Schneider Electric at Mayer

Multi9 - C60SP - MCB - 2P - 40 A - C Curve - 480Y/277 V - 5 kA - UL 1077

MULTI9 C60SP 2P C 40A MCB

SQDM9F22240 M9F22240 785901736745
126.09 / EA
  • Certifications: CCC, CSA, IEC, UR
  • Depth: 72 mm
  • Height: 81 mm
  • Line Rated Current: 25 °C, 40 A
  • Mounting Type: Clip-On
  • Operating Temperature: -30-70 °C
  • Standard: CSA C22.2 No 235, EN/IEC 60947-2, GB 14048.2, UL 1077
  • Storage Temperature: -40-80 °C
  • Strip Length: 14 mm
  • Width: 36 mm
This Multi9 C60SP is a low voltage miniature circuit breaker (MCB). It is a 2P circuit breaker with 2 protected poles, 40A rated current and C tripping curve. The rated short circuit breaking capacity goes up to 10kA at 415VAC conforming to EN/IEC 60947-2 standard and 10kA at 415VAC conforming to EN/IEC 60947-2 standard. This product complies with both industrial standard EN/IEC 60898-1 and residential standard EN/IEC 60947-2. It has been designed to offer enhanced protection by preventing, protecting people and equipment from electrical threats. This product protects from short circuit, earth leakage and overload. This product is dedicated for original equipment manufacturers (OEM) and control panel builders. It has an electrical endurance going up to 10000 cycles and a mechanical endurance going up to 20000 cycles. The Ue operational voltage is 240VAC. The Ui rated insulation voltage is 500VAC. The Uimp rated impulse withstand voltage is 6kV. The product can be clipped on a DIN rail. Its width is 4 pitches of 9mm. Pollution degree is 3. The product colour is light grey (RAL7035). The dimensions are (W) 36mm x (H) 81mm x (D) 72mm. It has an IP20 degree of protection (as per IEC/EN 60529) on its terminals. The operating temperature is -30°C to 70°C. The storage temperature is -40°C to 80°C.
  • Product Description
  • Specifications
This Multi9 C60SP is a low voltage miniature circuit breaker (MCB). It is a 2P circuit breaker with 2 protected poles, 40A rated current and C tripping curve. The rated short circuit breaking capacity goes up to 10kA at 415VAC conforming to EN/IEC 60947-2 standard and 10kA at 415VAC conforming to EN/IEC 60947-2 standard. This product complies with both industrial standard EN/IEC 60898-1 and residential standard EN/IEC 60947-2. It has been designed to offer enhanced protection by preventing, protecting people and equipment from electrical threats. This product protects from short circuit, earth leakage and overload. This product is dedicated for original equipment manufacturers (OEM) and control panel builders. It has an electrical endurance going up to 10000 cycles and a mechanical endurance going up to 20000 cycles. The Ue operational voltage is 240VAC. The Ui rated insulation voltage is 500VAC. The Uimp rated impulse withstand voltage is 6kV. The product can be clipped on a DIN rail. Its width is 4 pitches of 9mm. Pollution degree is 3. The product colour is light grey (RAL7035). The dimensions are (W) 36mm x (H) 81mm x (D) 72mm. It has an IP20 degree of protection (as per IEC/EN 60529) on its terminals. The operating temperature is -30°C to 70°C. The storage temperature is -40°C to 80°C.
  • Local Signalling : ON/OFF indication
  • Relative Humidity : 95-95 % 55-55 °C
  • Ambient Air Temperature For Operation : -30-70 °C
  • Mounting Mode : clip-on
  • Connections - Terminals : tunnel type terminal top or bottom) 1-35 mm² AWG 18...AWG 2) - rigid || tunnel type terminal top or bottom) 1-25 mm² AWG 18...AWG 3) - flexible with ferrule || tunnel type terminal top or bottom) 1-25 mm² AWG 18...AWG 3) - flexible
  • Wire Stripping Length : 14 mm top or bottom
  • Pollution Degree : 3 EN/IEC 60947-2
  • Product Certifications : IEC || CCC || UR || CSA
  • Electrical Durability : 10000 cycles
  • Maximum Width : 36 mm
  • Ambient Air Temperature For Storage : -40-80 °C
  • Trip Unit Technology : thermal-magnetic
  • Control Type : toggle
  • Maximum Height : 81 mm
  • Standards : EN/IEC 60947-2 || GB 14048.2 || UL 1077 || CSA C22.2 No 235
  • Number Of Protected Poles : 2
  • Product Name : Multi 9 C60
  • Poles Description : 2P
  • Curve Code : C
  • Mechanical Durability : 20000 cycles
  • Maximum Depth : 72 mm
  • Contact Position Indicator : yes
  • Line Rated Current : 40 A 25 °C EN/IEC 60947-2
  • [Ui] Rated Insulation Voltage : 500 V AC EN/IEC 60947-2
  • [Ics] Rated Service Breaking Capacity : 4.5 kA 75 % EN/IEC 60947-2 - 440 V AC || 7.5 kA 75 % EN/IEC 60947-2 - 415 V AC || 15 kA 75 % EN/IEC 60947-2 - 240 V AC || 4.5 kA 75 % GB 14048.2 - 440 V AC || 7.5 kA 75 % GB 14048.2 - 415 V AC || 15 kA 75 % GB 14048.2 - 240 V AC
  • Device Application : distribution
  • Magnetic Tripping Limit : 8.5 x In +/- 20 % AC
  • Provision For Padlocking : padlockable
  • Range Of Product : Multi 9
  • Tropicalisation : 2 IEC 60068-1
  • Mounting Support : DIN rail
  • 9 Mm Pitches : 4
  • Tightening Torque : 3.5-3.5 N.m top or bottom
  • Device Short Name : C60SP
  • Product Or Component Type : miniature circuit-breaker
  • Ip Degree Of Protection : IP20IEC 60529 || IP40 modular enclosure)IEC 60529
  • Network Type : AC
  • Operating Altitude : 0...6561.68 ft (0...2000 m)
  • [Uimp] Rated Impulse Withstand Voltage : 6 kVEN/IEC 60947-2
  • Range : Multi 9
  • [Ue] Rated Operational Voltage : 240 V AC 50/60 Hz || 415 V AC 50/60 Hz || 440 V AC 50/60 Hz
  • Earth-Leakage Protection : without
  • Breaking Capacity : 10 kA AIR 240 V AC UL 1077 || 10 kA AIR 240 V AC CSA C22.2 No 235 || 6 kA Icu 440 V AC EN/IEC 60947-2 || 10 kA Icu 415 V AC EN/IEC 60947-2 || 20 kA Icu 240 V AC EN/IEC 60947-2 || 6 kA Icu 440 V AC GB 14048.2 || 10 kA Icu 415 V AC GB 14048.2 || 20 kA Icu 240 V AC GB 14048.2 || 5 kA AIR 480Y/277 V AC UL 1077 || 5 kA AIR 480Y/277 V AC CSA C22.2 No 235
  • Suitability For Isolation : yes EN/IEC 60947-2
  • Color : Gray