IEC contactor, TeSys D, nonreversing, 12A, 7.5HP at 480VAC, up to 100kA SCCR, 3 phase, 3 NO, 440VAC 50/60Hz coil, open

CONTACTOR 600VAC 12AMP IEC +OP

SQDLC1D12R7 LC1D12R7 785901787471
130.17 / EACH
  • Certifications: BV, CCC, CSA, DNV, GL, GOST, LROS (Lloyds Register Of Shipping), RINA, UKCA, UL
  • Contact Configuration: 1 NO + 1 NC, 3 NO
  • Depth: 86 mm
  • Height: 77 mm
  • Impedance: 2.5 MOhm - Ith 25 A 50 Hz Power Circuit
  • Net Weight: 0.325 kg
  • Standard: CSA C22.2 No 14, EN 60947-4-1, EN 60947-5-1, IEC 60947-4-1, IEC 60947-5-1, UL 508
  • Storage Temperature: -60-80 °C
  • Warranty Length: 18 mth
  • Width: 45 mm
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 12A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 3HP at 200-208VAC, 3HP at 240VAC, 7.5HP at 480VAC and 10HP at 600VAC three phase. Contactor is also rated for 0.5HP at 115VAC and 2HP at 240VAC single phase. When used with a 480VAC up to 35A circuit breaker, this contactor can have a SCCR up to 85kA. When used with up to a 600VAC 30A Class J or CC fuse, this contactor can have a SCCR up to 100kA. Contactor is supplied with a 440 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.03 inches tall, 1.77 inches wide and 3.39 inches deep. It weighs 0.72 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
  • Product Description
  • Specifications
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 12A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 3HP at 200-208VAC, 3HP at 240VAC, 7.5HP at 480VAC and 10HP at 600VAC three phase. Contactor is also rated for 0.5HP at 115VAC and 2HP at 240VAC single phase. When used with a 480VAC up to 35A circuit breaker, this contactor can have a SCCR up to 85kA. When used with up to a 600VAC 30A Class J or CC fuse, this contactor can have a SCCR up to 100kA. Contactor is supplied with a 440 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.03 inches tall, 1.77 inches wide and 3.39 inches deep. It weighs 0.72 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
  • Average Impedance : 2.5 mOhm - Ith 25 A 50 Hz power circuit
  • Control Circuit Type : AC 50/60 Hz
  • Associated Fuse Rating : 10 A gG signalling circuit IEC 60947-5-1 || 40 A gG <= 690 V type 1 power circuit || 25 A gG <= 690 V type 2 power circuit
  • Safety Reliability Level : B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
  • Electrical Durability : 2 Mcycles 12 A AC-3 <= 440 V || 0.8 Mcycles 25 A AC-1 <= 440 V
  • Standards : CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508
  • Pole Contact Composition : 3 NO
  • [Ui] Rated Insulation Voltage : power circuit 690 V IEC 60947-4-1 || power circuit 600 V CSA || power circuit 600 V UL || signalling circuit 690 V IEC 60947-1 || signalling circuit 600 V CSA || signalling circuit 600 V UL
  • Product Or Component Type : contactor
  • Poles Description : 3P
  • [Uc] Control Circuit Voltage : 440 V AC 50/60 Hz
  • Auxiliary Contact Composition : 1 NO + 1 NC
  • Contactor Application : resistive load || motor control
  • Motor Power Kw : 3 kW 220...230 V AC 50/60 Hz AC-3) || 5.5 kW 380...400 V AC 50/60 Hz AC-3) || 5.5 kW 415...440 V AC 50/60 Hz AC-3) || 7.5 kW 500 V AC 50/60 Hz AC-3) || 7.5 kW 660...690 V AC 50/60 Hz AC-3) || 3.7 kW 400 V AC 50/60 Hz AC-4)
  • Operating Time : 12...22 ms closing || 4...19 ms opening
  • Tightening Torque : power circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || power circuit 1.7 N.m screw clamp terminals Philips No 2 || control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2
  • Power Dissipation Per Pole : 0.36 W AC-3 || 1.56 W AC-1
  • [Uimp] Rated Impulse Withstand Voltage : 6 kV IEC 60947
  • Mechanical Durability : 15 Mcycles
  • Maximum Operating Rate : 3600 cyc/h 60 °C
  • [Ith] Conventional Free Air Thermal Current : 25 A 60 °C power circuit || 10 A 60 °C signalling circuit
  • Product Name : TeSys D
  • Utilisation Category : AC-3 || AC-4 || AC-1
  • Overvoltage Category : III
  • Rated Breaking Capacity : 250 A 440 V power circuit IEC 60947
  • [Ie] Rated Operational Current : 25 A 60 °C) <= 440 V AC AC-1 power circuit || 12 A 60 °C) <= 440 V AC AC-3 power circuit
  • Range : TeSys
  • [Ue] Rated Operational Voltage : power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
  • Connections - Terminals : power circuit screw clamp terminals 1 1-4 mm²flexible without cable end || power circuit screw clamp terminals 2 1-4 mm²flexible without cable end || power circuit screw clamp terminals 1 1-4 mm²flexible with cable end || power circuit screw clamp terminals 2 1-2.5 mm²flexible with cable end || power circuit screw clamp terminals 1 1-4 mm²solid without cable end || power circuit screw clamp terminals 2 1-4 mm²solid without cable end || control circuit screw clamp terminals 1 1-4 mm²flexible without cable end || control circuit screw clamp terminals 2 1-4 mm²flexible without cable end || control circuit screw clamp terminals 1 1-4 mm²flexible with cable end || control circuit screw clamp terminals 2 1-2.5 mm²flexible with cable end || control circuit screw clamp terminals 1 1-4 mm²solid without cable end || control circuit screw clamp terminals 2 1-4 mm²solid without cable end
  • Maximum Horse Power Rating : 0.5 hp 115 V at AC 50/60 Hz for 1 phase || 2 hp 230/240 V at AC 50/60 Hz for 1 phase || 3 hp 200/208 V at AC 50/60 Hz for 3 phase || 3 hp 230/240 V at AC 50/60 Hz for 3 phase || 7.5 hp 460/480 V at AC 50/60 Hz for 3 phase || 10 hp 575/600 V at AC 50/60 Hz for 3 phase
  • Device Short Name : LC1D
  • [Icw] Rated Short-Time Withstand Current : 105 A 40 °C - 10 s power circuit || 210 A 40 °C - 1 s power circuit || 30 A 40 °C - 10 min power circuit || 61 A 40 °C - 1 min power circuit || 100 A - 1 s signalling circuit || 120 A - 500 ms signalling circuit || 140 A - 100 ms signalling circuit
  • Product Certifications : DNV || CSA || CCC || LROS (Lloyds register of shipping) || GOST || RINA || UL || GL || BV || UKCA
  • Mounting Support : rail || plate
  • Irms Rated Making Capacity : 250 A 440 V power circuit IEC 60947 || 140 A AC signalling circuit IEC 60947-5-1 || 250 A DC signalling circuit IEC 60947-5-1
  • Protective Cover : with
  • Complementary
    • Coil Technology : without built-in suppressor module
    • Hold-In Power Consumption In Va : 7.5-7.5 VA 60 Hz 0.3 20 °C) || 7-7 VA 50 Hz 0.3 20 °C)
    • Insulation Resistance : > 10 MOhm signalling circuit
    • Signalling Circuit Frequency : 25...400 Hz
    • Minimum Switching Current : 5 mA signalling circuit
    • Non-Overlap Time : 1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
    • Minimum Switching Voltage : 17 V signalling circuit
    • Heat Dissipation : 2-3 W 50/60 Hz
    • Control Circuit Voltage Limits : 0.3...0.6 Uc -40-70 °C drop-out AC 50/60 Hz || 0.8...1.1 Uc -40-60 °C operational AC 50 Hz || 0.85...1.1 Uc -40-60 °C operational AC 60 Hz || 1...1.1 Uc 60-70 °C operational AC 50/60 Hz
    • Inrush Power In Va : 70-70 VA 60 Hz 0.75 20 °C) || 70-70 VA 50 Hz 0.75 20 °C)
    • Auxiliary Contacts Type : mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
  • Contractual warranty
    • Warranty : 18 months
  • Offer Sustainability
    • Eu Rohs Directive : Compliant
    • California Proposition 65 : WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
    • Pvc Free : Yes
    • Reach Regulation : Free of Substances of Very High Concern above the threshold
    • Environmental Disclosure : ENVPEP1501004EN
    • Weee : The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
    • Mercury Free : Yes
    • Toxic Heavy Metal Free : Yes
    • China Rohs Regulation : Pro-active China RoHS declaration (out of China RoHS legal scope)
    • Rohs Exemption Information : Yes
    • Reach Free Of Svhc : Yes
    • Circularity Profile : ENVEOLI1501004EN
    • Sustainable Offer Status : Green Premium product
  • Environment
    • Fire Resistance : 850 °C IEC 60695-2-1
    • Height : 77 mm
    • Protective Treatment : TH IEC 60068-2-30
    • Ambient Air Temperature For Operation : -40-60 °C || 60-70 °C with derating
    • Width : 45 mm
    • Depth : 86 mm
    • Ip Degree Of Protection : IP20 front face IEC 60529
    • Mechanical Robustness : vibrations contactor open2 Gn, 5...300 Hz || vibrations contactor closed4 Gn, 5...300 Hz || shocks contactor open10 Gn for 11 ms || shocks contactor closed15 Gn for 11 ms
    • Flame Retardance : V1 conforming to UL 94
    • Operating Altitude : 0...9842.52 ft (0...3000 m)
    • Net Weight : 0.325 kg
    • Ambient Air Temperature For Storage : -60-80 °C
    • Pollution Degree : 3