Certifications:
CE EN 61557-12 Power Monitor), CE EN/IEC 61326-1 EMC), CE IEC 61010-1 Safety), CULus EN 61010-1 Safety), CULus UL 61010-1 Safety), EAC Sub-meter), RCM, UKCA BS EN 61010-1 Safety), UKCA BS EN 61326-1 EMC), UKCA BS EN 61557-12 Power Monitor)
-
Depth:
70 mm
-
Height:
95 mm
-
Line Rated Current:
1 A, 5 A
-
Mounting Type:
Clip-On
-
Net Weight:
0.26 kg
-
Number of Outputs:
0
-
Standard:
ANSI C12.20, BS EN 61010-1, BS EN 61010-2-30, BS EN 61326-1, BS EN 61557-12, BS EN 62052-11, BS EN 62053-21, BS EN 62053-22, BS EN 62053-23, EN 61010-1, EN 61010-2-30, EN 61326-1, EN 61557-12, EN 62052-11, EN 62052-22, EN 62052-23, EN 62053-21, IEC 61010-1, IEC 61010-2-30, IEC 61326-1, IEC 61557-12, IEC 62052-11, IEC 62053-21, IEC 62053-22, IEC 62053-23, UL 61010-1, UL 61010-2-30
-
Storage Temperature:
-40-85 °C
-
Warranty Length:
18 mth
-
Width:
90 mm
PM3200 DIN mount energy meter with a 128 by 96 pixel backlit, LCD display. The meter provides Class 0.5S accuracy per IEC 62053-22 standard and 32 samples per cycle. The meter will measure Energy, Active and Reactive Power, Voltage, Current, Frequency, Power Factor, Apparent Power and up to 15th Harmonic. The meter will function in a 50Hz or 60Hz network and accepts supply voltage ranging from 100 to 277VAC, 173 to 480VAC and 100 to 300VDC. Line rated current for this meter is 1A or 5A input and will support Single Phase, Single Phase and Neutral or Three Phase configurations. Direct measurement range is 50 to 570VAC, with an external VT 570 to 999000VAC. The range of measurement voltage between Phases is 80 to 570VAC at 45 to 65 Hz. Measurement range between Phase and Neutral is 50 to 330VAC at 45 to 65 Hz. This meter has no communication input or output capability. Product dimensions are as follows: width 3.54 in (90 mm), depth 2.76in (70 mm), height 3.74 in (95 mm) and product weight 9.17 oz (260 g).