IEC contactor, TeSys D, nonreversing, 18A, 10HP at 480VAC, 3 phase, 3 pole, 3 NO, 120VAC 50/60Hz coil, open style

IEC contactor, TeSys D, nonreversing, 18A, 10HP at 480VAC, 3 phase, 3 pole, 3 NO, 120VAC 50/60Hz coil, open style

SQDLC1D18G7 LC1D18G7 785901207108
138.14 / EACH
  • Certifications: BV, CCC, CSA, DNV, GL, GOST, LROS (Lloyds Register Of Shipping), RINA, UL
  • Contact Configuration: 1 NO + 1 NC
  • Country of Origin: Indonesia
  • Depth: 3.39 in, 86 mm
  • Height: 3.03 in, 77 mm
  • Impedance: 2.5 mOhm - Ith 32 A 50 Hz Power Circuit
  • Operating Cycles: 3600 cyc/h 60 °C
  • Standard: CSA C22.2 No 14, EN 60947-4-1, EN 60947-5-1, IEC 60947-4-1, IEC 60947-5-1, UL 508
  • Voltage: 300 V, 690 V
  • Warranty Length: 18 mth
  • Weight: 0.33 kg, 0.73 lb
  • Width: 1.77 in, 45 mm
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for any type of application. They can be used to create motor starters for almost any type of application. TeSys D contactors offer quick simple setup, while maintaining a compact size. Contactors have both Horsepower and Kw motor rating for international acceptance. An extennsive line of accessories makes it easy to meet the requirements of most applications. These contactors have UL, CSA, GOST, RINA, BV, CCC, DNV, GL, LROS certifications. Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh).
  • Product Description
  • Specifications
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for any type of application. They can be used to create motor starters for almost any type of application. TeSys D contactors offer quick simple setup, while maintaining a compact size. Contactors have both Horsepower and Kw motor rating for international acceptance. An extennsive line of accessories makes it easy to meet the requirements of most applications. These contactors have UL, CSA, GOST, RINA, BV, CCC, DNV, GL, LROS certifications. Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh).
  • Main
    • Connections - Terminals : Control circuit screw clamp terminals 1 0.00…0.01 in² (1…4 mm²)flexible without cable end || Control circuit screw clamp terminals 2 0.00…0.01 in² (1…4 mm²)flexible without cable end || Control circuit screw clamp terminals 1 0.00…0.01 in² (1…4 mm²)flexible with cable end || Control circuit screw clamp terminals 2 0.00…0.00 in² (1…2.5 mm²)flexible with cable end || Control circuit screw clamp terminals 1 0.00…0.01 in² (1…4 mm²)solid without cable end || Control circuit screw clamp terminals 2 0.00…0.01 in² (1…4 mm²)solid without cable end || Power circuit screw clamp terminals 1 0.00…0.01 in² (1.5…6 mm²)flexible without cable end || Power circuit screw clamp terminals 2 0.00…0.01 in² (1.5…6 mm²)flexible without cable end || Power circuit screw clamp terminals 1 0.00…0.01 in² (1…6 mm²)flexible with cable end || Power circuit screw clamp terminals 2 0.00…0.01 in² (1…4 mm²)flexible with cable end || Power circuit screw clamp terminals 1 0.00…0.01 in² (1.5…6 mm²)solid without cable end || Power circuit screw clamp terminals 2 0.00…0.01 in² (1.5…6 mm²)solid without cable end
    • Motor Power Hp (Ul / Csa) : 1 hp 115 V at AC 50/60 Hz for 1 phase || 3 hp 230/240 V at AC 50/60 Hz for 1 phase || 5 hp 200/208 V at AC 50/60 Hz for 3 phase || 5 hp 230/240 V at AC 50/60 Hz for 3 phase || 10 hp 460/480 V at AC 50/60 Hz for 3 phase || 15 hp 575/600 V at AC 50/60 Hz for 3 phase
    • Ue Rated Operational Voltage : Power circuit: <= 690 V AC 25...400 Hz || Power circuit <= 300 V DC
    • Power Pole Contact Composition : 3 NO
    • Motor Power kW : 4 kW 220...230 V AC 50/60 Hz AC-3) || 7.5 kW 380...400 V AC 50/60 Hz AC-3) || 9 kW 415...440 V AC 50/60 Hz AC-3) || 10 kW 500 V AC 50/60 Hz AC-3) || 10 kW 660...690 V AC 50/60 Hz AC-3) || 4 kW 400 V AC 50/60 Hz AC-4)
    • Operating Time : 12...22 ms closing || 4...19 ms opening
    • Poles Description : 3P
    • Product Or Component Type : Contactor
    • Ith Cnvtl Free Air Therm Crrt : 10 A 140 °F (60 °C) signalling circuit || 32 A 140 °F (60 °C) power circuit
    • Operating Rate : 3600 cyc/h 60 °C
    • Irms Rated Making Capacity : 140 A AC signalling circuit IEC 60947-5-1 || 250 A DC signalling circuit IEC 60947-5-1 || 300 A 440 V power circuit IEC 60947
    • Contactor Application : Resistive load || Motor control
    • Mechanical Durability : 15 Mcycles
    • Tightening Torque : Power circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals flat Ø 6 mm || Power circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals Philips No 2 || Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals flat Ø 6 mm || Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals Philips No 2
    • Safety Reliability Level : B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
    • Ui Rated Insulation Voltage : Power circuit 690 V IEC 60947-4-1 || Power circuit 600 V CSA || Power circuit 600 V UL || Signalling circuit 690 V IEC 60947-1 || Signalling circuit 600 V CSA || Signalling circuit 600 V UL
    • Control Circuit Type : AC at 50/60 Hz
    • Ie Rated Operational Current : 18 A 140 °F (60 °C)) <= 440 V AC AC-3 power circuit || 32 A 140 °F (60 °C)) <= 440 V AC AC-1 power circuit
    • Uimp Rated Imp Wstd Voltage : 6 kV IEC 60947
    • Overvoltage Category : III
    • Associated Fuse Rating : 10 A gG signalling circuit IEC 60947-5-1 || 50 A gG <= 690 V type 1 power circuit || 35 A gG <= 690 V type 2 power circuit
    • Electrical Durability : 1.65 Mcycles 18 A AC-3 <= 440 V || 1 Mcycles 32 A AC-1 <= 440 V
    • Standards : CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508
    • Uc Control Circuit Voltage : 120 V AC 50/60 Hz
    • Mounting Support : Plate || Rail
    • Rated Breaking Capacity : 300 A 440 V power circuit IEC 60947
    • Range : TeSys
    • Device Short Name : LC1D
    • Average Impedance : 2.5 mOhm - Ith 32 A 50 Hz power circuit
    • Icw Rated Short-Time Wstd Crrt : 145 A 104 °F (40 °C) - 10 s power circuit || 240 A 104 °F (40 °C) - 1 s power circuit || 40 A 104 °F (40 °C) - 10 min power circuit || 84 A 104 °F (40 °C) - 1 min power circuit || 100 A - 1 s signalling circuit || 120 A - 500 ms signalling circuit || 140 A - 100 ms signalling circuit
    • Auxiliary Contact Composition : 1 NO + 1 NC
    • Utilisation Category : AC-1 || AC-4 || AC-3
    • Product Certifications : BV || GL || CCC || CSA || RINA || DNV || GOST || LROS (Lloyds register of shipping) || UL
    • Product Name : TeSys D
    • Power Dissipation Per Pole : 2.5 W AC-1 || 0.8 W AC-3
    • Front Cover : With
  • Ordering And Shipping Details
    • Category : 22354 - CTR,TESYS D,OPEN,9-38A AC
    • Discount Schedule : I12
    • Returnability : Yes
    • GTIN : 00785901207108
    • Country Of Origin : ID
    • Nbr. Of Units In Pkg. : 1
  • Offer Sustainability
    • California Proposition 65 : WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
    • Pvc Free : Yes
    • REACh Free Of SVHC : Yes
    • EU RoHs Directive : Compliant
    • Toxic Heavy Metal Free : Yes
    • Mercury Free : Yes
    • Green Premium Status : Green Premium product
    • WEEE : The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
  • Contractual Warranty
    • Warranty : 18 months
  • Environment
    • Mechanical Robustness : Vibrations contactor open2 Gn, 5...300 Hz || Vibrations contactor closed4 Gn, 5...300 Hz || Shocks contactor open10 Gn for 11 ms || Shocks contactor closed15 Gn for 11 ms
    • Depth : 3.39 in (86 mm)
    • Operating Altitude : 0...9842.52 ft (0...3000 m)
    • Protective Treatment : TH IEC 60068-2-30
    • Height : 3.03 in (77 mm)
    • Width : 1.77 in (45 mm)
    • Ambient Air Temp For Op : -40…140 °F (-40…60 °C) || 140…158 °F (60…70 °C) with derating
    • Fire Resistance : 1562 °F (850 °C) IEC 60695-2-1
    • Product Weight : 0.73 lb(US) (0.33 kg)
    • IP Degree Of Protection : IP20 front face IEC 60529
    • Ambient Air Temp For Storage : -76…176 °F (-60…80 °C)
    • Pollution Degree : 3
    • Flame Retardance : V1 conforming to UL 94
  • Complementary
    • Signalling Circuit Frequency : 25...400 Hz
    • Non-Overlap Time : 1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
    • Insulation Resistance : > 10 MOhm for signalling circuit
    • Coil Technology : Without built-in suppressor module
    • Heat Dissipation : 2…3 W 50/60 Hz
    • Inrush Power In VA : 70 VA 60 Hz 0.75 68 °F (20 °C)) || 70 VA 50 Hz 0.75 68 °F (20 °C))
    • Ctrl Circuit Voltage Limits : 0.3...0.6 Uc -40…158 °F (-40…70 °C) drop-out AC 50/60 Hz || 0.8...1.1 Uc -40…140 °F (-40…60 °C) operational AC 50 Hz || 0.85...1.1 Uc -40…140 °F (-40…60 °C) operational AC 60 Hz || 1...1.1 Uc 140…158 °F (60…70 °C) operational AC 50/60 Hz
    • Minimum Switching Voltage : 17 V signalling circuit
    • Auxiliary Contacts Type : type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1 || Mirror contact 1 NC IEC 60947-4-1
    • Hold-In Power Consumption Va : 7.5 VA 60 Hz 0.3 68 °F (20 °C)) || 7 VA 50 Hz 0.3 68 °F (20 °C))
    • Minimum Switching Current : 5 mA signalling circuit