IEC contactor, TeSys Deca, nonreversing, 18A, 10HP at 480VAC, up to 100kA SCCR, 3 phase, 3 NO, 110VAC 50/60Hz coil, bulk

CONTACTOR 575VAC 18AMP IEC +OP

SQDLC1D18F7TQ LC1D18F7TQ 3389110123814
187.63 / EA
http://schema.org/OutOfStock
  • Depth: 86 mm
  • Warranty Length: 18 mth
TeSys Deca contactor, 3 poles (3NO), for motor control applications up to 18A/690V AC-3/3e (7.5kW@400V). They can be used to create motor starters for almost any type of application. It provides a 110V 50/60Hz AC coil, 1NO+1NC built-in auxiliary contacts (NC mirror certified), connection by screw clamp terminals. For operating rates until 3600 cycles/hour and environments until 60°C, it procures high reliability and durability. Compact (45mm width), DIN-rail mounting or screw fixing. Pack of 10 units. Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine). When used with a 480VAC up to 60A circuit breaker, this contactor can have a SCCR up to 85kA. When used with up to a 600VAC 40A Class J or CC fuse, this contactor can have a SCCR up to 100kA. Contactor is supplied with a 110 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.03 inches tall, 1.77 inches wide and 3.39 inches deep. It weighs 0.73 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards.
QTY
  • Product Description
  • Features
  • Specifications
TeSys Deca contactor, 3 poles (3NO), for motor control applications up to 18A/690V AC-3/3e (7.5kW@400V). They can be used to create motor starters for almost any type of application. It provides a 110V 50/60Hz AC coil, 1NO+1NC built-in auxiliary contacts (NC mirror certified), connection by screw clamp terminals. For operating rates until 3600 cycles/hour and environments until 60°C, it procures high reliability and durability. Compact (45mm width), DIN-rail mounting or screw fixing. Pack of 10 units. Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine). When used with a 480VAC up to 60A circuit breaker, this contactor can have a SCCR up to 85kA. When used with up to a 600VAC 40A Class J or CC fuse, this contactor can have a SCCR up to 100kA. Contactor is supplied with a 110 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.03 inches tall, 1.77 inches wide and 3.39 inches deep. It weighs 0.73 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards.
  • Prop 65
    • WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
  • Complementary Attributes
    • Control Circuit Voltage Limits : 0.3...0.6 Uc (60-60 °C):drop-out AC 50/60 Hz, 0.8...1.1 Uc (60-60 °C):operational AC 50 Hz0.85...1.1 Uc (60-60 °C):operational AC 60 Hz
    • Maximum Horse Power Rating : 10 hp at 460/480 V AC 50/60 Hz for 3 phase motors conforming to UL15 hp at 575/600 V AC 50/60 Hz for 3 phase motors conforming to UL5 hp at 200/208 V AC 50/60 Hz for 3 phase motors conforming to UL3 hp at 230...240 V AC 50/60 Hz for 1 phase motors conforming to UL5 hp at 230...240 V AC 50/60 Hz for 3 phase motors conforming to CSA5 hp at 230...240 V AC 50/60 Hz for 3 phase motors conforming to UL, 1 hp at 115 V AC 50/60 Hz for 1 phase motors conforming to UL, 1 hp at 115 V AC 50/60 Hz for 1 phase motors conforming to CSA, 10 hp at 460/480 V AC 50/60 Hz for 3 phase motors conforming to CSA15 hp at 575/600 V AC 50/60 Hz for 3 phase motors conforming to CSA5 hp at 200/208 V AC 50/60 Hz for 3 phase motors conforming to CSA3 hp at 230...240 V AC 50/60 Hz for 1 phase motors conforming to CSA
    • Control Circuit Type : AC 50/60 Hz
    • Irms Rated Making Capacity : 140 A AC for control circuit conforming to IEC 60947-5-1300 A at 440 V for power circuit conforming to IEC 60947
    • Maximum Operating Rate : 3600 cyc/h at 60 °C
    • Minimum Switching Current : 5 mA for control circuit
    • Minimum Switching Voltage : 17 V for control circuit
    • Rated Breaking Capacity : 300 kA at 440 V for power circuit conforming to IEC 60947
  • Important Information Attributes
    • Persona Type Ids : EU, LC, OM, OM8, PB
    • Persona Type Names : End User, Contractor, Original Equipment Manufacturer, OEM - Control Panelbuilder, Panel Builder
    • Contactor Application : resistive load, motor control
    • Insulation Resistance : > 10 MOhm for control circuit, > 10 MOhm for control circuit> 10 MOhm for control circuit, > 10 MOhm for control circuit
    • Mechanical Robustness : shocks contactor opened 10 Gn for 11 ms)shocks contactor closed 15 Gn for 11 ms)vibrations contactor opened 2 Gn, 5...300 Hz), vibrations contactor closed 4 Gn, 5...300 Hz)
    • Motor Power Kw : 10 kW at 500 V AC 50/60 Hz, 10 kW at 660...690 V AC 50/60 Hz4 kW at 220...230 V AC 50/60 Hz7.5 kW at 380...400 V AC 50/60 Hz9 kW at 415...440 V AC 50/60 Hz
    • Mounting Support : rail, plate
    • Power Dissipation Per Pole : 0.8 W AC-32.5 W AC-1, 0.8 W AC-3e
    • Range : TeSys, TeSys Deca
    • Tightening Torque : power circuit 1.7 N.m Philips No 2power circuit 1.7 N.m pozidriv No 2control circuit 1.7 N.m flat Ø 6 mm, control circuit 1.7 N.m Philips No 2, power circuit 1.7 N.m flat Ø 6 mm, control circuit 1.7 N.m pozidriv No 2
    • Utilisation Category : AC-1, AC-3, AC-3e
    • Certificate Agency : CCC, GOST, GL, UL, LROS (Lloyds register of shipping), DNV, BV, RINA, CSA, UKCA
    • [Ie] Rated Operational Current : 32 A (at <60 °C) at <= 440 V AC AC-1 for power circuit18 A (at <60 °C) at <= 440 V AC AC-3 for power circuit, 18 A (at <60 °C) at <= 440 V AC AC-3e for power circuit
    • [Ui] Rated Insulation Voltage : power circuit 600 V ULpower circuit 690 V IEC 60947-4-1control circuit 600 V CSA, control circuit 600 V UL, power circuit 600 V CSAcontrol circuit 690 V IEC 60947-4-1
    • Connections - Terminals : control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: flexible without cable endcontrol circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable endpower circuit: screw clamp terminals 2 1.5-6 mm² - cable stiffness: solid without cable endpower circuit: screw clamp terminals 1 1-6 mm² - cable stiffness: flexible with cable endpower circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: flexible with cable endpower circuit: screw clamp terminals 1 1.5-6 mm² - cable stiffness: flexible without cable endpower circuit: screw clamp terminals 2 1.5-6 mm² - cable stiffness: flexible without cable end, control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: solid without cable end, control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: solid without cable end, control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end, control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible with cable endpower circuit: screw clamp terminals 1 1.5-6 mm² - cable stiffness: solid without cable end
    • Non-overlap Time : 1.5 ms on de-energisation between NC and NO contacts, 1.5 ms on energisation between NC and NO contacts
    • Carbon Footprint Of The Distribution Phase [A4] : 0.1529533872191322, 0.2 kg CO2 eq.
    • Carbon Footprint Of The Installation Phase [A5] : 0.1 kg CO2 eq., 0.053901212559319844
    • Carbon Footprint Of The Manufacturing Phase [A1 To A3] : 1 kg CO2 eq., 1.3685313051180024
    • Carbon Footprint Of The Use Phase [B2 B3 B4 B6] : 24 kg CO2 eq., 24.42511252308
    • Local Data Status : Publishable
    • Local Publishable Date : 2025-05-31
    • Return Indicator : Y
    • Stocking Flag : Y
    • Stock Policy : 1
    • Device Type : LV equipment - LV contactor
    • Serviceability : No
    • Traceability : No
    • Field Service Division : PPIBS
    • Average Life Duration : 20 year(s)
    • Weee Scope : In
    • Weee Product Category : 5
    • Scope Perimeter : At least in Europe
    • Eoli Availability Display : Yes
    • End Of Life Doc Ref : ENVEOLI1501004
    • Reach Full Compliance Status : Free of Substances of Very High Concern above the threshold
    • Reach Full Compliance Status Id : NOT_CONTAINING_SVHC
    • Reach Compliance Directive : Free of Substances of Very High Concern above the threshold
    • Rohs Eur In Scope : Yes
    • Rohs Eur Status : Compliant
    • Rohs Eur Conformity Date : 2538
    • Rohs Eur Full Compliance Status : Compliant
    • China Rohs In Scope : No
    • China Rohs Label : 1
    • With Recycled Cardboard : Yes
    • Without Single Use Plastic : Yes
    • Product Contributes To Saved And Avoided Emissions : No
    • Tier Id : 2
    • Tier : 2
    • Function Option Id : STANDARD
    • Function Option : Standard
    • Market Segmentation Id : INDUSTRIAL
    • Market Segmentation : Industrial
    • Product Kit Identifier : N
    • Associated Fuse Rating : 10 A gG for control circuit conforming to IEC 60947-5-135 A at <= 690 V coordination type 2 for power circuit50 A at <= 690 V coordination type 1 for power circuit
    • Average Impedance : 2.5 mOhm - Ith 32 A 50 Hz for power circuit
    • Coil Technology : without built-in bidirectional peak limiting diode suppressor
    • Compatibility Code : LC1D
    • Device Short Name : LC1D
    • Fire Resistance : 850 °C IEC 60695-2-1
    • Flame Retardance : V1 conforming to UL 94
    • Heat Dissipation : 2-3 W at 50/60 Hz for control circuit
    • Inrush Power In Va : 70-70 VA cos phi 0.75 (at 20 °C)
    • Mechanical Durability : 15 Mcycles
    • Number Of Poles : 3P
    • Operating Time : 4...19 ms opening12...22 ms closing
    • Overvoltage Category : III
    • Pole Contact Composition : 3 NO
    • Product Availability : Stock - Normally stocked in distribution facility
    • Product Or Component Type : contactor
    • Quantity Per Set : set of 10
    • Range Of Product : TeSys Deca
    • Returnability : Yes
    • Safety Reliability Level : B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
    • Software Version : v6.2.4
    • Sustainable Packaging : Yes
    • Total Lifecycle Carbon Footprint : 26 kg CO2 eq.
    • Weee Label : The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
    • Pep Code : ENVPEP1501004EN
    • Database Version : 2024-01
    • Pep Verification Date : 2026-03-17
    • Pcr Version : PEP-PCR-ed4-2021 09 06
    • Psr Version : PSR-0005-ed3-2023 06 06
    • Type Of Verification For The Pep : Independent internal review
    • Data Source : extrapolated product
    • Functional-unit Description : Establish and cut off the supply of a downstream installation from an electrical and/or mechanical control characterised by the composition of the poles or type of contacts X, a rated voltage of Ue, a rated current Ie, a control circuit voltage Uc, with Np poles, and if applicable the specific specifications, in the Household/Commercial or Industrial application areas, according to the appropriate use scenario, and during the reference service life of the product of 20 years
    • Functional-unit Quantity : 1
    • Functional-unit Unit : unit
    • Reference Lifetime In Y : 20
    • Energy Consumption On Product Lifetime In Kwh : 271.56
    • Energy Model - Manufacturing [A1-a3] : Electricity Mix; Low voltage; 2020; France, FR
    • Energy Model - Installation [A5] : No energy used
    • Energy Model - Use [B6] : Electricity Mix; Low voltage; 2020; France, FR
    • Energy Model - End Of Life [C1-c4] : Global, European and French datasets are used.
    • Recyclability Potential In % : 66
    • Height Nominal : 77 mm
    • Width Nominal : 45 mm
    • [Ith] Conventional Free Air Thermal Current : 10 A (at 60 °C) for control circuit32 A (at 60 °C) for power circuit
    • [Uc] Control Circuit Voltage : 110 V AC 50/60 Hz
    • [Ue] Rated Operational Voltage : power circuit <= 690 V AC 25...400 Hz
    • [Uimp] Rated Impulse Withstand Voltage : 6 kV IEC 60947
    • Hold-in Power Consumption In Va : 7-7 VA 50/60 Hz cos phi 0.3 (at 20 °C)
    • Nbr. Of Units In Pkg. : 1
    • Package Weight(Lbs) : 320.0 g
    • Take-back : No
    • Warranty (In Months) : 18
    • Customs Code : 8536490065
  • Environment Attributes Main
    • China Rohs Regulation : Product out of China RoHS scope , Pro-active China RoHS declaration (out of China RoHS legal scope)
    • Climatic Withstand : IACS E10 exposure to damp heat, IEC 60947-1 Annex Q category D exposure to damp heat
    • Ip Degree Of Protection : IP2X IEC 60529, IP2X VDE 0106
    • Permissible Ambient Air Temperature Around The Device : -5-60 °C, -40-70 °C at Uc, -40-70 °C at Uc-5-60 °C, -40-70 °C at Uc, -40-70 °C at Uc
    • Take Back : No
    • Reach Free Shvc : Yes
    • Recycled Metal Content At Cr Level : 0 %
    • Toxic Heavy Metal Free : Yes
    • Mercury Free : Yes
    • Carbon Footprint : 26.000498427976453
    • Circularity Profile : ENVEOLI1501004
    • Environmental Disclosure : ENVPEP1501004EN
    • Eu Rohs Directive : Compliant
    • Operating Altitude : 9842.52 ft (3000 m) without derating
    • Packaging Made With Recycled Cardboard : Yes
    • Packaging Without Single Use Plastic : Yes
    • Reach Free Of Svhc : Yes
    • Reach Regulation : Free of Substances of Very High Concern above the threshold
    • Pep Code : ENVPEP1501004EN
    • Pep Verification Date : 2026-03-17
    • Pcr Version : PEP-PCR-ed4-2021 09 06
    • Psr Version : PSR-0005-ed3-2023 06 06
    • Type Of Verification For The Pep : Independent internal review
  • General Attributes
    • Product Or Component Type : contactor
    • Range Of Product : TeSys Deca
  • ETIM
    • ETIM 8 : EC000066
    • ETIM 9 : EC000066
  • Contractual Warranty Attributes
    • Warranty Period : 18 months
    • Warranty : 18 months
  • Specifications
    • Country of Origin : France, United States
    • Depth : 86 mm