PM3200 power meter

PM3200 power meter

SQDMETSEPM3200 METSEPM3200 360648048158
0.00 / EA
  • Amperage: 5 A
  • Certifications: CE EN 61010-1, CULus UL 61010-1, UL
  • Depth: 2.76 in, 70 mm
  • Height: 3.74 in, 95 mm
  • Mounting Type: Clip-On
  • Number of Outputs: 0
  • Standard: EN 50470-1, EN 50470-3, EN 61010-1, EN 61557-12, IEC 61557-12, IEC 62052-11, UL 61010-1
  • Weight: 0.26 kg, 0.57 lbs
  • Width: 3.54 in, 90 mm
PM3200 DIN mount energy meter with a 128 by 96 pixel backlit, LCD display. The meter provides Class 0.5S accuracy per IEC 62053-22 standard and 32 samples per cycle. The meter will measure Energy, Active and Reactive Power, Voltage, Current, Frequency, Power Factor, Apparent Power and up to 15th Harmonic. The meter will function in a 50Hz or 60Hz network and accepts supply voltage ranging from 100 to 277VAC, 173 to 480VAC and 100 to 300VDC. Line rated current for this meter is 1A or 5A input and will support Single Phase, Single Phase and Neutral or Three Phase configurations. Direct measurement range is 50 to 570VAC, with an external VT 570 to 999000VAC. The range of measurement voltage between Phases is 80 to 570VAC at 45 to 65 Hz. Measurement range between Phase and Neutral is 50 to 330VAC at 45 to 65 Hz. This meter has no communication input or output capability. Product dimensions are as follows: width 3.54 in (90 mm), depth 2.76in (70 mm), height 3.74 in (95 mm) and product weight 9.17 oz (260 g).
  • Product Description
  • Additional Information
PM3200 DIN mount energy meter with a 128 by 96 pixel backlit, LCD display. The meter provides Class 0.5S accuracy per IEC 62053-22 standard and 32 samples per cycle. The meter will measure Energy, Active and Reactive Power, Voltage, Current, Frequency, Power Factor, Apparent Power and up to 15th Harmonic. The meter will function in a 50Hz or 60Hz network and accepts supply voltage ranging from 100 to 277VAC, 173 to 480VAC and 100 to 300VDC. Line rated current for this meter is 1A or 5A input and will support Single Phase, Single Phase and Neutral or Three Phase configurations. Direct measurement range is 50 to 570VAC, with an external VT 570 to 999000VAC. The range of measurement voltage between Phases is 80 to 570VAC at 45 to 65 Hz. Measurement range between Phase and Neutral is 50 to 330VAC at 45 to 65 Hz. This meter has no communication input or output capability. Product dimensions are as follows: width 3.54 in (90 mm), depth 2.76in (70 mm), height 3.74 in (95 mm) and product weight 9.17 oz (260 g).
  • Specifications
    • Main
      • Range : PowerLogic
      • Product Name : PowerLogic PM3000
      • Device Short Name : PM3200
      • Product Or Component Type : Power meter
    • Complementary
      • Power Quality Analysis : up to the 15th harmonic
      • Device Application : Multi-tariff || Sub billing || Power monitoring
      • Type Of Measurement : Active and reactive power || Apparent power || Current || Voltage || Energy || Power factor || Frequency
      • Supply Voltage : 100...277 V AC 45...65 Hz || 173...480 V AC 45...65 Hz || 100...300 V DC
      • Network Frequency : 50 Hz || 60 Hz
      • In Rated Current : 5 A || 1 A
      • Type Of Network : 3P + N || 3P || 1P + N
      • Power Consumption In Va : 5 VA
      • Display Type : Backlit LCD
      • Display Resolution : 128 x 96 pixels
      • Sampling Rate : 32 samples/cycle
      • Measurement Current : 0.05…6 A || 0.02…1.2 A
      • Analogue Input Type : current 0...5 A || current 0...1 A
      • Measurement Voltage : 50…330 V AC 45...65 Hz direct || 50…330 V AC 45...65 Hz phase to neutral || 80…570 V AC 45...65 Hz direct || 80…570 V AC 45...65 Hz phase to phase || 570…999000 V AC 45...65 Hz with external VT
      • Frequency Measurement Range : 45…65 Hz
      • Number Of Inputs : 0
      • Measurement Accuracy : Current 0.3 % 0.5...6 A || Current 0.5 % 0.1...1.2 A || Voltage 0.3 % 50...330 V || Voltage 0.3 % 80...570 V
      • Accuracy Class : Class 0.5S active energy IEC 62053-22 || Class 1 active energy IEC 62053-21 || Class 2 reactive energy IEC 62053-23 || Class C active energy EN 50470-3
      • Number Of Outputs : 0
      • Information Displayed : Tariff 4)
      • Data Recording : Min/max of instantaneous values
      • Mounting Mode : Clip-on
      • Mounting Support : DIN rail
      • Standards : EN 61557-12 || EN 61010-1 || IEC 61557-12 || EN 50470-3 || UL 61010-1 || EN 50470-1 || IEC 62052-11
      • Product Certifications : CE EN 61010-1 || CULus UL 61010-1 || UL
      • Width : 3.54 in (90 mm)
      • Depth : 2.76 in (70 mm)
      • Height : 3.74 in (95 mm)
      • Product Weight : 0.57 lb(US) (0.26 kg)
    • Environment
      • Electromagnetic Compatibility : Electrostatic dischargelevel 4 IEC 61000-4-2 || Susceptibility to electromagnetic fieldslevel 3 IEC 61000-4-3 || Electrical fast transient/burst immunity testlevel 4 IEC 61000-4-4 || 1.2/50 µs shock waves immunity testlevel 4 IEC 61000-4-5 || Conducted RF disturbanceslevel 3 IEC 61000-4-6 || Magnetic field at power frequency 0.5 mT IEC 61000-4-8 || Conducted and radiated emissionsclass B EN 55022
      • Overvoltage Category : III
      • IP Degree Of Protection : Front panel IP40 IEC 60529 || Body IP20 IEC 60529
      • Relative Humidity : 5…95 % 122 °F (50 °C)
      • Pollution Degree : 2
      • Ambient Air Temp For Op : -13…131 °F (-25…55 °C)
      • Ambient Air Temp For Storage : -40…185 °F (-40…85 °C)
      • Operating Altitude : 0...9842.52 ft (0...3000 m)
    • Ordering And Shipping Details
      • Category : 09786 - SE ENTRY POWER METER
      • Discount Schedule : PL1
      • GTIN : 03606480481581
      • Nbr. Of Units In Pkg. : 1
      • Returnability : No
      • Country Of Origin : CN
    • Offer Sustainability
      • Green Premium Status : Green Premium product
      • EU RoHs Directive : Compliant
      • Mercury Free : Yes
      • WEEE : The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
    • Contractual Warranty
      • Warranty : 18 months