Multi9 - C60N - MCB - 2P - 50 A - C Curve - 415 V - 10 kA

Multi9 - C60N - MCB - 2P - 50 A - C Curve - 415 V - 10 kA

SQDM9F11250 M9F11250 785901234777
226.26 / EA
  • Amperage: 50 A
  • Certifications: CCC, EAC, KC
  • Country of Origin: France
  • Depth: 2.83 in, 72 mm
  • Height: 3.19 in, 81 mm
  • Mounting Type: Clip-On
  • Standard: EN/IEC 60947-2
  • Strip Length: 0.55 in, 14 mm
  • Voltage: 125 V, 240 V, 415 V, 440 V
  • Weight: 0.24 kg, 0.53 lb
  • Width: 1.42 in, 36 mm
This Multi9 C60N is a low voltage miniature circuit breaker (MCB). It is a 2P circuit breaker with 2 protected poles, 50A rated current and C tripping curve. The rated short circuit breaking capacity goes up to 10kA at 415VAC conforming to EN/IEC 60947-2 standard. This product complies with both industrial standard EN/IEC 60898-1 and residential standard EN/IEC 60947-2. It has been designed to offer enhanced protection by preventing, protecting people and equipment from electrical threats. This product protects from short circuit, earth leakage and overload. Its fast closing mechanism, overvolatge resistance and high performance limitation improve its service life. This product is dedicated for original equipment manufacturers (OEM) and control panel builders. It has an electrical endurance going up to 10000 cycles and a mechanical endurance going up to 20000 cycles. The Ue operational voltage is 240VAC. The Ui rated insulation voltage is 500VAC. The Uimp rated impulse withstand voltage is 6kV. The operating frequency is 50Hz or 60Hz. The product can be clipped on a DIN rail. Its width is 4 pitches of 9mm. Pollution degree is 3. Overvoltage category is IV. The product colour is light grey (RAL7035). The dimensions are (W) 36mm x (H) 81mm x (D) 72mm. The weight is 0.24kg. It has an IP20 degree of protection (as per IEC/EN 60529) on its terminals. The operating temperature is -30°C to 70°C. The storage temperature is -40°C to 80°C.
  • Product Description
  • Specifications
This Multi9 C60N is a low voltage miniature circuit breaker (MCB). It is a 2P circuit breaker with 2 protected poles, 50A rated current and C tripping curve. The rated short circuit breaking capacity goes up to 10kA at 415VAC conforming to EN/IEC 60947-2 standard. This product complies with both industrial standard EN/IEC 60898-1 and residential standard EN/IEC 60947-2. It has been designed to offer enhanced protection by preventing, protecting people and equipment from electrical threats. This product protects from short circuit, earth leakage and overload. Its fast closing mechanism, overvolatge resistance and high performance limitation improve its service life. This product is dedicated for original equipment manufacturers (OEM) and control panel builders. It has an electrical endurance going up to 10000 cycles and a mechanical endurance going up to 20000 cycles. The Ue operational voltage is 240VAC. The Ui rated insulation voltage is 500VAC. The Uimp rated impulse withstand voltage is 6kV. The operating frequency is 50Hz or 60Hz. The product can be clipped on a DIN rail. Its width is 4 pitches of 9mm. Pollution degree is 3. Overvoltage category is IV. The product colour is light grey (RAL7035). The dimensions are (W) 36mm x (H) 81mm x (D) 72mm. The weight is 0.24kg. It has an IP20 degree of protection (as per IEC/EN 60529) on its terminals. The operating temperature is -30°C to 70°C. The storage temperature is -40°C to 80°C.
  • Environment
    • Pollution Degree : 3 EN/IEC 60947-2
    • Overvoltage Category : IV
    • Ambient Air Temp For Storage : -40…176 °F (-40…80 °C)
    • Tropicalisation : 2 IEC 60068-1
    • IP Degree Of Protection : IP20IEC 60529 || IP40 modular enclosure)IEC 60529
    • Ambient Air Temp For Op : -22…158 °F (-30…70 °C)
    • Heat Dissipation : 9.6 W 415 V - 50 A
    • Relative Humidity : 95 % 131 °F (55 °C)
  • Offer Sustainability
    • Mercury Free : Yes
    • REACh Free Of SVHC : Yes
    • Green Premium Status : Green Premium product
    • Halogen Content Performance : Halogen free product
    • WEEE : The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
    • EU RoHs Directive : Compliant
  • Complementary
    • Mounting Mode : Clip-on
    • Magnetic Tripping Limit : 8.5 x In +/- 20 % AC || 12 x In +/- 20 % DC
    • Colour : Gray
    • Ue Rated Operational Voltage : 240 V AC 50/60 Hz between phases || 415 V AC 50/60 Hz between phases || 440 V AC 50/60 Hz between phases || <= 125 V DC
    • Product Weight : 0.53 lb(US) (0.24 kg)
    • Width : 1.42 in (36 mm)
    • Connections - Terminals : Tunnel type terminal top or bottom) 0.00…0.05 in² (1.5…35 mm²) - rigid || Tunnel type terminal top or bottom) 0.00…0.05 in² (1.5…35 mm²) - flexible || Tunnel type terminal top or bottom) 0.00…0.05 in² (1.5…35 mm²) - flexible with ferrule
    • Depth : 2.83 in (72 mm)
    • Uimp Rated Imp Wstd Voltage : 6 kVEN/IEC 60947-2
    • 9 mm Pitches : 4
    • Ui Rated Insulation Voltage : 500 V AC 50/60 Hz EN/IEC 60947-2
    • Contact Position Indicator : Yes
    • Control Type : Toggle
    • Provision For Padlocking : Padlockable
    • Mounting Support : DIN rail
    • Ics Rated Service Breaking Cap : 7.5 kA 75 % EN/IEC 60947-2 - 415 V AC 50/60 Hz || 16 kA 75 % EN/IEC 60947-2 - 240 V AC 50/60 Hz || 4.5 kA 75 % EN/IEC 60947-2 - 440 V AC 50/60 Hz || 20 kA 100 % EN/IEC 60947-2 - <= 125 V DC
    • Network Frequency : 50/60 Hz
    • Mechanical Durability : 20000 cycles
    • Limitation Class : 3
    • Local Signalling : ON/OFF indication
    • Earth-Leakage Protection : Separate block
    • Tightening Torque : 30.98 lbf.in (3.5 N.m) top or bottom
    • Height : 3.19 in (81 mm)
    • Wire Stripping Length : 0.55 in (14 mm) top or bottom
    • Electrical Durability : 10000 cycles
  • Main
    • Curve Code : C
    • Poles Description : 2P
    • Network Type : AC || DC
    • Product Or Component Type : Miniature circuit-breaker
    • Device Application : Distribution
    • Product Name : Multi 9 C60
    • Standards : EN/IEC 60947-2
    • Range : Multi 9
    • Suitability For ISOlation : Yes EN/IEC 60947-2
    • In Rated Current : 50 A 122 °F (50 °C) EN/IEC 60947-2
    • Trip Unit Technology : Thermal-magnetic
    • Device Short Name : C60N
    • Product Certifications : EAC || KC || CCC
    • Utilisation Category : Category A EN/IEC 60947-2
    • Number Of Protected Poles : 2
    • Breaking Capacity : 20 kA Icu <= 125 V DC EN/IEC 60947-2 || 10 kA Icu 415 V AC 50/60 Hz between phases EN/IEC 60947-2 || 20 kA Icu 240 V AC 50/60 Hz between phases EN/IEC 60947-2 || 6 kA Icu 440 V AC 50/60 Hz between phases EN/IEC 60947-2
  • Ordering And Shipping Details
    • Country Of Origin : FR
    • Category : 00908 - C60N SUPPLEMENTARY PROTECTORS
    • Nbr. Of Units In Pkg. : 1
    • Discount Schedule : DE2
    • Returnability : No
    • GTIN : 00785901234777