Multi9 - C60N - MCB - 2P - 6 A - D Curve - 415 V - 10 kA

Multi9 - C60N - MCB - 2P - 6 A - D Curve - 415 V - 10 kA

SQDM9F12206 M9F12206 360648057673
0.00 / EA
  • Certifications: CCC, EAC, KC
  • Depth: 72 mm
  • Height: 81 mm
  • Line Rated Current: 50 °C, 6 A
  • Net Weight: 0.24 kg
  • Operating Temperature: -30-70 °C
  • Standard: EN/IEC 60947-2
  • Storage Temperature: -40-80 °C
  • Strip Length: 14 mm
  • Width: 36 mm
This Multi9 C60N is a low voltage miniature circuit breaker (MCB). It is a 2P circuit breaker with 2 protected poles, 6A rated current and D tripping curve. The rated short circuit breaking capacity goes up to 10kA at 415VAC conforming to EN/IEC 60947-2 standard. This product complies with both industrial standard EN/IEC 60898-1 and residential standard EN/IEC 60947-2. It has been designed to offer enhanced protection by preventing, protecting people and equipment from electrical threats. This product protects from short circuit, earth leakage and overload. Its fast closing mechanism, overvolatge resistance and high performance limitation improve its service life. This product is dedicated for original equipment manufacturers (OEM) and control panel builders. It has an electrical endurance going up to 10000 cycles and a mechanical endurance going up to 20000 cycles. The Ue operational voltage is 240VAC. The Ui rated insulation voltage is 500VAC. The Uimp rated impulse withstand voltage is 6kV. The operating frequency is 50Hz or 60Hz. The product can be clipped on a DIN rail. Its width is 4 pitches of 9mm. Pollution degree is 3. Overvoltage category is IV. The product colour is light grey (RAL7035). The dimensions are (W) 36mm x (H) 81mm x (D) 72mm. The weight is 0.24kg. It has an IP20 degree of protection (as per IEC/EN 60529) on its terminals. The operating temperature is -30°C to 70°C. The storage temperature is -40°C to 80°C.
  • Product Description
  • Specifications
This Multi9 C60N is a low voltage miniature circuit breaker (MCB). It is a 2P circuit breaker with 2 protected poles, 6A rated current and D tripping curve. The rated short circuit breaking capacity goes up to 10kA at 415VAC conforming to EN/IEC 60947-2 standard. This product complies with both industrial standard EN/IEC 60898-1 and residential standard EN/IEC 60947-2. It has been designed to offer enhanced protection by preventing, protecting people and equipment from electrical threats. This product protects from short circuit, earth leakage and overload. Its fast closing mechanism, overvolatge resistance and high performance limitation improve its service life. This product is dedicated for original equipment manufacturers (OEM) and control panel builders. It has an electrical endurance going up to 10000 cycles and a mechanical endurance going up to 20000 cycles. The Ue operational voltage is 240VAC. The Ui rated insulation voltage is 500VAC. The Uimp rated impulse withstand voltage is 6kV. The operating frequency is 50Hz or 60Hz. The product can be clipped on a DIN rail. Its width is 4 pitches of 9mm. Pollution degree is 3. Overvoltage category is IV. The product colour is light grey (RAL7035). The dimensions are (W) 36mm x (H) 81mm x (D) 72mm. The weight is 0.24kg. It has an IP20 degree of protection (as per IEC/EN 60529) on its terminals. The operating temperature is -30°C to 70°C. The storage temperature is -40°C to 80°C.
  • Relative Humidity : 95-95 % 55-55 °C
  • [Ue] Rated Operational Voltage : 240 V AC 50/60 Hz between phases || 415 V AC 50/60 Hz between phases || 440 V AC 50/60 Hz between phases || <= 125 V DC
  • Tropicalisation : 2 IEC 60068-1
  • [Uimp] Rated Impulse Withstand Voltage : 6 kVEN/IEC 60947-2
  • Heat Dissipation : 5.4-5.4 W 415 V - 6 A
  • Product Or Component Type : miniature circuit-breaker
  • Utilisation Category : category A EN/IEC 60947-2
  • Standards : EN/IEC 60947-2
  • Trip Unit Technology : thermal-magnetic
  • [Ui] Rated Insulation Voltage : 500 V AC 50/60 Hz EN/IEC 60947-2
  • Local Signalling : ON/OFF indication
  • Mechanical Durability : 20000 cycles
  • Net Weight : 0.24 kg
  • Poles Description : 2P
  • Limitation Class : 3
  • Number Of Protected Poles : 2
  • Ambient Air Temperature For Operation : -30-70 °C
  • Electrical Durability : 10000 cycles
  • Suitability For Isolation : yes EN/IEC 60947-2
  • Line Rated Current : 6 A 50 °C EN/IEC 60947-2
  • Overvoltage Category : IV
  • Maximum Width : 36 mm
  • Control Type : toggle
  • Magnetic Tripping Limit : 12 x In +/- 20 % AC || 17 x In +/- 20 % DC
  • [Ics] Rated Service Breaking Capacity : 7.5 kA 75 % EN/IEC 60947-2 - 415 V AC 50/60 Hz || 16 kA 75 % EN/IEC 60947-2 - 240 V AC 50/60 Hz || 4.5 kA 75 % EN/IEC 60947-2 - 440 V AC 50/60 Hz || 20 kA 100 % EN/IEC 60947-2 - <= 125 V DC
  • Device Application : distribution
  • Network Type : DC || AC
  • Wire Stripping Length : 14 mm top or bottom
  • Product Certifications : EAC || KC || CCC
  • Provision For Padlocking : padlockable
  • Maximum Depth : 72 mm
  • Mounting Mode : clip-on
  • Maximum Height : 81 mm
  • Device Short Name : C60N
  • Pollution Degree : 3 EN/IEC 60947-2
  • Contact Position Indicator : yes
  • Network Frequency : 50/60 Hz
  • Ambient Air Temperature For Storage : -40-80 °C
  • Connections - Terminals : tunnel type terminal top or bottom) 1-25 mm² - rigid || tunnel type terminal top or bottom) 1-25 mm² - flexible || tunnel type terminal top or bottom) 1-25 mm² - flexible with ferrule
  • Range Of Product : Multi 9
  • Breaking Capacity : 20 kA Icu <= 125 V DC EN/IEC 60947-2 || 10 kA Icu 415 V AC 50/60 Hz between phases EN/IEC 60947-2 || 20 kA Icu 240 V AC 50/60 Hz between phases EN/IEC 60947-2 || 6 kA Icu 440 V AC 50/60 Hz between phases EN/IEC 60947-2
  • Mounting Support : DIN rail
  • 9 Mm Pitches : 4
  • Range : Multi 9
  • Color : Gray
  • Curve Code : D
  • Product Name : Multi 9 C60
  • Tightening Torque : 2-2 N.m top or bottom
  • Earth-Leakage Protection : separate block
  • Ip Degree Of Protection : IP20IEC 60529 || IP40 modular enclosure)IEC 60529
  • Breaking Capacity Code : N