PM5110 Meter, modbus, up to 15th H, 1DO 33 alarms

PM5110 Meter, modbus, up to 15th H, 1DO 33 alarms

SQDMETSEPM5110 METSEPM5110 785901869535
863.00 / EA
  • Amperage: 1 A
  • Certifications: CE IEC 61010-1, CULus UL 61010-1
  • Depth: 2.83 in, 72 mm
  • Height: 3.78 in, 96 mm
  • Mounting Type: Flush-Mounted
  • Number of Outputs: 1
  • Standard: EN 50470-1, EN 50470-3, IEC 60529, IEC 61557-12, IEC 62053-22, IEC 62053-24, UL 61010-1
  • Weight: 13.40 oz, 380 g
  • Width: 3.78 in, 96 mm
This device is a flush-mount energy meter with a 96mm by 96mm backlit LCD display. The meter provides Class 0.5S accuracy per IEC 62053-22 standard and 64 samples per cycle. The meter will measure Energy, Active and Reactive Power, Voltage, Current, Frequency, Power Factor and up to 15th Harmonic. The meter will function in a 50Hz or 60Hz network and accepts supply voltage ranging from 100 to 415 VAC and 125 to 250 VDC. Line rated current for this meter is 1A or 5A input and will support Single Phase and Neutral, Three Phase, or Three Phase and Neutral configurations. The range of measurement voltage between Phases is 35 to 690 VAC at 47 to 63 Hz. Measurement range between Phase and Neutral is 20 to 400VAC at 47 to 63 Hz. Communication protocol is Modbus RTU and ASCII 2 wires with RS485 port support. The meter also has one digital pulse output and 33 configurable alarms. Product dimensions are as follows: width 3.78 inches (96 millimetres), depth 2.83 inches (72 millimetres), height 3.78 inches (96 millimetres) and product weight 13.4 onces (380 g).
  • Product Description
  • Additional Information
This device is a flush-mount energy meter with a 96mm by 96mm backlit LCD display. The meter provides Class 0.5S accuracy per IEC 62053-22 standard and 64 samples per cycle. The meter will measure Energy, Active and Reactive Power, Voltage, Current, Frequency, Power Factor and up to 15th Harmonic. The meter will function in a 50Hz or 60Hz network and accepts supply voltage ranging from 100 to 415 VAC and 125 to 250 VDC. Line rated current for this meter is 1A or 5A input and will support Single Phase and Neutral, Three Phase, or Three Phase and Neutral configurations. The range of measurement voltage between Phases is 35 to 690 VAC at 47 to 63 Hz. Measurement range between Phase and Neutral is 20 to 400VAC at 47 to 63 Hz. Communication protocol is Modbus RTU and ASCII 2 wires with RS485 port support. The meter also has one digital pulse output and 33 configurable alarms. Product dimensions are as follows: width 3.78 inches (96 millimetres), depth 2.83 inches (72 millimetres), height 3.78 inches (96 millimetres) and product weight 13.4 onces (380 g).
  • Specifications
    • Main
      • Range : PowerLogic
      • Product Name : PowerLogic PM5000
      • Device Short Name : PM5110
      • Product Or Component Type : Power meter
    • Complementary
      • Power Quality Analysis : up to the 15th harmonic
      • Device Application : Power monitoring
      • Type Of Measurement : Current || Voltage || Frequency || Power factor || Energy || Active and reactive power
      • Supply Voltage : 100...415 V AC 45...65 Hz || 125...250 V DC
      • Network Frequency : 50 Hz || 60 Hz
      • In Rated Current : 1 A || 5 A
      • Type Of Network : 1P + N || 3P + N || 3P
      • Power Consumption In Va : 10 VA 415 V
      • Ride-Through Time : 80 ms 120 V AC typical || 100 ms 230 V AC typical || 100 ms 415 V AC typical
      • Display Type : Backlit LCD
      • Display Resolution : 128 x 128 pixels
      • Sampling Rate : 64 samples/cycle
      • Measurement Current : 10…9000 mA
      • Analogue Input Type : voltage 5 MOhm) || current 0.3 MOhm)
      • Measurement Voltage : 35…690 V AC 45...65 Hz between phases || 20…400 V AC 45...65 Hz between phase and neutral
      • Frequency Measurement Range : 45…65 Hz
      • Number Of Inputs : 0
      • Measurement Accuracy : Active energy +/- 0.5 % || Reactive energy +/- 2 % || Active power +/- 0.5 % || Apparent power +/- 0.5 % || Frequency +/- 0.05 % || Power factor +/- 0.005 % || Current +/- 0.5 % || Voltage +/- 0.5 %
      • Accuracy Class : Class 0.5S active energy IEC 62053-22
      • Number Of Outputs : 1 digital
      • Communication Port Protocol : Modbus RTU and ASCII 9.6, 19.2 and 38.4 kbauds even/odd or none - 2 wires 2500 V || JBUS
      • Communication Port Support : RS485
      • Data Recording : Time stamping || Min/max of instantaneous values
      • Connections - Terminals : Voltage circuit screw terminal block4 || Control circuit screw terminal block2 || Current transformer screw terminal block6 || Input/output circuit screw terminal block6 || RS485 link screw terminal block4
      • Mounting Mode : Flush-mounted
      • Mounting Support : Framework
      • Standards : UL 61010-1 || EN 50470-3 || EN 50470-1 || IEC 62053-22 || IEC 60529 || IEC 62053-24 || IEC 61557-12
      • Product Certifications : CE IEC 61010-1 || CULus UL 61010-1
      • Width : 3.78 in (96 mm)
      • Depth : 2.83 in (72 mm)
      • Height : 3.78 in (96 mm)
      • Product Weight : 13.40 oz (380 g)
    • Environment
      • Electromagnetic Compatibility : Limits for harmonic current emissionsclass A IEC 61000-3-2 || Electrostatic dischargelevel 4 IEC 61000-4-2 || Conducted RF disturbanceslevel 3 IEC 61000-4-6 || Magnetic field at power frequencylevel 4 IEC 61000-4-8 || Conducted and radiated emissionsclass B EN 55022
      • IP Degree Of Protection : Front IP52 IEC 60529 || Body IP30 IEC 60529
      • Relative Humidity : 5…95 % 122 °F (50 °C)
      • Pollution Degree : 2
      • Ambient Air Temp For Op : -13…158 °F (-25…70 °C)
      • Ambient Air Temp For Storage : -40…185 °F (-40…85 °C)
      • Operating Altitude : 6561.68 ft (2000 m)
    • Ordering And Shipping Details
      • Category : 09777 - POWERLOGIC PM5000 HARDWARE
      • Discount Schedule : PL1
      • GTIN : 00785901869535
      • Nbr. Of Units In Pkg. : 1
      • Returnability : Yes
      • Country Of Origin : IN
    • Offer Sustainability
      • EU RoHs Directive : Compliant
      • Mercury Free : Yes
      • WEEE : The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.