Multi9 - C60L - MCB - 3P - 2 A - C Curve - 415 V - 25 kA

Multi9 - C60L - MCB - 3P - 2 A - C Curve - 415 V - 25 kA

SQDM9F17302 M9F17302 360648057809
0.00 / EA
  • Certifications: CCC, EAC
  • Depth: 72 mm
  • Height: 81 mm
  • Line Rated Current: 2 A, 50 °C
  • Mounting Type: Clip-On
  • Net Weight: 0.36 kg
  • Operating Temperature: -30-70 °C
  • Standard: EN/IEC 60947-2
  • Storage Temperature: -40-80 °C
  • Strip Length: 14 mm
  • Width: 54 mm
This Multi9 C60L is a low voltage miniature circuit breaker (MCB). It is a 3P circuit breaker with 3 protected poles, 2A rated current and C tripping curve. The rated short circuit breaking capacity goes up to 25kA at 415VAC conforming to EN/IEC 60947-2 standard. This product complies with both industrial standard EN/IEC 60898-1 and residential standard EN/IEC 60947-2. It has been designed to offer enhanced protection by preventing, protecting people and equipment from electrical threats. This product protects from short circuit, earth leakage and overload. Its fast closing mechanism, overvolatge resistance and high performance limitation improve its service life. This product is dedicated for original equipment manufacturers (OEM) and control panel builders. It has an electrical endurance going up to 10000 cycles and a mechanical endurance going up to 20000 cycles. The Ue operational voltage is 240VAC. The Ui rated insulation voltage is 500VAC. The Uimp rated impulse withstand voltage is 6kV. The operating frequency is 50Hz or 60Hz. The product can be clipped on a DIN rail. Its width is 6 pitches of 9mm. Pollution degree is 3. Overvoltage category is IV. The product colour is light grey (RAL7035). The dimensions are (W) 54mm x (H) 81mm x (D) 72mm. The weight is 0.36kg. It has an IP20 degree of protection (as per IEC/EN 60529) on its terminals. The operating temperature is -30°C to 70°C. The storage temperature is -40°C to 80°C.
  • Product Description
  • Specifications
This Multi9 C60L is a low voltage miniature circuit breaker (MCB). It is a 3P circuit breaker with 3 protected poles, 2A rated current and C tripping curve. The rated short circuit breaking capacity goes up to 25kA at 415VAC conforming to EN/IEC 60947-2 standard. This product complies with both industrial standard EN/IEC 60898-1 and residential standard EN/IEC 60947-2. It has been designed to offer enhanced protection by preventing, protecting people and equipment from electrical threats. This product protects from short circuit, earth leakage and overload. Its fast closing mechanism, overvolatge resistance and high performance limitation improve its service life. This product is dedicated for original equipment manufacturers (OEM) and control panel builders. It has an electrical endurance going up to 10000 cycles and a mechanical endurance going up to 20000 cycles. The Ue operational voltage is 240VAC. The Ui rated insulation voltage is 500VAC. The Uimp rated impulse withstand voltage is 6kV. The operating frequency is 50Hz or 60Hz. The product can be clipped on a DIN rail. Its width is 6 pitches of 9mm. Pollution degree is 3. Overvoltage category is IV. The product colour is light grey (RAL7035). The dimensions are (W) 54mm x (H) 81mm x (D) 72mm. The weight is 0.36kg. It has an IP20 degree of protection (as per IEC/EN 60529) on its terminals. The operating temperature is -30°C to 70°C. The storage temperature is -40°C to 80°C.
  • Limitation Class : 3
  • Standards : EN/IEC 60947-2
  • Contact Position Indicator : yes
  • Mounting Support : DIN rail
  • Earth-Leakage Protection : separate block
  • Breaking Capacity Code : L
  • Wire Stripping Length : 14 mm top or bottom
  • Maximum Width : 54 mm
  • Curve Code : C
  • Electrical Durability : 10000 cycles
  • [Ics] Rated Service Breaking Capacity : 25 kA 50 % EN/IEC 60947-2 - 240 V AC 50/60 Hz || 12.5 kA 50 % EN/IEC 60947-2 - 415 V AC 50/60 Hz || 10 kA 50 % EN/IEC 60947-2 - 440 V AC 50/60 Hz || 50 kA 100 % EN/IEC 60947-2 - <= 125 V DC
  • Product Certifications : EAC || CCC
  • Breaking Capacity : 50 kA Icu <= 125 V DC EN/IEC 60947-2 || 50 kA Icu 240 V AC 50/60 Hz between phases EN/IEC 60947-2 || 25 kA Icu 415 V AC 50/60 Hz between phases EN/IEC 60947-2 || 20 kA Icu 440 V AC 50/60 Hz between phases EN/IEC 60947-2
  • Magnetic Tripping Limit : 8.5 x In +/- 20 % AC || 12 x In +/- 20 % DC
  • Heat Dissipation : 7.8-7.8 W 415 V - 2 A
  • Ambient Air Temperature For Operation : -30-70 °C
  • Network Frequency : 50/60 Hz
  • Pollution Degree : 3 EN/IEC 60947-2
  • Control Type : toggle
  • Suitability For Isolation : yes EN/IEC 60947-2
  • [Ui] Rated Insulation Voltage : 500 V AC 50/60 Hz EN/IEC 60947-2
  • Mounting Mode : clip-on
  • Device Short Name : C60L
  • Mechanical Durability : 20000 cycles
  • Ip Degree Of Protection : IP20IEC 60529 || IP40 modular enclosure)IEC 60529
  • Trip Unit Technology : thermal-magnetic
  • Maximum Depth : 72 mm
  • Ambient Air Temperature For Storage : -40-80 °C
  • Tightening Torque : 2-2 N.m top or bottom
  • Provision For Padlocking : padlockable
  • [Uimp] Rated Impulse Withstand Voltage : 6 kVEN/IEC 60947-2
  • Overvoltage Category : IV
  • Color : Gray
  • Relative Humidity : 95-95 % 55-55 °C
  • Connections - Terminals : tunnel type terminal top or bottom) 1-25 mm² - rigid || tunnel type terminal top or bottom) 1-25 mm² - flexible || tunnel type terminal top or bottom) 1-25 mm² - flexible with ferrule
  • Number Of Protected Poles : 3
  • Local Signalling : ON/OFF indication
  • Net Weight : 0.36 kg
  • [Ue] Rated Operational Voltage : 240 V AC 50/60 Hz between phases || 415 V AC 50/60 Hz between phases || 440 V AC 50/60 Hz between phases || <= 125 V DC
  • Device Application : distribution
  • 9 Mm Pitches : 6
  • Product Name : Multi 9 C60
  • Tropicalisation : 2 IEC 60068-1
  • Poles Description : 3P
  • Utilisation Category : category A EN/IEC 60947-2
  • Range Of Product : Multi 9
  • Network Type : AC || DC
  • Range : Multi 9
  • Product Or Component Type : miniature circuit-breaker
  • Line Rated Current : 2 A 50 °C EN/IEC 60947-2
  • Maximum Height : 81 mm