IEC contactor, TeSys Deca, nonreversing, 18A, 10HP at 480VAC, up to 100kA SCCR, 3 phase, 3 NO, 110VAC 50/60Hz coil, bulk

CONTACTOR 575VAC 18AMP IEC +OP

SQDLC1D18F7TQ LC1D18F7TQ 3389110123814
182.99 / EA
http://schema.org/OutOfStock
  • Certifications: BV, CCC, CSA, DNV, GL, GOST, LROS (Lloyds Register Of Shipping), RINA, UKCA, UL
  • Contact Configuration: 1 NO + 1 NC, 3 NO
  • Depth: 86 mm
  • Height: 77 mm
  • Impedance: 2.5 MOhm - Ith 32 A 50 Hz For Power Circuit
  • Net Weight: 3.3 kg
  • Standard: CSA C22.2 No 14, EN/IEC 60947-4-1, EN/IEC 60947-5-1, IEC 60335-1, UL 508
  • Warranty Length: 18 mth
  • Width: 45 mm
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 18A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 5HP at 200-208VAC, 5HP at 240VAC, 10HP at 480VAC and 15HP at 600VAC three phase. Contactor is also rated for 1HP at 115VAC and 3HP at 240VAC single phase. When used with a 480VAC up to 60A circuit breaker, this contactor can have a SCCR up to 85kA. When used with up to a 600VAC 40A Class J or CC fuse, this contactor can have a SCCR up to 100kA. Contactor is supplied with a 110 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.03 inches tall, 1.77 inches wide and 3.39 inches deep. It weighs 0.73 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
QTY
  • Product Description
  • Specifications
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 18A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 5HP at 200-208VAC, 5HP at 240VAC, 10HP at 480VAC and 15HP at 600VAC three phase. Contactor is also rated for 1HP at 115VAC and 3HP at 240VAC single phase. When used with a 480VAC up to 60A circuit breaker, this contactor can have a SCCR up to 85kA. When used with up to a 600VAC 40A Class J or CC fuse, this contactor can have a SCCR up to 100kA. Contactor is supplied with a 110 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.03 inches tall, 1.77 inches wide and 3.39 inches deep. It weighs 0.73 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
  • Environment
    • Product Certifications : CCC || GOST || GL || UL || LROS (Lloyds register of shipping) || DNV || BV || RINA || CSA || UKCA
    • Height : 77 mm
    • Standards : EN/IEC 60947-4-1 || CSA C22.2 No 14 || EN/IEC 60947-5-1 || UL 508 || IEC 60335-1
    • Climatic Withstand : IACS E10 exposure to damp heat || IEC 60947-1 Annex Q category D exposure to damp heat
    • Net Weight : 3.3 kg
    • Flame Retardance : V1 conforming to UL 94
    • Ip Degree Of Protection : IP2X IEC 60529 || IP2X VDE 0106
    • Mechanical Robustness : shocks contactor opened 10 Gn for 11 ms) || shocks contactor closed 15 Gn for 11 ms) || vibrations contactor opened 2 Gn, 5...300 Hz) || vibrations contactor closed 4 Gn, 5...300 Hz)
    • Operating Altitude : 9842.52 ft (3000 m) without derating
    • Quantity Per Set : set of 10
    • Fire Resistance : 850 °C IEC 60695-2-1
    • Width : 45 mm
    • Depth : 86 mm
    • Permissible Ambient Air Temperature Around The Device : -5-60 °C || -40-70 °C at Uc
  • Contractual warranty
    • Warranty : 18 months
  • Offer Sustainability
    • Rohs Exemption Information : Yes
    • Mercury Free : Yes
    • Environmental Disclosure : ENVPEP1501004
    • Sustainable Offer Status : Green Premium product
    • Pvc Free : Yes
    • Toxic Heavy Metal Free : Yes
    • Reach Regulation : Free of Substances of Very High Concern above the threshold
    • California Proposition 65 : WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
    • Reach Free Of Svhc : Yes
    • Weee : The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
    • China Rohs Regulation : Pro-active China RoHS declaration (out of China RoHS legal scope)
    • Circularity Profile : ENVEOLI1501004
    • Eu Rohs Directive : Compliant
  • Complementary
    • Non-Overlap Time : 1.5 ms on de-energisation between NC and NO contacts || 1.5 ms on energisation between NC and NO contacts
    • Minimum Switching Current : 5 mA for control circuit
    • Power Dissipation Per Pole : 0.8 W AC-3 || 2.5 W AC-1 || 0.8 W AC-3e
    • Average Impedance : 2.5 mOhm - Ith 32 A 50 Hz for power circuit
    • Auxiliary Contact Composition : 1 NO + 1 NC
    • [Ith] Conventional Free Air Thermal Current : 10 A (at 60 °C) for control circuit || 32 A (at 60 °C) for power circuit
    • Control Circuit Voltage Limits : 0.3...0.6 Uc 60-60 °C drop-out AC 50/60 Hz || 0.8...1.1 Uc 60-60 °C operational AC 50 Hz || 0.85...1.1 Uc 60-60 °C operational AC 60 Hz
    • Mounting Support : rail || plate
    • Control Circuit Type : AC 50/60 Hz
    • Safety Reliability Level : B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
    • Insulation Resistance : > 10 MOhm for control circuit
    • Rated Breaking Capacity : 300 kA at 440 V for power circuit conforming to IEC 60947
    • Irms Rated Making Capacity : 140 A AC for control circuit conforming to IEC 60947-5-1 || 300 A at 440 V for power circuit conforming to IEC 60947
    • Associated Fuse Rating : 10 A gG for control circuit conforming to IEC 60947-5-1 || 35 A at <= 690 V coordination type 2 for power circuit || 50 A at <= 690 V coordination type 1 for power circuit
    • Inrush Power In Va : 70-70 VA cos phi 0.75 (at 20 °C)
    • [Uimp] Rated Impulse Withstand Voltage : 6 kV IEC 60947
    • Pole Contact Composition : 3 NO
    • Connections - Terminals : control circuit: screw clamp terminal 1 1-4 mm² - cable stiffness: solid without cable end || control circuit: screw clamp terminal 2 1-4 mm² - cable stiffness: solid without cable end || control circuit: screw clamp terminal 1 1-4 mm² - cable stiffness: flexible without cable end || control circuit: screw clamp terminal 2 1-4 mm² - cable stiffness: flexible without cable end || control circuit: screw clamp terminal 1 1-4 mm² - cable stiffness: flexible with cable end || control circuit: screw clamp terminal 2 1-2.5 mm² - cable stiffness: flexible with cable end || power circuit: screw clamp terminal 1 1.5-6 mm² - cable stiffness: solid without cable end || power circuit: screw clamp terminal 2 1.5-6 mm² - cable stiffness: solid without cable end || power circuit: screw clamp terminal 1 1-6 mm² - cable stiffness: flexible with cable end || power circuit: screw clamp terminal 2 1-4 mm² - cable stiffness: flexible with cable end || power circuit: screw clamp terminal 1 1.5-6 mm² - cable stiffness: flexible without cable end || power circuit: screw clamp terminal 2 1.5-6 mm² - cable stiffness: flexible without cable end
    • Coil Technology : without built-in bidirectional peak limiting diode suppressor
    • Operating Time : 4...19 ms opening || 12...22 ms closing
    • Minimum Switching Voltage : 17 V for control circuit
    • Maximum Operating Rate : 3600 cyc/h 60 °C
    • Tightening Torque : control circuit 1.7 N.m flat Ø 6 mm || control circuit 1.7 N.m Philips No 2 || power circuit 1.7 N.m flat Ø 6 mm || power circuit 1.7 N.m Philips No 2 || control circuit 1.7 N.m pozidriv No 2 || power circuit 1.7 N.m pozidriv No 2
    • Mechanical Durability : 15000000 cycles
    • Compatibility Code : LC1D
    • Hold-In Power Consumption In Va : 7-7 VA 50/60 Hz cos phi 0.3 (at 20 °C)
    • Overvoltage Category : III
    • Maximum Horse Power Rating : 1 hp at 115 V AC 50/60 Hz for 1 phase motors conforming to UL || 1 hp at 115 V AC 50/60 Hz for 1 phase motors conforming to CSA || 10 hp at 460/480 V AC 50/60 Hz for 3 phase motors conforming to CSA || 10 hp at 460/480 V AC 50/60 Hz for 3 phase motors conforming to UL || 15 hp at 575/600 V AC 50/60 Hz for 3 phase motors conforming to CSA || 15 hp at 575/600 V AC 50/60 Hz for 3 phase motors conforming to UL || 5 hp at 200/208 V AC 50/60 Hz for 3 phase motors conforming to CSA || 5 hp at 200/208 V AC 50/60 Hz for 3 phase motors conforming to UL || 3 hp at 230...240 V AC 50/60 Hz for 1 phase motors conforming to CSA || 3 hp at 230...240 V AC 50/60 Hz for 1 phase motors conforming to UL || 5 hp at 230...240 V AC 50/60 Hz for 3 phase motors conforming to CSA || 5 hp at 230...240 V AC 50/60 Hz for 3 phase motors conforming to UL
    • Motor Power Kw : 10 kW at 500 V AC 50/60 Hz || 10 kW at 660...690 V AC 50/60 Hz || 4 kW at 220...230 V AC 50/60 Hz || 7.5 kW at 380...400 V AC 50/60 Hz || 9 kW at 415...440 V AC 50/60 Hz
    • [Ui] Rated Insulation Voltage : control circuit 600 V CSA || control circuit 600 V UL || power circuit 600 V CSA || power circuit 600 V UL || control circuit 690 V IEC 60947-4-1 || power circuit 690 V IEC 60947-4-1
    • Heat Dissipation : 2-3 W at 50/60 Hz for control circuit
    • Protective Cover : with
  • Specifications
    • [Uc] Control Circuit Voltage : 110 V AC 50/60 Hz
    • [Ue] Rated Operational Voltage : power circuit <= 690 V AC 25...400 Hz
    • Range Of Product : TeSys Deca
    • Contactor Application : resistive load || motor control
    • Product Or Component Type : contactor
    • Range : TeSys || TeSys Deca
    • Utilisation Category : AC-1 || AC-3 || AC-3e
    • [Ie] Rated Operational Current : 32 A (at <60 °C) at <= 440 V AC AC-1 for power circuit || 18 A (at <60 °C) at <= 440 V AC AC-3 for power circuit || 18 A (at <60 °C) at <= 440 V AC AC-3e for power circuit
    • Poles Description : 3P
    • Device Short Name : LC1D