power meter PowerLogic PM5563, 2 ethernet, up to 63th Harmonic, 1,1MB 4DI/2DO 52 alarms, with remote display

INTERMEDIATE POWER METER CL 0.

SQDMETSEPM5563RD METSEPM5563RD 3606480761416
4187.19 / EA
http://schema.org/OutOfStock
  • Depth: 2.83 in
  • IsSustainable: Yes
  • Number of Outputs: 2 Digital
This device is a DIN-mount energy meter with an additional 96mm by 96mm backlit LCD remote display. The meter provides Class 0.2S accuracy per IEC 62053-22 standard and 128 samples per cycle. The meter will measure Energy, Active and Reactive Power, Voltage, Current, Frequency, Power Factor and up to the 63rd Harmonic. Include 1.1 MegaBytes of memory for up to 14 selectable parameters with configurable interval and duration. This meter also feature the direct monitoring of neutral current. The meter will function in a 50Hz or 60Hz network and accepts supply voltage ranging from 100 to 480 VAC and 125 to 250 VDC. Line rated current for this meter is 1A or 5A input and will support Single Phase and Neutral, Three Phase, or Three Phase and Neutral configurations. The range of measurement voltage between Phases is 20 to 690 VAC at 45 to 65 Hz. Measurement range between Phase and Neutral is 20 to 400VAC at 45 to 65 Hz. Communication protocol are Modbus RTU and ASCII 2 wires with RS485 port support plus Modbus TCP/IP, Ethernet/IP and BACnet/IP based on 10/100 Mbit/s, daisy chain Ethernet with RJ45 port support. The embedded communication capabilities allow the support of the DNP 3.0 protocol, the access to an onboard web server and a Serial to Ethernet gateway. The meter also has four digital inputs with WAGES support and two digital outputs. There are 52 configurable alarms and it supports eight tariff schedules. Product dimensions are as follows: width 3.78 inches (96 millimetres), depth 3.03 inches (77 millimetres), height 3.78 inches (96 millimetres) and product weight 15.9 onces (450 g).
QTY
  • Features
  • Specifications
  • Prop 65
    • WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
  • Communications & Management Attributes
    • Communication Port Protocol : Modbus RTU and ASCII 9.6, 19.2 and 38.4 kbauds even/odd or none - 2 wires 2500 V, JBUS, Modbus TCP/IP 10/100 Mbit/s 2500 V, Ethernet Modbus TCP/IP daisy chain, BACnet IP, DNP3 over ethernet
    • Communication Port Support : RS485, ETHERNET
    • Communication Gateway : Ethernet/serial
  • Conformance Attributes
    • Product Certifications : CE conforming to IEC 61010-1, cULus conforming to UL 61010-1, BTL
    • Standards : EN 50470-3, EN 50470-1, IEC 62053-22:2020, IEC 60529, UL 61010-1, IEC 62053-24, IEC 61557-12:2015, ANSI C12.20, IEC 62053-23:2020, IEC 62052-11:2020, IEC 62052-31:2015
  • Complementary Attributes
    • US Rated Supply Voltage : 100...300 V DC, 90...528 V AC 45...65 Hz
    • Maximum Power Consumption In VA : 16 VA 480 V
  • Important Information Attributes
    • Data Recording : time stamping, data logs, maintenance logs, event logs, alarm logs, min/max of instantaneous values
    • Electromagnetic Compatibility : limits for harmonic current emissions class A conforming to IEC 61000-3-2, conducted RF disturbances level 3 conforming to IEC 61000-4-6, magnetic field at power frequency level 4 conforming to IEC 61000-4-8, conducted and radiated emissions class B conforming to EN 55022, limitation of voltage changes, voltage fluctuations and flicker in low-voltage conforming to IEC 61000-3-3, electrostatic discharge - test level: 8 kV level 4 conforming to IEC 61000-4-2, radiated radio-frequency electromagnetic field immunity test conforming to IEC 61000-4-3, electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4, surge immunity test level 4 conforming to IEC 61000-4-5, voltage dips and interruptions immunity test conforming to IEC 61000-4-11
    • Ethernet Service : SNTP client, SNMP-Traps
    • Market Segment : buildings small building cost management: billing: main incomer, buildings small building cost management: billing: sub feeder, buildings medium building cost management: billing: main incomer, buildings medium building cost management: billing: sub feeder, buildings large building cost management: billing: main incomer, buildings large building cost management: billing: sub feeder, buildings multi-site cost management: billing: main incomer, buildings multi-site cost management: billing: sub feeder, data center cost management: billing: main incomer, data center cost management: billing: sub feeder, healthcare cost management: billing: main incomer, healthcare cost management: billing: sub feeder, industry cost management: billing: main incomer, industry cost management: billing: sub feeder, buildings small building cost management: cost allocation: main incomer, buildings small building cost management: cost allocation: sub feeder, buildings medium building cost management: cost allocation: main incomer, buildings medium building cost management: cost allocation: sub feeder, buildings large building cost management: cost allocation: main incomer, buildings large building cost management: cost allocation: sub feeder, buildings multi-site cost management: cost allocation: main incomer, buildings multi-site cost management: cost allocation: sub feeder, data center cost management: cost allocation: main incomer, data center cost management: cost allocation: sub feeder, healthcare cost management: cost allocation: main incomer, healthcare cost management: cost allocation: sub feeder, industry cost management: cost allocation: main incomer, industry cost management: cost allocation: sub feeder, buildings small building network management: main incomer, buildings small building network management: sub feeder, buildings medium building network management: main incomer, buildings medium building network management: sub feeder, buildings large building network management: sub feeder, buildings multi-site network management: sub feeder, data center network management: sub feeder, healthcare network management: sub feeder, industry network management: sub feeder
    • Measurement Accuracy : apparent power +/- 0.5 %, frequency +/- 0.05 %, active energy +/- 0.2 %, reactive energy +/- 1 %, active power +/- 0.2 %, voltage +/- 0.1 %, power factor +/- 0.005, current +/- 0.15 %, reactive power +/- 1 %
    • Measurement Voltage : 20-400 V AC 45...65 Hz between phase and neutral, 20-828 V AC 45...65 Hz between phases
    • Ride Through Time : 35 ms 120 V AC typical, 129 ms 230 V AC typical, 50 ms 125 V DC typical
    • Type Of Measurement : current, voltage, frequency, power factor, energy, active and reactive power
    • Carbon Footprint Of The Distribution Phase A4 : 0.24020635933459739, 0.2 kg CO2 eq.
    • Carbon Footprint Of The End Of Life Phase C1 To C4 : 1.2006731281890972, 1 kg CO2 eq.
    • Carbon Footprint Of The Installation Phase A5 : 0 kg CO2 eq., 0.04421092926151829
    • Carbon Footprint Of The Manufacturing Phase A1 To A3 : 33 kg CO2 eq., 33.22408228090151
    • Carbon Footprint Of The Use Phase B2 B3 B4 B6 : 7 kg CO2 eq., 7.352530784746031
    • Connections Terminals : voltage circuit screw terminal block4, control circuit screw terminal block2, current transformer screw terminal block6, RS485 link screw terminal block4, digital input screw terminal block8, digital output screw terminal block4, Ethernet network RJ45 connector2
    • Local Data Status : Publishable
    • Local Publishable Date : 2025-06-18
    • HTML Description : The PowerLogic PM5000 series power meters are the new benchmark in affordable, precision metering. It is the ideal fit for high-end cost management applications, providing the measurement capabilities needed to allocate energy. The PM5563 provides basic metering with class 0.2S accuracy + 4DI/2DO + data logging + multi tariff + dual Ethernet & serial comms Modbus & BACnet/IP+ 4th CT input + gateway + internal web server - DIN rail meter, no display usage, perform tenant metering and sub-billing, pin-point energy savings, optimize equipment efficiency and utilization, and perform a high level assessment of the power quality in an electrical network.
    • Manufacturer : Schneider Electric
    • Device Type : Relay, Control & Measurement - measuring, monitoring device
    • Serviceability : Yes
    • Traceability : Yes
    • Field Service Division : DPIBS
    • Legacy WEEE Scope : In
    • Scope Perimeter : At least in Europe
    • EOLI Availability Display : Yes
    • End Of Life Doc Ref : ENVEOLI1310016_V2
    • Reach Full Compliance Status : Reference contains Substances of Very High Concern above the threshold
    • Reach Full Compliance Status Id : CONTAINS_SVHC
    • Reach Compliance Directive : Reference contains Substances of Very High Concern above the threshold
    • ROHS EUR In Scope : Yes
    • ROHS EUR Status : Compliant
    • ROHS EUR Full Compliance Status : Compliant
    • ROHS EUR Full Compliance Status Id : COMPLIANT
    • China ROHS In Scope : Yes
    • Green Premium Status For Reporting : Green Premium product
    • With Recycled Cardboard : No
    • Without Single Use Plastic : No
    • Product Contributes To Saved And Avoided Emissions : No
    • Return Indicator : Y
    • WD Status : 1 - GSC certified
    • Dangerous Goods Code : LITHIUM METAL BATTERIES IN EQUIP. BUTTON CELL-BAT EXEMPT
    • Compatibility Code : PM5563
    • Device Short Name : PM5563
    • Energy Efficiency Optimized : False
    • Frequency Measurement Range : 45-65 Hz
    • Information Displayed : tariff 8)
    • Mounting Support : DIN rail
    • Package Weight Lbs : 949.000 g
    • Power Quality Analysis : up to the 63rd harmonic
    • Product Availability : Stock - Normally stocked in distribution facility
    • Product Or Component Type : power meter
    • Range : PowerLogic
    • Returnability : Yes
    • Sustainable Packaging : No
    • Total Lifecycle Carbon Footprint : 42 kg CO2 eq.
    • Weee Label : The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
    • Relationship Type : Compatible relationship
    • Pep Code : ENVPEP1310016_V2
    • Pep Verification Date : 2025-07-29
    • PCR Version : PCR-4-ed4-EN-2021 09 06
    • PSR Version : PSR-0005-ed3.1-EN-2023 12 08
    • Functional Unit Description : PM5560 is a power and energy meter that provides functions such as measuring electrical parameters, monitoring power quality and enabling energy management during the lifetime of 15 years. It helps users analyze and optimize energy usage while ensuring power quality and reliability.
    • Functional Unit Unit : Unit
    • Product Kit Identifier : N
    • Product Manager : SEVERINO MUSSI
  • Environment Attributes Main
    • EU ROHS Directive : Compliant​, Compliant
    • IP Degree Of Protection : IP54 display: conforming to IEC 60529, IP30 rear: conforming to IEC 60529
    • ROHS Exemption Information : Yes
    • Take Back : No
    • Recycled Metal Content At Cr Level : 0 %
    • China ROHS Regulation : X
    • Toxic Heavy Metal Free : Yes
    • Mercury Free : Yes
    • Carbon Footprint : 42.061703482432755
    • Ambient Air Temperature For Operation : -25-70 °C
    • Circularity Profile : ENVEOLI1310016_V2
    • Environmental Disclosure : ENVPEP1310016_V2
    • Operating Altitude : <= 9842.52 ft (3000 m)
    • Packaging Made With Recycled Cardboard : No
    • Packaging Without Single Use Plastic : No
    • Reach Regulation : Reference contains Substances of Very High Concern above the threshold
    • Relative Humidity : 5-95 % 50-50 °C non-condensing
    • Pep Code : ENVPEP1310016_V2
    • Pep Verification Date : 2025-07-29
    • PCR Version : PCR-4-ed4-EN-2021 09 06
    • PSR Version : PSR-0005-ed3.1-EN-2023 12 08
  • General Attributes
    • Product Or Component Type : power meter
  • Output Attributes
    • Number Of Outputs : 2 digital
  • Input Attributes
    • Analogue Input Type : voltage (impedance 5 MOhm), current (impedance <= 0.3 mOhm)
    • Number Of Inputs : 4 digital
  • Specifications
    • Depth : 2.83 in