Multi9 - C60N - MCB - 3P - 32 A - C Curve - 415 V - 10 kA

Multi9 - C60N - MCB - 3P - 32 A - C Curve - 415 V - 10 kA

SQDM9F11332 M9F11332 785901168287
299.01 / EA
  • Certifications: CCC, EAC, KC
  • Depth: 72 mm
  • Height: 81 mm
  • Line Rated Current: 32 A, 50 °C
  • Net Weight: 0.36 kg
  • Operating Temperature: -30-70 °C
  • Standard: EN/IEC 60947-2
  • Storage Temperature: -40-80 °C
  • Strip Length: 14 mm
  • Width: 54 mm
This Multi9 C60N is a low voltage miniature circuit breaker (MCB). It is a 3P circuit breaker with 3 protected poles, 32A rated current and C tripping curve. The rated short circuit breaking capacity goes up to 10kA at 415VAC conforming to EN/IEC 60947-2 standard. This product complies with both industrial standard EN/IEC 60898-1 and residential standard EN/IEC 60947-2. It has been designed to offer enhanced protection by preventing, protecting people and equipment from electrical threats. This product protects from short circuit, earth leakage and overload. Its fast closing mechanism, overvolatge resistance and high performance limitation improve its service life. This product is dedicated for original equipment manufacturers (OEM) and control panel builders. It has an electrical endurance going up to 10000 cycles and a mechanical endurance going up to 20000 cycles. The Ue operational voltage is 240VAC. The Ui rated insulation voltage is 500VAC. The Uimp rated impulse withstand voltage is 6kV. The operating frequency is 50Hz or 60Hz. The product can be clipped on a DIN rail. Its width is 6 pitches of 9mm. Pollution degree is 3. Overvoltage category is IV. The product colour is light grey (RAL7035). The dimensions are (W) 54mm x (H) 81mm x (D) 72mm. The weight is 0.36kg. It has an IP20 degree of protection (as per IEC/EN 60529) on its terminals. The operating temperature is -30°C to 70°C. The storage temperature is -40°C to 80°C.
  • Product Description
  • Specifications
This Multi9 C60N is a low voltage miniature circuit breaker (MCB). It is a 3P circuit breaker with 3 protected poles, 32A rated current and C tripping curve. The rated short circuit breaking capacity goes up to 10kA at 415VAC conforming to EN/IEC 60947-2 standard. This product complies with both industrial standard EN/IEC 60898-1 and residential standard EN/IEC 60947-2. It has been designed to offer enhanced protection by preventing, protecting people and equipment from electrical threats. This product protects from short circuit, earth leakage and overload. Its fast closing mechanism, overvolatge resistance and high performance limitation improve its service life. This product is dedicated for original equipment manufacturers (OEM) and control panel builders. It has an electrical endurance going up to 10000 cycles and a mechanical endurance going up to 20000 cycles. The Ue operational voltage is 240VAC. The Ui rated insulation voltage is 500VAC. The Uimp rated impulse withstand voltage is 6kV. The operating frequency is 50Hz or 60Hz. The product can be clipped on a DIN rail. Its width is 6 pitches of 9mm. Pollution degree is 3. Overvoltage category is IV. The product colour is light grey (RAL7035). The dimensions are (W) 54mm x (H) 81mm x (D) 72mm. The weight is 0.36kg. It has an IP20 degree of protection (as per IEC/EN 60529) on its terminals. The operating temperature is -30°C to 70°C. The storage temperature is -40°C to 80°C.
  • Product Name : Multi 9 C60
  • Network Type : DC || AC
  • Standards : EN/IEC 60947-2
  • Device Short Name : C60N
  • [Ui] Rated Insulation Voltage : 500 V AC 50/60 Hz EN/IEC 60947-2
  • Tightening Torque : 3.5-3.5 N.m top or bottom
  • Maximum Depth : 72 mm
  • Suitability For Isolation : yes EN/IEC 60947-2
  • Overvoltage Category : IV
  • Wire Stripping Length : 14 mm top or bottom
  • Ip Degree Of Protection : IP20IEC 60529 || IP40 modular enclosure)IEC 60529
  • [Ics] Rated Service Breaking Capacity : 7.5 kA 75 % EN/IEC 60947-2 - 415 V AC 50/60 Hz || 16 kA 75 % EN/IEC 60947-2 - 240 V AC 50/60 Hz || 4.5 kA 75 % EN/IEC 60947-2 - 440 V AC 50/60 Hz || 30 kA 100 % EN/IEC 60947-2 - <= 125 V DC
  • Control Type : toggle
  • Mechanical Durability : 20000 cycles
  • Contact Position Indicator : yes
  • Magnetic Tripping Limit : 8.5 x In +/- 20 % AC || 12 x In +/- 20 % DC
  • Mounting Support : DIN rail
  • 9 Mm Pitches : 6
  • Provision For Padlocking : padlockable
  • [Uimp] Rated Impulse Withstand Voltage : 6 kVEN/IEC 60947-2
  • Connections - Terminals : tunnel type terminal top or bottom) 1.5-35 mm² - rigid || tunnel type terminal top or bottom) 1.5-35 mm² - flexible || tunnel type terminal top or bottom) 1.5-35 mm² - flexible with ferrule
  • Breaking Capacity : 30 kA Icu <= 125 V DC EN/IEC 60947-2 || 10 kA Icu 415 V AC 50/60 Hz between phases EN/IEC 60947-2 || 20 kA Icu 240 V AC 50/60 Hz between phases EN/IEC 60947-2 || 6 kA Icu 440 V AC 50/60 Hz between phases EN/IEC 60947-2
  • Ambient Air Temperature For Operation : -30-70 °C
  • Line Rated Current : 32 A 50 °C EN/IEC 60947-2
  • Range : Multi 9
  • Range Of Product : Multi 9
  • Limitation Class : 3
  • Maximum Width : 54 mm
  • Number Of Protected Poles : 3
  • [Ue] Rated Operational Voltage : 240 V AC 50/60 Hz between phases || 415 V AC 50/60 Hz between phases || 440 V AC 50/60 Hz between phases || <= 125 V DC
  • Device Application : distribution
  • Pollution Degree : 3 EN/IEC 60947-2
  • Product Certifications : EAC || KC || CCC
  • Curve Code : C
  • Relative Humidity : 95-95 % 55-55 °C
  • Poles Description : 3P
  • Earth-Leakage Protection : separate block
  • Product Or Component Type : miniature circuit-breaker
  • Tropicalisation : 2 IEC 60068-1
  • Breaking Capacity Code : N
  • Utilisation Category : category A EN/IEC 60947-2
  • Heat Dissipation : 10.5-10.5 W 415 V - 32 A
  • Mounting Mode : clip-on
  • Local Signalling : ON/OFF indication
  • Ambient Air Temperature For Storage : -40-80 °C
  • Maximum Height : 81 mm
  • Network Frequency : 50/60 Hz
  • Electrical Durability : 10000 cycles
  • Color : Gray
  • Net Weight : 0.36 kg
  • Trip Unit Technology : thermal-magnetic