Schneider Electric at Mayer

IEC contactor, TeSys D, nonreversing, 9A, 5HP at 480VAC, up to 100kA SCCR, 3 phase, 3 NO, 12VDC coil, open style

CONTACTOR 600VAC 9AMP IEC +OPT

SQDLC1D09JD LC1D09JD 785901207238
130.17 / EACH
  • Certifications: BV, CCC, CSA, DNV, GL, GOST, LROS (Lloyds Register Of Shipping), RINA, UKCA, UL
  • Contact Configuration: 1 NO + 1 NC
  • Contact Configuration: 3 NO
  • Depth: 95 mm
  • Height: 77 mm
  • Impedance: 2.5 MOhm - Ith 25 A 50 Hz Power Circuit
  • Net Weight: 0.48 kg
  • Standard: CSA C22.2 No 14, EN 60947-4-1, EN 60947-5-1, IEC 60947-4-1, IEC 60947-5-1, UL 508
  • Storage Temperature: -60-80 °C
  • Warranty Length: 18 mth
  • Width: 45 mm
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 9A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 20HP at 200-208VAC, 25HP at 240VAC, 60HP at 480VAC and 60HP at 600VAC three phase. Contactor is also rated for 7.5HP at 115VAC and 15HP at 240VAC single phase. When used with a 480VAC up to 35A circuit breaker, this contactor can have a SCCR up to 85kA. When used with up to a 600VAC 25A Class J or CC fuse, this contactor can have a SCCR up to 100kA. Contactor is supplied with a 12 VDC coil with transient suppressor module. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.15 inches tall, 1.77 inches wide and 3.39 inches deep. It weighs 0.71 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
  • Product Description
  • Specifications
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 9A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 20HP at 200-208VAC, 25HP at 240VAC, 60HP at 480VAC and 60HP at 600VAC three phase. Contactor is also rated for 7.5HP at 115VAC and 15HP at 240VAC single phase. When used with a 480VAC up to 35A circuit breaker, this contactor can have a SCCR up to 85kA. When used with up to a 600VAC 25A Class J or CC fuse, this contactor can have a SCCR up to 100kA. Contactor is supplied with a 12 VDC coil with transient suppressor module. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.15 inches tall, 1.77 inches wide and 3.39 inches deep. It weighs 0.71 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
  • Environment
    • Ambient Air Temperature For Storage : -60-80 °C
    • Net Weight : 0.48 kg
    • Flame Retardance : V1 conforming to UL 94
    • Ambient Air Temperature For Operation : -40-60 °C || 60-70 °C with derating
    • Mechanical Robustness : vibrations contactor open2 Gn, 5...300 Hz || vibrations contactor closed4 Gn, 5...300 Hz || shocks contactor open10 Gn for 11 ms || shocks contactor closed15 Gn for 11 ms
    • Width : 45 mm
    • Protective Treatment : TH IEC 60068-2-30
    • Operating Altitude : 0...9842.52 ft (0...3000 m)
    • Fire Resistance : 850 °C IEC 60695-2-1
    • Height : 77 mm
    • Pollution Degree : 3
    • Ip Degree Of Protection : IP20 front face IEC 60529
    • Depth : 95 mm
  • [Ith] Conventional Free Air Thermal Current : 25 A 60 °C power circuit || 10 A 60 °C signalling circuit
  • Mechanical Durability : 30 Mcycles
  • Operating Time : 53.55...72.45 ms closing || 16...24 ms opening
  • Contactor Application : resistive load || motor control
  • [Uc] Control Circuit Voltage : 12 V DC
  • Auxiliary Contact Composition : 1 NO + 1 NC
  • Power Dissipation Per Pole : 1.56 W AC-1 || 0.2 W AC-3
  • Connections - Terminals : power circuit screw clamp terminals 1 1-4 mm²flexible without cable end || power circuit screw clamp terminals 2 1-4 mm²flexible without cable end || power circuit screw clamp terminals 1 1-4 mm²flexible with cable end || power circuit screw clamp terminals 2 1-2.5 mm²flexible with cable end || power circuit screw clamp terminals 1 1-4 mm²solid without cable end || power circuit screw clamp terminals 2 1-4 mm²solid without cable end || control circuit screw clamp terminals 1 1-4 mm²flexible without cable end || control circuit screw clamp terminals 2 1-4 mm²flexible without cable end || control circuit screw clamp terminals 1 1-4 mm²flexible with cable end || control circuit screw clamp terminals 2 1-2.5 mm²flexible with cable end || control circuit screw clamp terminals 1 1-4 mm²solid without cable end || control circuit screw clamp terminals 2 1-4 mm²solid without cable end
  • Pole Contact Composition : 3 NO
  • [Ui] Rated Insulation Voltage : power circuit 690 V IEC 60947-4-1 || power circuit 600 V CSA || power circuit 600 V UL || signalling circuit 690 V IEC 60947-1 || signalling circuit 600 V CSA || signalling circuit 600 V UL
  • Standards : CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508
  • Product Certifications : LROS (Lloyds register of shipping) || CSA || GL || CCC || RINA || UL || BV || DNV || GOST || UKCA
  • [Uimp] Rated Impulse Withstand Voltage : 6 kV IEC 60947
  • Overvoltage Category : III
  • Utilisation Category : AC-3 || AC-1 || AC-4
  • Tightening Torque : power circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || power circuit 1.7 N.m screw clamp terminals Philips No 2 || control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2
  • Range : TeSys
  • Maximum Horse Power Rating : 1 hp 230/240 V at AC 50/60 Hz for 1 phase || 2 hp 200/208 V at AC 50/60 Hz for 3 phase || 2 hp 230/240 V at AC 50/60 Hz for 3 phase || 5 hp 460/480 V at AC 50/60 Hz for 3 phase || 7.5 hp 575/600 V at AC 50/60 Hz for 3 phase || 0.33 hp 115 V at AC 50/60 Hz for 1 phase
  • Device Short Name : LC1D
  • Protective Cover : with
  • Irms Rated Making Capacity : 250 A 440 V power circuit IEC 60947 || 140 A AC signalling circuit IEC 60947-5-1 || 250 A DC signalling circuit IEC 60947-5-1
  • Product Or Component Type : contactor
  • Associated Fuse Rating : 10 A gG signalling circuit IEC 60947-5-1 || 25 A gG <= 690 V type 1 power circuit || 20 A gG <= 690 V type 2 power circuit
  • Poles Description : 3P
  • Rated Breaking Capacity : 250 A 440 V power circuit IEC 60947
  • [Ie] Rated Operational Current : 9 A 60 °C) <= 440 V AC AC-3 power circuit || 25 A 60 °C) <= 440 V AC AC-1 power circuit
  • Control Circuit Type : DC standard
  • Safety Reliability Level : B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
  • Mounting Support : rail || plate
  • [Ue] Rated Operational Voltage : power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
  • Electrical Durability : 0.6 Mcycles 25 A AC-1 <= 440 V || 2 Mcycles 9 A AC-3 <= 440 V
  • Motor Power Kw : 2.2 kW 220...230 V AC 50/60 Hz AC-3) || 4 kW 380...400 V AC 50/60 Hz AC-3) || 4 kW 415...440 V AC 50/60 Hz AC-3) || 5.5 kW 500 V AC 50/60 Hz AC-3) || 5.5 kW 660...690 V AC 50/60 Hz AC-3) || 2.2 kW 400 V AC 50/60 Hz AC-4)
  • Maximum Operating Rate : 3600 cyc/h 60 °C
  • Average Impedance : 2.5 mOhm - Ith 25 A 50 Hz power circuit
  • Product Name : TeSys D
  • [Icw] Rated Short-Time Withstand Current : 105 A 40 °C - 10 s power circuit || 210 A 40 °C - 1 s power circuit || 30 A 40 °C - 10 min power circuit || 61 A 40 °C - 1 min power circuit || 100 A - 1 s signalling circuit || 120 A - 500 ms signalling circuit || 140 A - 100 ms signalling circuit
  • Offer Sustainability
    • Circularity Profile : ENVEOLI1102030EN
    • Reach Regulation : Free of Substances of Very High Concern above the threshold
    • California Proposition 65 : WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
    • Pvc Free : Yes
    • Sustainable Offer Status : Green Premium product
    • Environmental Disclosure : ENVPEP110230EN
    • China Rohs Regulation : Product out of China RoHS scope. Substance declaration for your information.
    • Eu Rohs Directive : Compliant
    • Weee : The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
    • Mercury Free : Yes
    • Rohs Exemption Information : Yes
  • Complementary
    • Hold-In Power Consumption In W : 5.4-5.4 W 20 °C
    • Inrush Power In W : 5.4-5.4 W 20 °C)
    • Minimum Switching Current : 5 mA signalling circuit
    • Coil Technology : built-in bidirectional peak limiting diode suppressor
    • Insulation Resistance : > 10 MOhm signalling circuit
    • Minimum Switching Voltage : 17 V signalling circuit
    • Auxiliary Contacts Type : mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
    • Non-Overlap Time : 1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
    • Signalling Circuit Frequency : 25...400 Hz
    • Time Constant : 28 ms
    • Control Circuit Voltage Limits : 0.1...0.25 Uc -40-70 °C drop-out DC || 0.7...1.25 Uc -40-60 °C operational DC || 1...1.25 Uc 60-70 °C operational DC
  • Contractual warranty
    • Warranty : 18 months