Schneider Electric at Mayer

Residual current circuit breaker (RCCB), Multi9 GFP, 2P, 40A, A-SI type, 30mA, 480Y/277VAC

MULTI9 GFP 2P 40A 26MA A 480Y/

SQDM9R41240 M9R41240 3606481198495
730.32 / EA
http://schema.org/OutOfStock
  • Country of Origin: USA
  • Depth: 60 mm
  • IsSustainable: No
This is a Multi GFP residual current circuit breaker (RCCB). It is a 2P circuit breaker with In rated current of 40A, A-SI type protection class and a 26mA earth leakage sensitivity. It protects persons against electric shock by direct contact. It also protects installations against fire risks. The tripping upon fault is indicated by a red mechanical status indicator on the front panel. The A-SI type offers enhanced immunity to electrical disturbances. This product is dedicated to original equipment manufacturers (OEM) and control panel builders in indisutrial and tertiary buildings. It is compliant with IEC/EN 61008-1 standard. The (Im/IΔm) rated breaking and making short circuit capacity is 1500A. The (Inc/IΔc) conditional rated short circuit current is 10kA. It has a mechanical endurance going up to 20000 cycles. The Ue operational voltage is 240VAC. The Ui rated insulation voltage is 440VAC. The Uimp rated impulse withstand voltage is 6kV. The frequency is 50Hz or 60Hz. It is DIN rail mountable. The width in 9mm pitches is 4. The product colour is light grey (RAL7035). The dimensions are (W) 36mm x (H) 81mm x (D) 60mm. The weight is 0.22kg. It has an IP20 degree of protection. It becomes IP40 once in modular enclosure according to IEC/EN 60529 standard. The operating temperature is from -25°C to 60°C. The storage temperature is from -40°C to 70°C.
QTY
  • Specifications
  • Assets
    • Cad : https://download.schneider-electric.com/files?p_Doc_Ref=MCADFD0002518_3D-CAD
  • Physical Attributes
    • Color : Gray
    • Wire Stripping Length : 14 mm for top or bottom connection
  • Conformance Attributes
    • Product Certifications : IEC, UL
    • Standards : EN/IEC 61008-1, UL 1053
  • Complementary Attributes
    • Ue Rated Operational Voltage : 480Y/277 V AC 60 Hz, 240/415 V AC 50 Hz
    • Line Rated Current : 40 A 40 °C EN/IEC 61008-1
    • Rated Breaking And Making Capacity : Idm 1500 A EN/IEC 61008-1
    • Rated Conditional Short Circuit Current : Inc 10 kA 100 A gG
    • Ui Rated Insulation Voltage : 440 V AC 50/60 Hz
    • Uimp Rated Impulse Withstand Voltage : 6 kVEN/IEC 61008-1
  • Important Information Attributes
    • Persona Type Ids : EU, OM, OM8
    • Persona Type Names : End User, Original Equipment Manufacturer, OEM - Control Panelbuilder
    • Earth Leakage Sensitivity : 26 mA UL 1053, 30 mA EN/IEC 61008-1
    • Poles Description : 2P, 2P
    • Connections Terminals : tunnel type terminals (top or bottom)1-25 mm² (AWG 18...AWG 3) - flexible, tunnel type terminals (top or bottom)1-35 mm² (AWG 18...AWG 2) - rigid, tunnel type terminals (top or bottom)1-25 mm² (AWG 18...AWG 3) - flexible with ferrule
    • Carbon Footprint Of The Distribution Phase A4 : 0.0364069023692282, 0 kg CO2 eq.
    • Carbon Footprint Of The End Of Life Phase C1 To C4 : 0.679389575001311, 0.7 kg CO2 eq.
    • Carbon Footprint Of The Installation Phase A5 : 0 kg CO2 eq., 0.0163089293723848
    • Carbon Footprint Of The Manufacturing Phase A1 To A3 : 3 kg CO2 eq., 2.65180023010561
    • Carbon Footprint Of The Use Phase B2 B3 B4 B6 : 39 kg CO2 eq., 38.7766666666666
    • Medium Desc : Residual current circuit breaker (RCCB), Multi9 GFP, 2P, 40A, A-SI type, 30mA, 480Y/277VAC
    • Local Data Status : Publishable
    • Local Publishable Date : 2025-08-13
    • Global Commercial Status : Commercialised
    • Return Indicator : Y
    • Stocking Flag : N
    • H And D Domain : Safety
    • H And D Subrange : Multi9 GFP XM RCCB UL
    • H And D Enrichment Assignment : yes
    • H And D Enrichment Function : RCCB
    • H And D Enrichment Class 3 : Earth leakage protection devices
    • H And D Enrichment Class 4 : RCCB
    • H And Dod Responsibility : Multi9
    • H And Dod Platform : RCD&Switches
    • Device Type : LV equipment - Low voltage circuit breaker
    • Serviceability : No
    • Traceability : No
    • Field Service Division : PPIBS
    • Average Life Duration : 15 year(s)
    • Legacy Weee Scope : In
    • Scope Perimeter : At least in Europe
    • Eoli Availability Display : No need of specific recycling operations
    • Reach Full Compliance Status : Reference contains Substances of Very High Concern above the threshold
    • Reach Full Compliance Status Id : CONTAINS_SVHC
    • Reach Compliance Directive : Reference contains Substances of Very High Concern above the threshold
    • Rohs Eur In Scope : Yes
    • Rohs Eur Status : Compliant By Exemption
    • Rohs Eur Full Compliance Status : Compliant By Exemption
    • China Rohs In Scope : Yes
    • With Recycled Cardboard : Yes
    • Without Single Use Plastic : Yes
    • Product Contributes To Saved And Avoided Emissions : No
    • Function Option Id : STANDARD
    • Function Option : Standard
    • Market Segmentation Id : COMMERCIAL
    • Market Segmentation : Commercial
    • Product Kit Identifier : N
    • Connection Pitch : 18 mm between phases
    • Contact Position Indicator : yes
    • Control Type : toggle
    • Device Application : distribution
    • Device Short Name : GFP
    • Earth Leakage Protection Class : type A-SI (Super Immunised)
    • Earth Leakage Protection Time Delay : instantaneous
    • Electromagnetic Compatibility : 8/20 µs impulse withstand, 3000 A EN/IEC 61008-1
    • Energy Efficiency Optimized : False
    • Halogen Free Status : Product contains halogen above thresholds
    • Local Signalling : ON, OFF, fault trip
    • Locking Options Description : padlocking in OFF position
    • Mechanical Durability : 20000 cycles
    • Mounting Mode : clip-on
    • Mounting Support : DIN rail
    • Network Frequency : 50/60 Hz
    • Network Type : AC
    • Neutral Position : left
    • Power Losses Per Pole : 3.6 W
    • Product Availability : Stock - Normally stocked in distribution facility
    • Product Name : Multi9 GFP
    • Product Or Component Type : residual current circuit breaker (RCCB)
    • Range : Multi9
    • Range Of Product : Multi9
    • Residual Current Tripping Technology : voltage independent
    • Returnability : Yes
    • Software Version : v5.9.4
    • Sustainable Packaging : Yes
    • Tightening Torque : 3.5-3.5 N.m top or bottom
    • Total Lifecycle Carbon Footprint : 42 kg CO2 eq.
    • Total Power Losses : 7.2 W
    • Tropicalisation : 2 IEC 60068-1
    • Utilisation Category : AC-23A EN/IEC 61008-1
    • Weee Label : The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
    • Rated Current 3 : 40 A
    • Earth Leakage Sensitivity 1 : 30 mA
    • Pep Code : ENVPEP2301023_V1-EN
    • Database Version : 2022-01
    • Pep Verification Date : 2025-04-20
    • Pcr Version : PEP-PCR-ed4-2021 09 06
    • Psr Version : PSR-0005-ed2-2016 03 29
    • Type Of Verification For The Pep : Independent external review
    • Data Source : extrapolated product
    • Functional Unit Description : Protect during 20 years the installation against overloads and short-circuits and people and premises at risk of fire or explosion against insulation defects in circuit with assigned voltage 400V and rated current 40A. This protection is ensured in accordance with the following parameters:& 10- Number of poles 4& 10- Sensitivity 300mA& 10- Type of differential protection AC
    • Functional Unit Unit : Unit
    • Energy Model Manufacturing A1 A3 2 : Electricity Mix; Low voltage; 2018; Spain, SP
    • Energy Model Installation A5 2 : Electricity Mix; Production mix; Low voltage; UE-27
    • Energy Model Use B6 2 : Electricity Mix; Production mix; Low voltage; UE-27
    • Energy Model End Of Life C1 C4 2 : Electricity Mix; Production mix; Low voltage; UE-27
    • Height Nominal : 81 mm
    • Width Nominal : 36 mm
  • Environment Attributes Main
    • Ambient Air Temperature For Operation : -25-60 °C, -25-60 °C
    • Ip Degree Of Protection : IP20 conforming to IEC 60529, IP40 (modular enclosure) conforming to IEC 60529
    • Take Back : Nej
    • Halogene Performance : Product contains halogen above thresholds
    • Recycled Metal Content At Cr Level : 0 %
    • China Rohs Regulation : X
    • Mercury Free : Yes
    • Carbon Footprint : 42.1605723035152
    • 9 Mm Pitches : 4
    • Ambient Air Temperature For Storage : -40-70 °C
    • Environmental Disclosure : ENVPEP2301023_V1-EN
    • Eu Rohs Directive : Compliant By Exemption
    • Halogen Content Performance : Product contains halogen above thresholds
    • Packaging Made With Recycled Cardboard : Yes
    • Packaging Without Single Use Plastic : Yes
    • Reach Regulation : Reference contains Substances of Very High Concern above the threshold
    • Relative Humidity : 95-95 % 55-55 °C
    • Pep Code : ENVPEP2301023_V1-EN
    • Pep Verification Date : 2025-04-20
    • Pcr Version : PEP-PCR-ed4-2021 09 06
    • Psr Version : PSR-0005-ed2-2016 03 29
    • Type Of Verification For The Pep : Independent external review
  • General Attributes
    • Product Or Component Type : residual current circuit breaker (RCCB)
    • Range Of Product : Multi9
  • ETIM
    • ETIM 8 : EC000003
    • ETIM 9 : EC000003
  • Specifications
    • Country of Origin : United States
    • Depth : 60 mm