IEC contactor, TeSys D, nonreversing, 18A, 10HP at 480VAC, up to 100kA SCCR, 3 phase, 3 NO, 36VDC coil, open

IEC contactor, TeSys D, nonreversing, 18A, 10HP at 480VAC, up to 100kA SCCR, 3 phase, 3 NO, 36VDC coil, open

SQDLC1D18CD LC1D18CD 785901584506
185.95 / EACH
  • Certifications: BV, CCC, CSA, DNV, GL, GOST, LROS (Lloyds Register Of Shipping), RINA, UKCA, UL
  • Contact Configuration: 1 NO + 1 NC
  • Contact Configuration: 3 NO
  • Depth: 95 mm
  • Height: 77 mm
  • Impedance: 2.5 MOhm - Ith 32 A 50 Hz Power Circuit
  • Net Weight: 0.49 kg
  • Standard: CSA C22.2 No 14, EN 60947-4-1, EN 60947-5-1, IEC 60947-4-1, IEC 60947-5-1, UL 508
  • Storage Temperature: -60-80 °C
  • Warranty Length: 18 mth
  • Width: 45 mm
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 18A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 5HP at 200-208VAC, 5HP at 240VAC, 10HP at 480VAC and 15HP at 600VAC three phase. Contactor is also rated for 1HP at 115VAC and 3HP at 240VAC single phase. When used with a 480VAC up to 60A circuit breaker, this contactor can have a SCCR up to 85kA. When used with up to a 600VAC 40A Class J or CC fuse, this contactor can have a SCCR up to 100kA. Contactor is supplied with a 36 VDC coil with transient suppressor module. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.03 inches tall, 1.77 inches wide and 3.74 inches deep. It weighs 1.08 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
  • Product Description
  • Specifications
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 18A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 5HP at 200-208VAC, 5HP at 240VAC, 10HP at 480VAC and 15HP at 600VAC three phase. Contactor is also rated for 1HP at 115VAC and 3HP at 240VAC single phase. When used with a 480VAC up to 60A circuit breaker, this contactor can have a SCCR up to 85kA. When used with up to a 600VAC 40A Class J or CC fuse, this contactor can have a SCCR up to 100kA. Contactor is supplied with a 36 VDC coil with transient suppressor module. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.03 inches tall, 1.77 inches wide and 3.74 inches deep. It weighs 1.08 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
  • Environment
    • Ambient Air Temperature For Storage : -60-80 °C
    • Ambient Air Temperature For Operation : -40-60 °C || 60-70 °C with derating
    • Maximum Height : 77 mm
    • Operating Altitude : 0...9842.52 ft (0...3000 m)
    • Protective Treatment : TH IEC 60068-2-30
    • Ip Degree Of Protection : IP20 front face IEC 60529
    • Maximum Width : 45 mm
    • Pollution Degree : 3
    • Fire Resistance : 850 °C IEC 60695-2-1
    • Net Weight : 0.49 kg
    • Maximum Depth : 95 mm
    • Mechanical Robustness : vibrations contactor open2 Gn, 5...300 Hz || vibrations contactor closed4 Gn, 5...300 Hz || shocks contactor open10 Gn for 11 ms || shocks contactor closed15 Gn for 11 ms
    • Flame Retardance : V1 conforming to UL 94
  • Offer Sustainability
    • Eu Rohs Directive : Compliant
    • Circularity Profile : ENVEOLI1102030EN
    • Pvc Free : Yes
    • China Rohs Regulation : Product out of China RoHS scope. Substance declaration for your information.
    • Rohs Exemption Information : Yes
    • Reach Regulation : Free of Substances of Very High Concern above the threshold
    • Environmental Disclosure : ENVPEP110230EN
    • Mercury Free : Yes
    • Weee : The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
    • Sustainable Offer Status : Green Premium product
    • California Proposition 65 : WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
  • Contractual warranty
    • Warranty : 18 months
  • Complementary
    • Control Circuit Voltage Limits : 0.1...0.25 Uc -40-70 °C drop-out DC || 0.7...1.25 Uc -40-60 °C operational DC || 1...1.25 Uc 60-70 °C operational DC
    • Auxiliary Contacts Type : mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
    • Non-Overlap Time : 1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
    • Coil Technology : with integral suppression device
    • Signalling Circuit Frequency : 25...400 Hz
    • Time Constant : 28 ms
    • Inrush Power In W : 5.4-5.4 W 20 °C)
    • Insulation Resistance : > 10 MOhm signalling circuit
    • Minimum Switching Voltage : 17 V signalling circuit
    • Minimum Switching Current : 5 mA signalling circuit
    • Hold-In Power Consumption In W : 5.4-5.4 W 20 °C
  • Product Name : TeSys D
  • Device Short Name : LC1D
  • [Icw] Rated Short-Time Withstand Current : 145 A 40 °C - 10 s power circuit || 240 A 40 °C - 1 s power circuit || 40 A 40 °C - 10 min power circuit || 84 A 40 °C - 1 min power circuit || 100 A - 1 s signalling circuit || 120 A - 500 ms signalling circuit || 140 A - 100 ms signalling circuit
  • [Ie] Rated Operational Current : 18 A 60 °C) <= 440 V AC AC-3 power circuit || 32 A 60 °C) <= 440 V AC AC-1 power circuit
  • Poles Description : 3P
  • Mechanical Durability : 30 Mcycles
  • Utilisation Category : AC-3 || AC-1 || AC-4
  • [Ue] Rated Operational Voltage : power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
  • [Ith] Conventional Free Air Thermal Current : 10 A 60 °C signalling circuit || 32 A 60 °C power circuit
  • Mounting Support : rail || plate
  • Power Dissipation Per Pole : 2.5 W AC-1 || 0.8 W AC-3
  • [Uimp] Rated Impulse Withstand Voltage : 6 kV IEC 60947
  • Motor Power Kw : 4 kW 220...230 V AC 50/60 Hz AC-3) || 7.5 kW 380...400 V AC 50/60 Hz AC-3) || 9 kW 415...440 V AC 50/60 Hz AC-3) || 10 kW 500 V AC 50/60 Hz AC-3) || 10 kW 660...690 V AC 50/60 Hz AC-3) || 4 kW 400 V AC 50/60 Hz AC-4)
  • Associated Fuse Rating : 10 A gG signalling circuit IEC 60947-5-1 || 50 A gG <= 690 V type 1 power circuit || 35 A gG <= 690 V type 2 power circuit
  • Electrical Durability : 1.65 Mcycles 18 A AC-3 <= 440 V || 1 Mcycles 32 A AC-1 <= 440 V
  • Range : TeSys
  • Irms Rated Making Capacity : 140 A AC signalling circuit IEC 60947-5-1 || 250 A DC signalling circuit IEC 60947-5-1 || 300 A 440 V power circuit IEC 60947
  • Tightening Torque : power circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || power circuit 1.7 N.m screw clamp terminals Philips No 2 || control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2
  • Maximum Operating Rate : 3600 cyc/h 60 °C
  • Product Or Component Type : contactor
  • Overvoltage Category : III
  • Control Circuit Type : DC standard
  • Standards : CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508
  • Contactor Application : resistive load || motor control
  • [Uc] Control Circuit Voltage : 36 V DC
  • Maximum Horse Power Rating : 1 hp 115 V at AC 50/60 Hz for 1 phase || 3 hp 230/240 V at AC 50/60 Hz for 1 phase || 5 hp 200/208 V at AC 50/60 Hz for 3 phase || 5 hp 230/240 V at AC 50/60 Hz for 3 phase || 10 hp 460/480 V at AC 50/60 Hz for 3 phase || 15 hp 575/600 V at AC 50/60 Hz for 3 phase
  • Product Certifications : GL || GOST || UL || BV || DNV || CSA || RINA || LROS (Lloyds register of shipping) || CCC || UKCA
  • Auxiliary Contact Composition : 1 NO + 1 NC
  • Safety Reliability Level : B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
  • Pole Contact Composition : 3 NO
  • Rated Breaking Capacity : 300 A 440 V power circuit IEC 60947
  • Connections - Terminals : control circuit screw clamp terminals 1 1-4 mm²flexible without cable end || control circuit screw clamp terminals 2 1-4 mm²flexible without cable end || control circuit screw clamp terminals 1 1-4 mm²flexible with cable end || control circuit screw clamp terminals 2 1-2.5 mm²flexible with cable end || control circuit screw clamp terminals 1 1-4 mm²solid without cable end || control circuit screw clamp terminals 2 1-4 mm²solid without cable end || power circuit screw clamp terminals 1 1.5-6 mm²flexible without cable end || power circuit screw clamp terminals 2 1.5-6 mm²flexible without cable end || power circuit screw clamp terminals 1 1-6 mm²flexible with cable end || power circuit screw clamp terminals 2 1-4 mm²flexible with cable end || power circuit screw clamp terminals 1 1.5-6 mm²solid without cable end || power circuit screw clamp terminals 2 1.5-6 mm²solid without cable end
  • Operating Time : 53.55...72.45 ms closing || 16...24 ms opening
  • Protective Cover : with
  • Average Impedance : 2.5 mOhm - Ith 32 A 50 Hz power circuit
  • [Ui] Rated Insulation Voltage : power circuit 690 V IEC 60947-4-1 || power circuit 600 V CSA || power circuit 600 V UL || signalling circuit 690 V IEC 60947-1 || signalling circuit 600 V CSA || signalling circuit 600 V UL