IEC contactor, TeSys Deca Green, nonreversing, 40A, 30HP at 480VAC, 3 phase, 3 pole, 3 NO, 100/250VAC/VDC coil, open style

TESY D CONT 3PAC3 440V40A 100

SQDLC1D40A6KUE LC1D40A6KUE 3606489493370
369.99 / EA
http://schema.org/OutOfStock
QTY
  • Product Description
  • Specifications
TeSys Deca contactor, 3 poles (3NO), for motor control applications up to 40A/690V AC-3/3e (18.5kW@400V). They can be used to create motor starters for almost any type of application. It provides a low consumption 100-250V AC/DC coil with electronic control, 1NO+1NC built-in auxiliary contacts (NC mirror certified), connection by ring-lugs screw terminals. For operating rates until 3600 cycles/hour and environments until 60°C, it procures high reliability and durability. Compact (55mm width), DIN-rail mounting or screw fixing. Contactor is rated for 10HP at 200 to 208VAC, 10HP at 240VAC, 30HP at 480VAC and 30HP at 600VAC three phase. Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh). Equipped with an electronic coil, wide band voltage 100-250V, AC/DC compatible, low consumption. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Ring-lug screw terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 4.80 inches tall, 2.17 inches wide and 4.72 inches deep. It weighs 2.19 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
  • Environment
    • Product Certifications : CCC || CSA || EAC || UL || KC || DNV-GL || LROS (Lloyds register of shipping) || UKCA
    • Height : 122 mm
    • Standards : EN/IEC 60947-4-1 || EN/IEC 60947-5-1 || UL 60947-4-1 || CSA C22.2 No 60947-4-1 || IEC 60335-1
    • Climatic Withstand : IACS E10 exposure to damp heat || IEC 60947-1 Annex Q category D exposure to damp heat
    • Net Weight : 0.992 kg
    • Flame Retardance : V1 conforming to UL 94
    • Ip Degree Of Protection : IP20 front face IEC 60529
    • Mechanical Robustness : vibrations contactor open 2 Gn, 5...300 Hz) || vibrations contactor closed 4 Gn, 5...300 Hz) || shocks contactor open 10 Gn for 11 ms) || shocks contactor closed 15 Gn for 11 ms)
    • Operating Altitude : 0...9842.52 ft (0...3000 m)
    • Fire Resistance : 850 °C IEC 60695-2-1
    • Width : 55 mm
    • Depth : 120 mm
    • Permissible Ambient Air Temperature Around The Device : -40-60 °C || 60-70 °C with derating
  • Contractual warranty
    • Warranty : 18 months
  • Offer Sustainability
    • Rohs Exemption Information : Yes
    • Mercury Free : Yes
    • Environmental Disclosure : ENVPEP1607010EN
    • Sustainable Offer Status : Green Premium product
    • Reach Regulation : Reference contains Substances of Very High Concern above the threshold
    • Weee : The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
    • China Rohs Regulation : Product out of China RoHS scope. Substance declaration for your information.
    • Circularity Profile : ENVEOLI1607010EN
    • Sustainable Packaging : Yes
    • Eu Rohs Directive : Compliant with Exemptions
    • Halogen Content Performance : Halogen free plastic parts & cables product
  • Complementary
    • Non-Overlap Time : 1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
    • Minimum Switching Current : 5 mA for signalling circuit
    • Power Dissipation Per Pole : 5.4 W AC-1 || 2.4 W AC-3 || 2.4 W AC-3e
    • Average Impedance : 1.5 mOhm - Ith 60 A 50 Hz for power circuit
    • Auxiliary Contact Composition : 1 NO + 1 NC
    • [Ith] Conventional Free Air Thermal Current : 60 A (at 60 °C) for power circuit || 10 A (at 60 °C) for signalling circuit
    • Control Circuit Voltage Limits : <= 0.1 Uc -40-70 °C drop-out AC/DC || 0.85...1.1 Uc -40-60 °C operational AC/DC || 1...1.1 Uc 60-70 °C operational AC/DC
    • Mounting Support : plate || rail
    • Control Circuit Type : AC/DC 50/60 Hz AC/DC electronic
    • Safety Reliability Level : B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
    • Pollution Degree : 3
    • Hold-In Power Consumption In W : 1.2-1.2 W 20 °C
    • Insulation Resistance : > 10 MOhm for signalling circuit
    • Rated Breaking Capacity : 800 A at 440 V for power circuit conforming to IEC 60947
    • Irms Rated Making Capacity : 800 A at 440 V for power circuit conforming to IEC 60947 || 140 A AC for signalling circuit conforming to IEC 60947-5-1 || 250 A DC for signalling circuit conforming to IEC 60947-5-1
    • Associated Fuse Rating : 80 A gG at <= 690 V coordination type 1 for power circuit || 80 A gG at <= 690 V coordination type 2 for power circuit || 10 A gG for signalling circuit conforming to IEC 60947-5-1
    • Inrush Power In Va : 18-18 VA 50/60 Hz (at 20 °C)
    • [Uimp] Rated Impulse Withstand Voltage : 6 kV IEC 60947
    • Pole Contact Composition : 3 NO
    • Connections - Terminals : power circuit: lugs-ring terminals - external diameter: 16.5 mm || control circuit: lugs-ring terminals - external diameter: 8 mm
    • Coil Technology : built-in bidirectional peak limiting
    • Operating Time : 55...65 ms closing || 20...80 ms opening
    • Minimum Switching Voltage : 17 V for signalling circuit
    • Maximum Operating Rate : 3600 cyc/h at 60 °C
    • Signalling Circuit Frequency : 25...400 Hz
    • Tightening Torque : control circuit 1.7 N.m lugs-ring terminals flat Ø 6 mm M3.5 || control circuit 1.7 N.m lugs-ring terminals Philips No 2 M3.5 || power circuit 6 N.m lugs-ring terminals hexagonal 10 mm M6 || power circuit 6 N.m lugs-ring terminals pozidriv No 2 M4 || control circuit 1.7 N.m lugs-ring terminals pozidriv No 2 M3.5
    • Electrical Durability : 2 Mcycles 35 A AC-3 <= 440 V || 0.7 Mcycles 60 A AC-1 <= 440 V || 2 Mcycles 35 A AC-3e <= 440 V
    • Mechanical Durability : 6 Mcycles
    • Inrush Power In W : 14-14 W 20 °C)
    • Auxiliary Contacts Type : mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
    • Compatibility Code : LC1D
    • Hold-In Power Consumption In Va : 1.8-1.8 VA 50/60 Hz (at 20 °C)
    • Overvoltage Category : III
    • Maximum Horse Power Rating : 3 hp at 115 V AC 60 Hz for 1 phase motors || 5 hp at 230/240 V AC 60 Hz for 1 phase motors || 10 hp at 200/208 V AC 60 Hz for 3 phase motors || 10 hp at 230/240 V AC 60 Hz for 3 phase motors || 30 hp at 460/480 V AC 60 Hz for 3 phase motors || 30 hp at 575/600 V AC 60 Hz for 3 phase motors
    • Motor Power Kw : 11 kW at 220...230 V AC 50 Hz (AC-3) || 18.5 kW at 380...400 V AC 50 Hz (AC-3) || 22 kW at 415 V AC 50 Hz (AC-3) || 22 kW at 440 V AC 50 Hz (AC-3) || 22 kW at 500 V AC 50 Hz (AC-3) || 30 kW at 660...690 V AC 50 Hz (AC-3) || 11 kW at 220...230 V AC 50 Hz (AC-3e) || 18.5 kW at 380...400 V AC 50 Hz (AC-3e) || 22 kW at 415 V AC 50 Hz (AC-3e) || 22 kW at 440 V AC 50 Hz (AC-3e) || 22 kW at 500 V AC 50 Hz (AC-3e) || 30 kW at 660...690 V AC 50 Hz (AC-3e)
    • [Ui] Rated Insulation Voltage : power circuit 690 V IEC 60947-4-1 || signalling circuit 690 V IEC 60947-1
    • [Icw] Rated Short-Time Withstand Current : 72 A 40 °C - 10 min for power circuit || 165 A 40 °C - 1 min for power circuit || 320 A 40 °C - 10 s for power circuit || 720 A 40 °C - 1 s for power circuit || 100 A - 1 s for signalling circuit || 120 A - 500 ms for signalling circuit || 140 A - 100 ms for signalling circuit
    • Heat Dissipation : 1.2-1.2 W at 50/60 Hz
    • Protective Cover : with
  • Specifications
    • Country of Origin : France
    • Width : 55 mm
    • Height : 122 mm
    • Weight : 0.992 kg
    • [Uc] Control Circuit Voltage : 100...250 V AC 50/60 Hz || 100...250 V DC
    • [Ue] Rated Operational Voltage : power circuit <= 690 V AC 25...400 Hz
    • Range Of Product : TeSys Deca
    • Contactor Application : resistive load || motor control
    • Product Or Component Type : contactor
    • Range : TeSys || TeSys Deca
    • Utilisation Category : AC-1 || AC-3 || AC-3e
    • [Ie] Rated Operational Current : 60 A (at <60 °C) at <= 440 V AC-1 for power circuit || 40 A (at <60 °C) at <= 440 V AC-3 for power circuit || 40 A (at <60 °C) at <= 440 V AC-3e for power circuit
    • Poles Description : 3P
    • Device Short Name : LC1D