IEC contactor, TeSys D, nonreversing, 18A, 10HP at 480VAC, up to 100kA SCCR, 3 phase, 3 NO, 380VAC 50/60Hz coil, open

CONTACTOR 600VAC 18AMP IEC +OP

SQDLC1D18Q7 LC1D18Q7 785901459835
148.77 / EACH
  • Certifications: BV, CCC, CSA, DNV, GL, GOST, LROS (Lloyds Register Of Shipping), RINA, UKCA, UL
  • Contact Configuration: 1 NO + 1 NC, 3 NO
  • Depth: 86 mm
  • Height: 77 mm
  • Impedance: 2.5 MOhm - Ith 32 A 50 Hz Power Circuit
  • Net Weight: 0.33 kg
  • Standard: CSA C22.2 No 14, EN 60947-4-1, EN 60947-5-1, IEC 60335-1, IEC 60947-4-1, IEC 60947-5-1, UL 508
  • Storage Temperature: -60-80 °C
  • Warranty Length: 18 mth
  • Width: 45 mm
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 18A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 5HP at 200-208VAC, 5HP at 240VAC, 10HP at 480VAC and 15HP at 600VAC three phase. Contactor is also rated for 1HP at 115VAC and 3HP at 240VAC single phase. When used with a 480VAC up to 60A circuit breaker, this contactor can have a SCCR up to 85kA. When used with up to a 600VAC 40A Class J or CC fuse, this contactor can have a SCCR up to 100kA. Contactor is supplied with a 380 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.03 inches tall, 1.77 inches wide and 3.39 inches deep. It weighs 0.73 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
  • Product Description
  • Specifications
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 18A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 5HP at 200-208VAC, 5HP at 240VAC, 10HP at 480VAC and 15HP at 600VAC three phase. Contactor is also rated for 1HP at 115VAC and 3HP at 240VAC single phase. When used with a 480VAC up to 60A circuit breaker, this contactor can have a SCCR up to 85kA. When used with up to a 600VAC 40A Class J or CC fuse, this contactor can have a SCCR up to 100kA. Contactor is supplied with a 380 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.03 inches tall, 1.77 inches wide and 3.39 inches deep. It weighs 0.73 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
  • Maximum Operating Rate : 3600 cyc/h 60 °C
  • Product Certifications : RINA || LROS (Lloyds register of shipping) || GL || CSA || BV || GOST || DNV || CCC || UL || UKCA
  • Motor Power Kw : 4 kW 220...230 V AC 50/60 Hz AC-3) || 7.5 kW 380...400 V AC 50/60 Hz AC-3) || 9 kW 415...440 V AC 50/60 Hz AC-3) || 10 kW 500 V AC 50/60 Hz AC-3) || 10 kW 660...690 V AC 50/60 Hz AC-3) || 4 kW 400 V AC 50/60 Hz AC-4)
  • Connections - Terminals : control circuit screw clamp terminals 1 1-4 mm²flexible without cable end || control circuit screw clamp terminals 2 1-4 mm²flexible without cable end || control circuit screw clamp terminals 1 1-4 mm²flexible with cable end || control circuit screw clamp terminals 2 1-2.5 mm²flexible with cable end || control circuit screw clamp terminals 1 1-4 mm²solid without cable end || control circuit screw clamp terminals 2 1-4 mm²solid without cable end || power circuit screw clamp terminals 1 1.5-6 mm²flexible without cable end || power circuit screw clamp terminals 2 1.5-6 mm²flexible without cable end || power circuit screw clamp terminals 1 1-6 mm²flexible with cable end || power circuit screw clamp terminals 2 1-4 mm²flexible with cable end || power circuit screw clamp terminals 1 1.5-6 mm²solid without cable end || power circuit screw clamp terminals 2 1.5-6 mm²solid without cable end
  • Safety Reliability Level : B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
  • Auxiliary Contact Composition : 1 NO + 1 NC
  • Product Name : TeSys D || TeSys Deca
  • Rated Breaking Capacity : 300 A 440 V power circuit IEC 60947
  • Average Impedance : 2.5 mOhm - Ith 32 A 50 Hz power circuit
  • Mechanical Durability : 15 Mcycles
  • Standards : CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508 || IEC 60335-1
  • Protective Cover : with
  • Associated Fuse Rating : 10 A gG signalling circuit IEC 60947-5-1 || 50 A gG <= 690 V type 1 power circuit || 35 A gG <= 690 V type 2 power circuit
  • [Ui] Rated Insulation Voltage : power circuit 690 V IEC 60947-4-1 || power circuit 600 V CSA || power circuit 600 V UL || signalling circuit 690 V IEC 60947-1 || signalling circuit 600 V CSA || signalling circuit 600 V UL
  • [Icw] Rated Short-Time Withstand Current : 145 A 40 °C - 10 s power circuit || 240 A 40 °C - 1 s power circuit || 40 A 40 °C - 10 min power circuit || 84 A 40 °C - 1 min power circuit || 100 A - 1 s signalling circuit || 120 A - 500 ms signalling circuit || 140 A - 100 ms signalling circuit
  • Contactor Application : resistive load || motor control
  • [Uc] Control Circuit Voltage : 380 V AC 50/60 Hz
  • Pole Contact Composition : 3 NO
  • [Ue] Rated Operational Voltage : power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
  • Utilisation Category : AC-3 || AC-4 || AC-1
  • Overvoltage Category : III
  • Mounting Support : rail || plate
  • Irms Rated Making Capacity : 140 A AC signalling circuit IEC 60947-5-1 || 250 A DC signalling circuit IEC 60947-5-1 || 300 A 440 V power circuit IEC 60947
  • Tightening Torque : power circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || power circuit 1.7 N.m screw clamp terminals Philips No 2 || control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || control circuit 1.7 N.m screw clamp terminals pozidriv No 2 || power circuit 2.5 N.m screw clamp terminals pozidriv No 2
  • Power Dissipation Per Pole : 2.5 W AC-1 || 0.8 W AC-3
  • Product Or Component Type : contactor
  • Range : TeSys || TeSys Deca
  • Electrical Durability : 1.65 Mcycles 18 A AC-3 <= 440 V || 1 Mcycles 32 A AC-1 <= 440 V
  • [Ith] Conventional Free Air Thermal Current : 10 A 60 °C signalling circuit || 32 A 60 °C power circuit
  • Poles Description : 3P
  • Device Short Name : LC1D
  • Operating Time : 12...22 ms closing || 4...19 ms opening
  • [Ie] Rated Operational Current : 18 A 60 °C) <= 440 V AC AC-3 power circuit || 32 A 60 °C) <= 440 V AC AC-1 power circuit
  • Control Circuit Type : AC 50/60 Hz
  • [Uimp] Rated Impulse Withstand Voltage : 6 kV IEC 60947
  • Maximum Horse Power Rating : 1 hp 115 V at AC 50/60 Hz for 1 phase || 3 hp 230/240 V at AC 50/60 Hz for 1 phase || 5 hp 200/208 V at AC 50/60 Hz for 3 phase || 5 hp 230/240 V at AC 50/60 Hz for 3 phase || 10 hp 460/480 V at AC 50/60 Hz for 3 phase || 15 hp 575/600 V at AC 50/60 Hz for 3 phase
  • Complementary
    • Control Circuit Voltage Limits : 0.3...0.6 Uc -40-70 °C drop-out AC 50/60 Hz || 0.8...1.1 Uc -40-60 °C operational AC 50 Hz || 0.85...1.1 Uc -40-60 °C operational AC 60 Hz || 1...1.1 Uc 60-70 °C operational AC 50/60 Hz
    • Minimum Switching Current : 5 mA signalling circuit
    • Hold-In Power Consumption In Va : 7.5-7.5 VA 60 Hz 0.3 20 °C) || 7-7 VA 50 Hz 0.3 20 °C)
    • Non-Overlap Time : 1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
    • Coil Technology : without built-in suppressor module
    • Auxiliary Contacts Type : mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
    • Signalling Circuit Frequency : 25...400 Hz
    • Minimum Switching Voltage : 17 V signalling circuit
    • Inrush Power In Va : 70-70 VA 60 Hz 0.75 20 °C) || 70-70 VA 50 Hz 0.75 20 °C)
    • Insulation Resistance : > 10 MOhm signalling circuit
    • Heat Dissipation : 2-3 W 50/60 Hz
  • Offer Sustainability
    • Environmental Disclosure : ENVPEP1501004EN
    • Mercury Free : Yes
    • Eu Rohs Directive : Compliant
    • Sustainable Offer Status : Green Premium product
    • China Rohs Regulation : Pro-active China RoHS declaration (out of China RoHS legal scope)
    • Reach Free Of Svhc : Yes
    • Reach Regulation : Free of Substances of Very High Concern above the threshold
    • Weee : The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
    • Circularity Profile : ENVEOLI1501004EN
    • California Proposition 65 : WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
    • Rohs Exemption Information : Yes
    • Toxic Heavy Metal Free : Yes
    • Pvc Free : Yes
  • Environment
    • Pollution Degree : 3
    • Flame Retardance : V1 conforming to UL 94
    • Protective Treatment : TH IEC 60068-2-30
    • Depth : 86 mm
    • Width : 45 mm
    • Fire Resistance : 850 °C IEC 60695-2-1
    • Mechanical Robustness : vibrations contactor open2 Gn, 5...300 Hz || vibrations contactor closed4 Gn, 5...300 Hz || shocks contactor open10 Gn for 11 ms || shocks contactor closed15 Gn for 11 ms
    • Ambient Air Temperature For Operation : -40-60 °C || 60-70 °C with derating
    • Ambient Air Temperature For Storage : -60-80 °C
    • Net Weight : 0.33 kg
    • Height : 77 mm
    • Operating Altitude : 0...9842.52 ft (0...3000 m)
    • Ip Degree Of Protection : IP20 front face IEC 60529
  • Contractual warranty
    • Warranty : 18 months