-3 power circuit || 40 A 60 °C) <= 440 V AC-3e power circuit
  • Average Impedance : 1.5 mOhm - Ith 60 A 50 Hz power circuit
  • [Icw] Rated Short-Time Withstand Current : 72 A 40 °C - 10 min power circuit || 165 A 40 °C - 1 min power circuit || 320 A 40 °C - 10 s power circuit || 720 A 40 °C - 1 s power circuit || 100 A - 1 s signalling circuit || 120 A - 500 ms signalling circuit || 140 A - 100 ms signalling circuit
  • Product Or Component Type : contactor
  • Contactor Application : resistive load || motor control
  • [Uc] Control Circuit Voltage : 24...60 V AC 50/60 Hz || 24...60 V DC
  • [Ue] Rated Operational Voltage : power circuit <= 690 V AC 25...400 Hz
  • Associated Fuse Rating : 80 A gG <= 690 V type 1 power circuit || 80 A gG <= 690 V type 2 power circuit || 10 A gG signalling circuit IEC 60947-5-1
  • Electrical Durability : 2 Mcycles 35 A AC-3 <= 440 V || 0.7 Mcycles 60 A AC-1 <= 440 V || 2 Mcycles 35 A AC-3e <= 440 V
  • Protective Cover : with
  • Poles Description : 3P
  • Mechanical Durability : 6 Mcycles
  • [Uimp] Rated Impulse Withstand Voltage : 6 kV IEC 60947
  • Range : TeSys || TeSys Deca
  • Maximum Horse Power Rating : 3 hp 115 V at AC 60 Hz for 1 phase || 5 hp 230/240 V at AC 60 Hz for 1 phase || 10 hp 200/208 V at AC 60 Hz for 3 phase || 10 hp 230/240 V at AC 60 Hz for 3 phase || 30 hp 460/480 V at AC 60 Hz for 3 phase || 30 hp 575/600 V at AC 60 Hz for 3 phase
  • Overvoltage Category : III
  • [Ui] Rated Insulation Voltage : power circuit 690 V IEC 60947-4-1 || signalling circuit 690 V IEC 60947-1
  • Product Name : TeSys D Green || TeSys Deca
  • Motor Power Kw : 11 kW 220...230 V AC 50 Hz AC-3) || 18.5 kW 380...400 V AC 50 Hz AC-3) || 22 kW 415 V AC 50 Hz AC-3) || 22 kW 440 V AC 50 Hz AC-3) || 22 kW 500 V AC 50 Hz AC-3) || 30 kW 660...690 V AC 50 Hz AC-3) || 11 kW 220...230 V AC 50 Hz AC-3e) || 18.5 kW 380...400 V AC 50 Hz AC-3e) || 22 kW 415 V AC 50 Hz AC-3e) || 22 kW 440 V AC 50 Hz AC-3e) || 22 kW 500 V AC 50 Hz AC-3e) || 30 kW 660...690 V AC 50 Hz AC-3e)
  • Product Certifications : CCC || CSA || EAC || UL || KC || DNV-GL || LROS (Lloyds register of shipping) || UKCA
  • Power Dissipation Per Pole : 5.4 W AC-1 || 2.4 W AC-3 || 2.4 W AC-3e
  • Irms Rated Making Capacity : 800 A 440 V power circuit IEC 60947 || 140 A AC signalling circuit IEC 60947-5-1 || 250 A DC signalling circuit IEC 60947-5-1
  • Utilisation Category : AC-3 || AC-1 || AC-3e
  • Safety Reliability Level : B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
  • Maximum Operating Rate : 3600 cyc/h 60 °C
  • Auxiliary Contact Composition : 1 NO + 1 NC
  • Standards : EN/IEC 60947-4-1 || EN/IEC 60947-5-1 || UL 60947-4-1 || CSA C22.2 No 60947-4-1 || IEC 60335-1
  • Coil Type : AC/DC electronic
  • Rated Breaking Capacity : 800 A 440 V power circuit IEC 60947
  • Mounting Support : plate || rail
  • Tightening Torque : control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || power circuit 8 N.m EverLink BTR screw connectors 25-35 mm² hexagonal 4 mm || power circuit 5 N.m EverLink BTR screw connectors 1-25 mm² hexagonal 4 mm || power circuit 2.5 N.m lugs-ring terminals pozidriv No 2 M4 || control circuit 1.7 N.m lugs-ring terminals pozidriv No 2 M3.5
  • [Ith] Conventional Free Air Thermal Current : 60 A 60 °C power circuit || 10 A 60 °C signalling circuit
  • Device Short Name : LC1D
  • Connections - Terminals : control circuit screw clamp terminals 1 1-4 mm²flexible without cable end || control circuit screw clamp terminals 2 1-4 mm²flexible without cable end || control circuit screw clamp terminals 1 1-4 mm²flexible with cable end || control circuit screw clamp terminals 2 1-2.5 mm²flexible with cable end || control circuit screw clamp terminals 1 1-4 mm²solid || control circuit screw clamp terminals 2 1-4 mm²solid || power circuit EverLink BTR screw connectors 1 1-35 mm²flexible without cable end || power circuit EverLink BTR screw connectors 1 1-35 mm²flexible with cable end || power circuit EverLink BTR screw connectors 1 1-35 mm²solid || power circuit EverLink BTR screw connectors 2 1-25 mm²flexible without cable end || power circuit EverLink BTR screw connectors 2 1-25 mm²flexible with cable end || power circuit EverLink BTR screw connectors 2 1-25 mm²solid
  • Pole Contact Composition : 3 NO
  • Contractual warranty
    • Warranty : 18 months
  • Environment
    • Protective Treatment : TH IEC 60068-2-30
    • Mechanical Robustness : vibrations contactor open2 Gn, 5...300 Hz || vibrations contactor closed4 Gn, 5...300 Hz || shocks contactor open10 Gn for 11 ms || shocks contactor closed15 Gn for 11 ms
    • Flame Retardance : V1 conforming to UL 94
    • Net Weight : 0.992 kg
    • Width : 55 mm
    • Ip Degree Of Protection : IP20 front face IEC 60529
    • Ambient Air Temperature For Operation : -40-60 °C || 60-70 °C with derating
    • Fire Resistance : 850 °C IEC 60695-2-1
    • Operating Altitude : 0...9842.52 ft (0...3000 m)
    • Depth : 120 mm
    • Ambient Air Temperature For Storage : -60-80 °C
    • Height : 122 mm
    • Pollution Degree : 3
    • Color : Gray SE GREY 6) || Green SE GREEN 2)
  • Complementary
    • Coil Technology : built-in bidirectional peak limiting
    • Inrush Power In W : 16-16 W 20 °C
    • Auxiliary Contacts Type : mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
    • Inrush Power In Va : 15-15 VA 50/60 Hz 20 °C)
    • Minimum Switching Current : 5 mA signalling circuit
    • Signalling Circuit Frequency : 25...400 Hz
    • Control Circuit Voltage Limits : <= 0.1 Uc -40-70 °C drop-out AC/DC || 0.85...1.1 Uc -40-60 °C operational AC || 0.8...1.1 Uc -40-60 °C operational DC || 1...1.1 Uc 60-70 °C operational AC/DC
    • Non-Overlap Time : 1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
    • Insulation Resistance : > 10 MOhm signalling circuit
    • Heat Dissipation : 0.7-0.7 W 50/60 Hz
    • Hold-In Power Consumption In Va : 1-1 VA 20 °C) 50/60 Hz
    • Minimum Switching Voltage : 17 V signalling circuit
    • Hold-In Power Consumption In W : 0.7-0.7 W 20 °C