Schneider Electric at Mayer

Multi9 - C60N - MCB - 2P - 6 A - C Curve - 415 V - 10 kA

MINIATURE CIRCUIT BREAKER 240/

SQDM9F11206 M9F11206 785901669180
206.32 / EA
  • Certifications: CCC, EAC, KC
  • Depth: 72 mm
  • Height: 81 mm
  • Line Rated Current: 50 °C, 6 A
  • Mounting Type: Clip-On
  • Net Weight: 0.24 kg
  • Operating Temperature: -30-70 °C
  • Standard: EN/IEC 60947-2
  • Storage Temperature: -40-80 °C
  • Strip Length: 14 mm
  • Width: 36 mm
This Multi9 C60N is a low voltage miniature circuit breaker (MCB). It is a 2P circuit breaker with 2 protected poles, 6A rated current and C tripping curve. The rated short circuit breaking capacity goes up to 10kA at 415VAC conforming to EN/IEC 60947-2 standard. This product complies with both industrial standard EN/IEC 60898-1 and residential standard EN/IEC 60947-2. It has been designed to offer enhanced protection by preventing, protecting people and equipment from electrical threats. This product protects from short circuit, earth leakage and overload. Its fast closing mechanism, overvolatge resistance and high performance limitation improve its service life. This product is dedicated for original equipment manufacturers (OEM) and control panel builders. It has an electrical endurance going up to 10000 cycles and a mechanical endurance going up to 20000 cycles. The Ue operational voltage is 240VAC. The Ui rated insulation voltage is 500VAC. The Uimp rated impulse withstand voltage is 6kV. The operating frequency is 50Hz or 60Hz. The product can be clipped on a DIN rail. Its width is 4 pitches of 9mm. Pollution degree is 3. Overvoltage category is IV. The product colour is light grey (RAL7035). The dimensions are (W) 36mm x (H) 81mm x (D) 72mm. The weight is 0.24kg. It has an IP20 degree of protection (as per IEC/EN 60529) on its terminals. The operating temperature is -30°C to 70°C. The storage temperature is -40°C to 80°C.
  • Product Description
  • Specifications
This Multi9 C60N is a low voltage miniature circuit breaker (MCB). It is a 2P circuit breaker with 2 protected poles, 6A rated current and C tripping curve. The rated short circuit breaking capacity goes up to 10kA at 415VAC conforming to EN/IEC 60947-2 standard. This product complies with both industrial standard EN/IEC 60898-1 and residential standard EN/IEC 60947-2. It has been designed to offer enhanced protection by preventing, protecting people and equipment from electrical threats. This product protects from short circuit, earth leakage and overload. Its fast closing mechanism, overvolatge resistance and high performance limitation improve its service life. This product is dedicated for original equipment manufacturers (OEM) and control panel builders. It has an electrical endurance going up to 10000 cycles and a mechanical endurance going up to 20000 cycles. The Ue operational voltage is 240VAC. The Ui rated insulation voltage is 500VAC. The Uimp rated impulse withstand voltage is 6kV. The operating frequency is 50Hz or 60Hz. The product can be clipped on a DIN rail. Its width is 4 pitches of 9mm. Pollution degree is 3. Overvoltage category is IV. The product colour is light grey (RAL7035). The dimensions are (W) 36mm x (H) 81mm x (D) 72mm. The weight is 0.24kg. It has an IP20 degree of protection (as per IEC/EN 60529) on its terminals. The operating temperature is -30°C to 70°C. The storage temperature is -40°C to 80°C.
  • Relative Humidity : 95-95 % 55-55 °C
  • Breaking Capacity Code : N
  • Maximum Width : 36 mm
  • Ambient Air Temperature For Operation : -30-70 °C
  • Heat Dissipation : 5.4-5.4 W 415 V - 6 A
  • Network Type : AC || DC
  • Tropicalisation : 2 IEC 60068-1
  • Local Signalling : ON/OFF indication
  • Connections - Terminals : tunnel type terminal top or bottom) 1-25 mm² - rigid || tunnel type terminal top or bottom) 1-25 mm² - flexible || tunnel type terminal top or bottom) 1-25 mm² - flexible with ferrule
  • Suitability For Isolation : yes EN/IEC 60947-2
  • Contact Position Indicator : yes
  • Ip Degree Of Protection : IP20IEC 60529 || IP40 modular enclosure)IEC 60529
  • [Ui] Rated Insulation Voltage : 500 V AC 50/60 Hz EN/IEC 60947-2
  • Pollution Degree : 3 EN/IEC 60947-2
  • Utilisation Category : category A EN/IEC 60947-2
  • Maximum Height : 81 mm
  • Poles Description : 2P
  • [Ue] Rated Operational Voltage : 240 V AC 50/60 Hz between phases || 415 V AC 50/60 Hz between phases || 440 V AC 50/60 Hz between phases || <= 125 V DC
  • Overvoltage Category : IV
  • Provision For Padlocking : padlockable
  • Limitation Class : 3
  • Range : Multi 9
  • Electrical Durability : 10000 cycles
  • [Ics] Rated Service Breaking Capacity : 7.5 kA 75 % EN/IEC 60947-2 - 415 V AC 50/60 Hz || 16 kA 75 % EN/IEC 60947-2 - 240 V AC 50/60 Hz || 4.5 kA 75 % EN/IEC 60947-2 - 440 V AC 50/60 Hz || 20 kA 100 % EN/IEC 60947-2 - <= 125 V DC
  • Ambient Air Temperature For Storage : -40-80 °C
  • 9 Mm Pitches : 4
  • Mounting Mode : clip-on
  • Mounting Support : DIN rail
  • Control Type : toggle
  • Product Or Component Type : miniature circuit-breaker
  • Device Short Name : C60N
  • Wire Stripping Length : 14 mm top or bottom
  • Color : Gray
  • Trip Unit Technology : thermal-magnetic
  • Breaking Capacity : 20 kA Icu <= 125 V DC EN/IEC 60947-2 || 10 kA Icu 415 V AC 50/60 Hz between phases EN/IEC 60947-2 || 20 kA Icu 240 V AC 50/60 Hz between phases EN/IEC 60947-2 || 6 kA Icu 440 V AC 50/60 Hz between phases EN/IEC 60947-2
  • Mechanical Durability : 20000 cycles
  • Number Of Protected Poles : 2
  • Tightening Torque : 2-2 N.m top or bottom
  • Product Certifications : EAC || KC || CCC
  • Product Name : Multi 9 C60
  • Earth-Leakage Protection : separate block
  • Magnetic Tripping Limit : 8.5 x In +/- 20 % AC || 12 x In +/- 20 % DC
  • Network Frequency : 50/60 Hz
  • Standards : EN/IEC 60947-2
  • Maximum Depth : 72 mm
  • Range Of Product : Multi 9
  • Curve Code : C
  • Line Rated Current : 6 A 50 °C EN/IEC 60947-2
  • Net Weight : 0.24 kg
  • [Uimp] Rated Impulse Withstand Voltage : 6 kVEN/IEC 60947-2
  • Device Application : distribution