IEC contactor, TeSys D, nonreversing, 18A, 10HP at 480VAC, up to 100kA SCCR, 3 phase, 3 NO, 72VDC coil, open

IEC contactor, TeSys D, nonreversing, 18A, 10HP at 480VAC, up to 100kA SCCR, 3 phase, 3 NO, 72VDC coil, open

SQDLC1D18SD LC1D18SD 338911035562
0.00 / EA
  • Certifications: BV, CCC, CSA, DNV, GL, GOST, LROS (Lloyds Register Of Shipping), RINA, UKCA, UL
  • Contact Configuration: 1 NO + 1 NC
  • Contact Configuration: 3 NO
  • Depth: 95 mm
  • Height: 77 mm
  • Impedance: 2.5 MOhm - Ith 32 A 50 Hz Power Circuit
  • Net Weight: 0.49 kg
  • Standard: CSA C22.2 No 14, EN 60947-4-1, EN 60947-5-1, IEC 60947-4-1, IEC 60947-5-1, UL 508
  • Storage Temperature: -60-80 °C
  • Warranty Length: 18 mth
  • Width: 45 mm
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 18A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 5HP at 200-208VAC, 5HP at 240VAC, 10HP at 480VAC and 15HP at 600VAC three phase. Contactor is also rated for 1HP at 115VAC and 3HP at 240VAC single phase. When used with a 480VAC up to 60A circuit breaker, this contactor can have a SCCR up to 85kA. When used with up to a 600VAC 40A Class J or CC fuse, this contactor can have a SCCR up to 100kA. Contactor is supplied with a 72 VDC coil with transient suppressor module. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.03 inches tall, 1.77 inches wide and 3.74 inches deep. It weighs 1.08 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
  • Product Description
  • Specifications
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 18A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 5HP at 200-208VAC, 5HP at 240VAC, 10HP at 480VAC and 15HP at 600VAC three phase. Contactor is also rated for 1HP at 115VAC and 3HP at 240VAC single phase. When used with a 480VAC up to 60A circuit breaker, this contactor can have a SCCR up to 85kA. When used with up to a 600VAC 40A Class J or CC fuse, this contactor can have a SCCR up to 100kA. Contactor is supplied with a 72 VDC coil with transient suppressor module. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.03 inches tall, 1.77 inches wide and 3.74 inches deep. It weighs 1.08 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
  • Offer Sustainability
    • China Rohs Regulation : Product out of China RoHS scope. Substance declaration for your information.
    • Mercury Free : Yes
    • Weee : The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
    • Circularity Profile : ENVEOLI1102030EN
    • California Proposition 65 : WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
    • Sustainable Offer Status : Green Premium product
    • Rohs Exemption Information : Yes
    • Eu Rohs Directive : Compliant
    • Pvc Free : Yes
    • Reach Regulation : Free of Substances of Very High Concern above the threshold
    • Environmental Disclosure : ENVPEP110230EN
  • Environment
    • Operating Altitude : 0...9842.52 ft (0...3000 m)
    • Maximum Width : 45 mm
    • Ip Degree Of Protection : IP20 front face IEC 60529
    • Pollution Degree : 3
    • Protective Treatment : TH IEC 60068-2-30
    • Flame Retardance : V1 conforming to UL 94
    • Ambient Air Temperature For Operation : -40-60 °C || 60-70 °C with derating
    • Ambient Air Temperature For Storage : -60-80 °C
    • Mechanical Robustness : vibrations contactor open2 Gn, 5...300 Hz || vibrations contactor closed4 Gn, 5...300 Hz || shocks contactor open10 Gn for 11 ms || shocks contactor closed15 Gn for 11 ms
    • Maximum Height : 77 mm
    • Fire Resistance : 850 °C IEC 60695-2-1
    • Maximum Depth : 95 mm
    • Net Weight : 0.49 kg
  • Complementary
    • Coil Technology : with integral suppression device
    • Hold-In Power Consumption In W : 5.4-5.4 W 20 °C
    • Inrush Power In W : 5.4-5.4 W 20 °C)
    • Signalling Circuit Frequency : 25...400 Hz
    • Minimum Switching Current : 5 mA signalling circuit
    • Insulation Resistance : > 10 MOhm signalling circuit
    • Time Constant : 28 ms
    • Auxiliary Contacts Type : mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
    • Control Circuit Voltage Limits : 0.1...0.25 Uc -40-70 °C drop-out DC || 0.7...1.25 Uc -40-60 °C operational DC || 1...1.25 Uc 60-70 °C operational DC
    • Minimum Switching Voltage : 17 V signalling circuit
    • Non-Overlap Time : 1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
  • Rated Breaking Capacity : 300 A 440 V power circuit IEC 60947
  • Product Name : TeSys D
  • Average Impedance : 2.5 mOhm - Ith 32 A 50 Hz power circuit
  • Utilisation Category : AC-3 || AC-4 || AC-1
  • Mechanical Durability : 30 Mcycles
  • Auxiliary Contact Composition : 1 NO + 1 NC
  • Standards : CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508
  • Protective Cover : with
  • Product Certifications : GOST || LROS (Lloyds register of shipping) || UL || GL || CCC || BV || CSA || DNV || RINA || UKCA
  • Device Short Name : LC1D
  • Maximum Horse Power Rating : 1 hp 115 V at AC 50/60 Hz for 1 phase || 3 hp 230/240 V at AC 50/60 Hz for 1 phase || 5 hp 200/208 V at AC 50/60 Hz for 3 phase || 5 hp 230/240 V at AC 50/60 Hz for 3 phase || 10 hp 460/480 V at AC 50/60 Hz for 3 phase || 15 hp 575/600 V at AC 50/60 Hz for 3 phase
  • [Ie] Rated Operational Current : 18 A 60 °C) <= 440 V AC AC-3 power circuit || 32 A 60 °C) <= 440 V AC AC-1 power circuit
  • [Ith] Conventional Free Air Thermal Current : 10 A 60 °C signalling circuit || 32 A 60 °C power circuit
  • Overvoltage Category : III
  • Range : TeSys
  • Poles Description : 3P
  • Maximum Operating Rate : 3600 cyc/h 60 °C
  • Connections - Terminals : control circuit screw clamp terminals 1 1-4 mm²flexible without cable end || control circuit screw clamp terminals 2 1-4 mm²flexible without cable end || control circuit screw clamp terminals 1 1-4 mm²flexible with cable end || control circuit screw clamp terminals 2 1-2.5 mm²flexible with cable end || control circuit screw clamp terminals 1 1-4 mm²solid without cable end || control circuit screw clamp terminals 2 1-4 mm²solid without cable end || power circuit screw clamp terminals 1 1.5-6 mm²flexible without cable end || power circuit screw clamp terminals 2 1.5-6 mm²flexible without cable end || power circuit screw clamp terminals 1 1-6 mm²flexible with cable end || power circuit screw clamp terminals 2 1-4 mm²flexible with cable end || power circuit screw clamp terminals 1 1.5-6 mm²solid without cable end || power circuit screw clamp terminals 2 1.5-6 mm²solid without cable end
  • Associated Fuse Rating : 10 A gG signalling circuit IEC 60947-5-1 || 50 A gG <= 690 V type 1 power circuit || 35 A gG <= 690 V type 2 power circuit
  • [Uc] Control Circuit Voltage : 72 V DC
  • Safety Reliability Level : B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
  • Product Or Component Type : contactor
  • Mounting Support : plate || rail
  • [Uimp] Rated Impulse Withstand Voltage : 6 kV IEC 60947
  • Contactor Application : motor control || resistive load
  • Irms Rated Making Capacity : 140 A AC signalling circuit IEC 60947-5-1 || 250 A DC signalling circuit IEC 60947-5-1 || 300 A 440 V power circuit IEC 60947
  • Motor Power Kw : 4 kW 220...230 V AC 50/60 Hz AC-3) || 7.5 kW 380...400 V AC 50/60 Hz AC-3) || 9 kW 415...440 V AC 50/60 Hz AC-3) || 10 kW 500 V AC 50/60 Hz AC-3) || 10 kW 660...690 V AC 50/60 Hz AC-3) || 4 kW 400 V AC 50/60 Hz AC-4)
  • [Ue] Rated Operational Voltage : power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
  • [Ui] Rated Insulation Voltage : power circuit 690 V IEC 60947-4-1 || power circuit 600 V CSA || power circuit 600 V UL || signalling circuit 690 V IEC 60947-1 || signalling circuit 600 V CSA || signalling circuit 600 V UL
  • Control Circuit Type : DC standard
  • Tightening Torque : power circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || power circuit 1.7 N.m screw clamp terminals Philips No 2 || control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2
  • Electrical Durability : 1.65 Mcycles 18 A AC-3 <= 440 V || 1 Mcycles 32 A AC-1 <= 440 V
  • Power Dissipation Per Pole : 2.5 W AC-1 || 0.8 W AC-3
  • Pole Contact Composition : 3 NO
  • [Icw] Rated Short-Time Withstand Current : 145 A 40 °C - 10 s power circuit || 240 A 40 °C - 1 s power circuit || 40 A 40 °C - 10 min power circuit || 84 A 40 °C - 1 min power circuit || 100 A - 1 s signalling circuit || 120 A - 500 ms signalling circuit || 140 A - 100 ms signalling circuit
  • Operating Time : 53.55...72.45 ms closing || 16...24 ms opening
  • Contractual warranty
    • Warranty : 18 months