IEC contactor, TeSys D Green, nonreversing, 18A, 10HP at 480VAC, up to 100kA SCCR, 3 phase, 3 NO, 100/250VAC/VDC coil

IEC contactor, TeSys D Green, nonreversing, 18A, 10HP at 480VAC, up to 100kA SCCR, 3 phase, 3 NO, 100/250VAC/VDC coil

SQDLC1D18KUE LC1D18KUE 785901965794
55.78 / EA
  • Certifications: CCC, CSA, DNV-GL, EAC, KC, LROS (Lloyds Register Of Shipping), UL
  • Color: Gray SE GREY 6), Green SE GREEN 2)
  • Contact Configuration: 1 NO + 1 NC
  • Contact Configuration: 3 NO
  • Depth: 86 mm
  • Height: 77 mm
  • Impedance: 2.5 MOhm - Ith 32 A 50 Hz Power Circuit
  • Net Weight: 0.378 kg
  • Standard: CSA C22.2 No 60947-4-1, EN/IEC 60947-4-1, EN/IEC 60947-5-1, UL 60947-4-1
  • Storage Temperature: -60-80 °C
  • Warranty Length: 18 mth
  • Width: 45 mm
TeSys D Green contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 18A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 5HP at 200-208VAC, 5HP at 240VAC, 10HP at 480VAC and 15HP at 600VAC three phase. Contactor is also rated for 1HP at 115VAC and 3HP at 240VAC single phase. When used with a 480VAC up to 60A circuit breaker, this contactor can have a SCCR up to 85kA. When used with up to a 600VAC 40A Class J or CC fuse, this contactor can have a SCCR up to 100kA. Equipped with an electronic coil, wide band voltage 100-250V, AC/DC compatible, low consumption. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.03 inches tall, 1.77 inches wide and 3.39 inches deep. It weighs 0.83 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
  • Product Description
  • Specifications
TeSys D Green contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 18A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 5HP at 200-208VAC, 5HP at 240VAC, 10HP at 480VAC and 15HP at 600VAC three phase. Contactor is also rated for 1HP at 115VAC and 3HP at 240VAC single phase. When used with a 480VAC up to 60A circuit breaker, this contactor can have a SCCR up to 85kA. When used with up to a 600VAC 40A Class J or CC fuse, this contactor can have a SCCR up to 100kA. Equipped with an electronic coil, wide band voltage 100-250V, AC/DC compatible, low consumption. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.03 inches tall, 1.77 inches wide and 3.39 inches deep. It weighs 0.83 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
  • Contractual warranty
    • Warranty : 18 months
  • Environment
    • Maximum Width : 45 mm
    • Mechanical Robustness : vibrations contactor open2 Gn, 5...300 Hz || vibrations contactor closed4 Gn, 5...300 Hz || shocks contactor open10 Gn for 11 ms || shocks contactor closed15 Gn for 11 ms
    • Net Weight : 0.378 kg
    • Ambient Air Temperature For Storage : -60-80 °C
    • Operating Altitude : 0...9842.52 ft (0...3000 m)
    • Flame Retardance : V1 conforming to UL 94
    • Protective Treatment : TH IEC 60068-2-30
    • Maximum Height : 77 mm
    • Color : Gray SE GREY 6) || Green SE GREEN 2)
    • Maximum Depth : 86 mm
    • Pollution Degree : 3
    • Fire Resistance : 850 °C IEC 60695-2-1
    • Ip Degree Of Protection : IP20 front face IEC 60529
    • Ambient Air Temperature For Operation : -40-60 °C || 60-70 °C with derating
  • Complementary
    • Inrush Power In W : 18-18 W 20 °C
    • Minimum Switching Current : 5 mA signalling circuit
    • Minimum Switching Voltage : 17 V signalling circuit
    • Hold-In Power Consumption In W : 1.1-1.1 W 20 °C
    • Inrush Power In Va : 25-25 VA 50/60 Hz 20 °C)
    • Insulation Resistance : > 10 MOhm signalling circuit
    • Heat Dissipation : 1.1-1.1 W 50/60 Hz
    • Hold-In Power Consumption In Va : 1.6-1.6 VA 20 °C) 50/60 Hz
    • Coil Technology : built-in bidirectional peak limiting
    • Control Circuit Voltage Limits : <= 0.1 Uc -40-70 °C drop-out AC/DC || 0.85...1.1 Uc -40-60 °C operational AC/DC || 1...1.1 Uc 60-70 °C operational AC/DC
    • Signalling Circuit Frequency : 25...400 Hz
    • Auxiliary Contacts Type : mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
    • Non-Overlap Time : 1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
  • Offer Sustainability
    • Rohs Exemption Information : Yes
    • Halogen Content Performance : Halogen free plastic parts & cables product
    • Circularity Profile : ENVEOLI1609001EN
    • Sustainable Offer Status : Green Premium product
    • Reach Regulation : Free of Substances of Very High Concern above the threshold
    • Eu Rohs Directive : Compliant
    • China Rohs Regulation : Product out of China RoHS scope. Substance declaration for your information.
    • Mercury Free : Yes
    • Weee : The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
    • Environmental Disclosure : ENVPEP1609001EN
  • [Ie] Rated Operational Current : 18 A 60 °C) <= 440 V AC-3 power circuit || 32 A 60 °C) <= 440 V AC-1 power circuit
  • Product Or Component Type : contactor
  • Tightening Torque : control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || power circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || power circuit 1.7 N.m screw clamp terminals Philips No 2
  • Pole Contact Composition : 3 NO
  • Product Certifications : CCC || CSA || EAC || UL || KC || DNV-GL || LROS (Lloyds register of shipping)
  • Standards : EN/IEC 60947-4-1 || EN/IEC 60947-5-1 || UL 60947-4-1 || CSA C22.2 No 60947-4-1
  • Associated Fuse Rating : 10 A gG signalling circuit IEC 60947-5-1 || 50 A gG <= 690 V type 1 power circuit || 35 A gG <= 690 V type 2 power circuit
  • Auxiliary Contact Composition : 1 NO + 1 NC
  • Motor Power Kw : 4 kW 220...230 V AC 50 Hz AC-3) || 7.5 kW 380...400 V AC 50 Hz AC-3) || 9 kW 415 V AC 50 Hz AC-3) || 9 kW 440 V AC 50 Hz AC-3) || 10 kW 500 V AC 50 Hz AC-3) || 10 kW 660...690 V AC 50 Hz AC-3)
  • Rated Breaking Capacity : 300 A 440 V power circuit IEC 60947
  • Mounting Support : plate || rail
  • Maximum Operating Rate : 3600 cyc/h 60 °C
  • Utilisation Category : AC-1 || AC-3
  • Operating Time : 45...55 ms closing || 20...90 ms opening
  • Maximum Horse Power Rating : 1 hp 115 V at AC 60 Hz for 1 phase || 3 hp 230/240 V at AC 60 Hz for 1 phase || 5 hp 200/208 V at AC 60 Hz for 3 phase || 5 hp 230/240 V at AC 60 Hz for 3 phase || 10 hp 460/480 V at AC 60 Hz for 3 phase || 15 hp 575/600 V at AC 60 Hz for 3 phase
  • Coil Type : AC/DC electronic
  • [Ith] Conventional Free Air Thermal Current : 10 A 60 °C signalling circuit || 32 A 60 °C power circuit
  • Product Name : TeSys D Green
  • [Icw] Rated Short-Time Withstand Current : 100 A - 1 s signalling circuit || 120 A - 500 ms signalling circuit || 140 A - 100 ms signalling circuit || 40 A 40 °C - 10 min power circuit || 84 A 40 °C - 1 min power circuit || 145 A 40 °C - 10 s power circuit || 240 A 40 °C - 1 s power circuit
  • Power Dissipation Per Pole : 2.5 W AC-1 || 0.8 W AC-3
  • Irms Rated Making Capacity : 140 A AC signalling circuit IEC 60947-5-1 || 250 A DC signalling circuit IEC 60947-5-1 || 300 A 440 V power circuit IEC 60947
  • Average Impedance : 2.5 mOhm - Ith 32 A 50 Hz power circuit
  • Safety Reliability Level : B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
  • Range : TeSys
  • Poles Description : 3P
  • [Ue] Rated Operational Voltage : power circuit <= 690 V AC 25...400 Hz
  • Connections - Terminals : control circuit screw clamp terminals 1 1-4 mm²flexible without cable end || control circuit screw clamp terminals 2 1-4 mm²flexible without cable end || control circuit screw clamp terminals 1 1-4 mm²flexible with cable end || control circuit screw clamp terminals 2 1-2.5 mm²flexible with cable end || control circuit screw clamp terminals 1 1-4 mm²solid || control circuit screw clamp terminals 2 1-4 mm²solid || power circuit screw clamp terminals 1 1.5-6 mm²flexible without cable end || power circuit screw clamp terminals 2 1.5-6 mm²flexible without cable end || power circuit screw clamp terminals 1 1-6 mm²flexible with cable end || power circuit screw clamp terminals 2 1-4 mm²flexible with cable end || power circuit screw clamp terminals 1 1.5-6 mm²solid || power circuit screw clamp terminals 2 1.5-6 mm²solid
  • [Ui] Rated Insulation Voltage : power circuit 690 V IEC 60947-4-1 || signalling circuit 690 V IEC 60947-1
  • Overvoltage Category : III
  • Protective Cover : with
  • Device Short Name : LC1D
  • [Uimp] Rated Impulse Withstand Voltage : 6 kV IEC 60947
  • Mechanical Durability : 15 Mcycles
  • Contactor Application : motor control || resistive load
  • Electrical Durability : 2.2 Mcycles 15 A AC-3 <= 440 V || 0.9 Mcycles 32 A AC-1 <= 440 V
  • [Uc] Control Circuit Voltage : 100...250 V AC 50/60 Hz || 100...250 V DC