Multi9 - C60SP - MCB - 3P - 40 A - B Curve - 480Y/277 V - 5 kA - UL 1077

MULTI9 C60SP 3P B 40A MCB

SQDM9F21340 M9F21340 785901738190
182.37 / EA
  • Certifications: CCC, CSA, IEC, UR
  • Depth: 72 mm
  • Height: 81 mm
  • Line Rated Current: 25 °C, 40 A
  • Mounting Type: Clip-On
  • Operating Temperature: -30-70 °C
  • Standard: CSA C22.2 No 235, EN/IEC 60947-2, GB 14048.2, UL 1077
  • Storage Temperature: -40-80 °C
  • Strip Length: 14 mm
  • Width: 54 mm
This Multi9 C60SP is a low voltage miniature circuit breaker (MCB). It is a 3P circuit breaker with 3 protected poles, 40A rated current and B tripping curve. The rated short circuit breaking capacity goes up to 10kA at 415VAC conforming to EN/IEC 60947-2 standard and 10kA at 415VAC conforming to EN/IEC 60947-2 standard. This product complies with both industrial standard EN/IEC 60898-1 and residential standard EN/IEC 60947-2. It has been designed to offer enhanced protection by preventing, protecting people and equipment from electrical threats. This product protects from short circuit, earth leakage and overload. This product is dedicated for original equipment manufacturers (OEM) and control panel builders. It has an electrical endurance going up to 10000 cycles and a mechanical endurance going up to 20000 cycles. The Ue operational voltage is 240VAC. The Ui rated insulation voltage is 500VAC. The Uimp rated impulse withstand voltage is 6kV. The product can be clipped on a DIN rail. Its width is 6 pitches of 9mm. Pollution degree is 3. The product colour is light grey (RAL7035). The dimensions are (W) 54mm x (H) 81mm x (D) 72mm. It has an IP20 degree of protection (as per IEC/EN 60529) on its terminals. The operating temperature is -30°C to 70°C. The storage temperature is -40°C to 80°C.
  • Product Description
  • Specifications
This Multi9 C60SP is a low voltage miniature circuit breaker (MCB). It is a 3P circuit breaker with 3 protected poles, 40A rated current and B tripping curve. The rated short circuit breaking capacity goes up to 10kA at 415VAC conforming to EN/IEC 60947-2 standard and 10kA at 415VAC conforming to EN/IEC 60947-2 standard. This product complies with both industrial standard EN/IEC 60898-1 and residential standard EN/IEC 60947-2. It has been designed to offer enhanced protection by preventing, protecting people and equipment from electrical threats. This product protects from short circuit, earth leakage and overload. This product is dedicated for original equipment manufacturers (OEM) and control panel builders. It has an electrical endurance going up to 10000 cycles and a mechanical endurance going up to 20000 cycles. The Ue operational voltage is 240VAC. The Ui rated insulation voltage is 500VAC. The Uimp rated impulse withstand voltage is 6kV. The product can be clipped on a DIN rail. Its width is 6 pitches of 9mm. Pollution degree is 3. The product colour is light grey (RAL7035). The dimensions are (W) 54mm x (H) 81mm x (D) 72mm. It has an IP20 degree of protection (as per IEC/EN 60529) on its terminals. The operating temperature is -30°C to 70°C. The storage temperature is -40°C to 80°C.
  • Magnetic Tripping Limit : 4 x In +/- 20 % AC
  • Number Of Protected Poles : 3
  • Maximum Depth : 72 mm
  • 9 Mm Pitches : 6
  • Range Of Product : Multi 9
  • Product Name : Multi 9 C60
  • Trip Unit Technology : thermal-magnetic
  • Curve Code : B
  • Maximum Width : 54 mm
  • Mounting Support : DIN rail
  • [Ics] Rated Service Breaking Capacity : 4.5 kA 75 % EN/IEC 60947-2 - 440 V AC || 7.5 kA 75 % EN/IEC 60947-2 - 415 V AC || 15 kA 75 % EN/IEC 60947-2 - 240 V AC || 4.5 kA 75 % GB 14048.2 - 440 V AC || 7.5 kA 75 % GB 14048.2 - 415 V AC || 15 kA 75 % GB 14048.2 - 240 V AC
  • Maximum Height : 81 mm
  • Contact Position Indicator : yes
  • Range : Multi 9
  • Wire Stripping Length : 14 mm top or bottom
  • Product Certifications : IEC || CCC || UR || CSA
  • Ambient Air Temperature For Operation : -30-70 °C
  • Provision For Padlocking : padlockable
  • Local Signalling : ON/OFF indication
  • Network Type : AC
  • Earth-Leakage Protection : without
  • [Ui] Rated Insulation Voltage : 500 V AC EN/IEC 60947-2
  • Color : Gray
  • Ip Degree Of Protection : IP20IEC 60529 || IP40 modular enclosure)IEC 60529
  • Line Rated Current : 40 A 25 °C EN/IEC 60947-2
  • Connections - Terminals : tunnel type terminal top or bottom) 1-35 mm² AWG 18...AWG 2) - rigid || tunnel type terminal top or bottom) 1-25 mm² AWG 18...AWG 3) - flexible with ferrule || tunnel type terminal top or bottom) 1-25 mm² AWG 18...AWG 3) - flexible
  • Device Short Name : C60SP
  • Relative Humidity : 95-95 % 55-55 °C
  • Poles Description : 3P
  • Mechanical Durability : 20000 cycles
  • Ambient Air Temperature For Storage : -40-80 °C
  • Operating Altitude : 0...6561.68 ft (0...2000 m)
  • Tightening Torque : 3.5-3.5 N.m top or bottom
  • Pollution Degree : 3 EN/IEC 60947-2
  • Electrical Durability : 10000 cycles
  • Mounting Mode : clip-on
  • Standards : EN/IEC 60947-2 || GB 14048.2 || UL 1077 || CSA C22.2 No 235
  • Product Or Component Type : miniature circuit-breaker
  • Tropicalisation : 2 IEC 60068-1
  • [Ue] Rated Operational Voltage : 240 V AC 50/60 Hz || 415 V AC 50/60 Hz || 440 V AC 50/60 Hz
  • Control Type : toggle
  • [Uimp] Rated Impulse Withstand Voltage : 6 kVEN/IEC 60947-2
  • Breaking Capacity : 10 kA AIR 240 V AC UL 1077 || 10 kA AIR 240 V AC CSA C22.2 No 235 || 6 kA Icu 440 V AC EN/IEC 60947-2 || 10 kA Icu 415 V AC EN/IEC 60947-2 || 20 kA Icu 240 V AC EN/IEC 60947-2 || 6 kA Icu 440 V AC GB 14048.2 || 10 kA Icu 415 V AC GB 14048.2 || 20 kA Icu 240 V AC GB 14048.2 || 5 kA AIR 480Y/277 V AC UL 1077 || 5 kA AIR 480Y/277 V AC CSA C22.2 No 235
  • Device Application : distribution
  • Suitability For Isolation : yes EN/IEC 60947-2